background image

361813-UIM-A-0208

12

Unitary Products Group

SECTION VI: EVACUATION

It will be necessary to evacuate the system to 500 microns or less. If a
leak is suspected, leak test with dry nitrogen to locate the leak. Repair
the leak and test again. 

To verify that the system has no leaks, simply close the valve to the vac-
uum pump suction to isolate the pump and hold the system under vac-
uum. Watch the micron gauge for a few minutes. If the micron gauge
indicates a steady and continuous rise, it’s an indication of a leak. If the
gauge shows a rise, then levels off after a few minutes and remains
fairly constant, its an indication that the system is leak free but still con-
tains moisture and may require further evacuation if the reading is
above 500 microns.

SECTION VII: SYSTEM CHARGE

The factory charge in the outdoor unit includes enough charge for the
unit, a 15 ft. line set and the smallest indoor coil match-up. Some indoor
coil matches may require additional charge. See tabular data sheet pro-
vided in unit literature packet for charge requirements.

The “TOTAL SYSTEM CHARGE” must be permanently stamped on the
unit data plate.

Total system charge is determined as follows:

1.

Determine outdoor unit charge from tabular data sheet.

2.

Determine indoor coil adjustment from tabular data sheet.

3.

Calculate the line charge using the tabular data sheet if line length
is greater than 15 feet.

4.

Total system charge = item 1 + item 2 + item 3.

5.

Permanently stamp the unit data plate with the total amount of
refrigerant in the system.

If a calibrated charging cylinder or accurate weighing device is avail-
able, add refrigerant accordingly. Otherwise, model-specific charging
charts are provided in Tables 3 - 9 for cooling mode only. There is no
accurate method for charging these units in the heating mode. If charg-
ing is required during the heating mode, the unit must be evacuated
and charge weighed in according to the rating plate. If TXV indoor coils
are used with the 2 through 3-1/2 ton models, the following subcooling
charging method must be used. Superheat charging charts are not valid
with TXV equipped systems.

Subcooling Charging Method

For the 

heating operation

, there is no accurate subcooling method for

charging the unit. If unit charging is required during heating operation,
the unit must be evacuated and charge weighed-in per the marking on
the rating plate.

For the 

cooling operation

, the recommended subcooling is typically

around 10°F. This may vary greatly based on each unique system.

1.

Set the system running in the cooling mode by setting the thermo-
stat at least 6°F below the room temperature.

2.

Operate the system for a minimum of 15-20 minutes.

3.

Refer to the tabular data sheet for the recommended airflow and
verify this indoor airflow (it should be about 400 SCFM per ton).

4.

Measure the liquid refrigerant pressure P and temperature T at the
service valve.

5.

Calculate the saturated liquid temperature ST from Table 2 on the
last page of this document.

6.

Subcooling temperature TC = Saturated Temperature (ST) - Liquid
Temp (T).

Add charge if the calculated subcooling temperature TC in Step 6 is
lower than the recommended level. Remove and recover the refrigerant
if the subcooling TC is higher than the recommended level.

See rating plate for unit specific subcooling chart.

See Figure 12 to trace the flow of refrigerant through the system.

Do not leave the system open to the atmosphere.

Refrigerant charging should only be carried out by a qualified air
conditioning contractor.

Compressor damage will occur if system is improperly charged. On
new system installations, charge system per tabular data sheet for
the matched coil and follow guidelines in this instruction.

Example: The pressure P and temperature T measured at the liquid 
service port is 360 Psig and 93°F. From Table 13, the saturated tem-
perature for 360 Psig is 109°. The subcooling temperature TC = 
109°-93°=16°F

 FIGURE 12: 

Heat Pump Flow Diagram

.

TXV
(Cooling)

SHOWN IN COOLING POSITION.

COOLING CYCLE FLOW

HEATING CYCLE FLOW

INDOOR COIL

4-WAY
REVERSING
VALVE

SUCTION
ACCUMULATOR

COMPRESSOR

OUTDOOR
COIL

FIELD CONNECTED LINE

FILTER DRYER
(Solid core)

LIQUID
SENSOR

FIELD CONNECTED LINE

TXV
(Heating)

Summary of Contents for HC3A SERIES

Page 1: ...ry It is also used to alert against unsafe practices and hazards involving only property dam age Improper installation may create a condition where the operation of the product could cause personal in...

Page 2: ...to be installed on a hot sun exposed roof or a black topped ground area the unit should be raised sufficiently above the roof or ground to avoid taking the accumulated layer of hot air into the outdo...

Page 3: ...stalling tubing of longer lengths and elevation differences NOTE Using a larger than specified line size could result in oil return problems Using too small a line will result in loss of capacity and...

Page 4: ...coil Braze the vapor line to the evaporator vapor connection After the connection has cooled slide the grommet back into original position Refer to the Tabular Data Sheet for proper vapor line siz ing...

Page 5: ...se soft solder Install the TXV bulb to the vapor line near the equalizer line using the two bulb clamps furnished with the TXV assembly Ensure the bulb is making maximum contact Refer to TXV installat...

Page 6: ...ON CONTROL A dehumidification control accessory 2HU06700124 may be used with variable speed air handlers or furnaces in high humidity areas This control works with the variable speed indoor unit to pr...

Page 7: ...r W Auxiliary Heat BS Bonnet Sensor BSG Bonnet Sensor YORKGUARD VI CONTROL SINGLE STAGE HEAT PUMP 1 H 3 YMB YZB OD MODELS Part Numbers SAP Legacy 126768 031 09137 18395 031 01996 340512 031 09178 1 C...

Page 8: ...E Emergency Heat W2 Second Stage Heat B O Switch on Thermostat must be in the O position C 24 Volt Common Y1 First Stage Compressor O B Reversing Valve L Malfunction Light Y2 Second Stage Compressor G...

Page 9: ...the O position C 24 Volt Common Y1 First Stage Compressor O B Reversing Valve L Malfunction Light Y2 Second Stage Compressor G Fan DN22U00124 THERMOSTAT E Emergency Heat AUX Auxiliary Heat R 24 Volt...

Page 10: ...mergency Heat W2 Second Stage Heat B O Switch on Thermostat must be in the O position C 24 Volt Common Y1 First Stage Compressor O B Reversing Valve L Malfunction Light Y2 Second Stage Compressor G Fa...

Page 11: ...must be in the O position C 24 Volt Common Y1 First Stage Compressor O B Reversing Valve L Malfunction Light Y2 Second Stage Compressor G Fan DN22U00124 THERMOSTAT E Emergency Heat AUX Auxiliary Heat...

Page 12: ...ls the following subcooling charging method must be used Superheat charging charts are not valid with TXV equipped systems Subcooling Charging Method For the heating operation there is no accurate sub...

Page 13: ...ed with a crankcase heater to prevent the migration of refrigerant to the compressor during the OFF cycle The heater is energized only when the unit is not running If the main switch is disconnected f...

Page 14: ...e Printed in U S A 361813 UIM A 0208 Copyright by Unitary Products Group 2008 All rights reserved Supersedes 170761 UIM D 1106 Unitary 5005 Norman Product York OK Group Drive 73069 SECTION X WIRING DI...

Reviews: