036-21023-005 Rev. A (0802)

14

Unitary Products Group

Multipliers for determining the performance with other indoor sections.

COOLING PERFORMANCE DATA - 

LOW CFM 1-CYLINDER OPERATION

AIR CONDITIONER MODEL NO.

H4TS060S06

INDOOR COIL MODEL NO.

G2FN1VSD20

CONDENSER 

ENTERING AIR 

TEMPERATURE

ID CFM

1100

1200

1300

ID DB (°F)

85

80

75

70

85

80

75

70

85

80

75

70

ID WB (°F)

72

67

62

57

72

67

62

57

72

67

62

57

75

T.C.

39.8

36.4

33.1

30.0

40.1

36.8

33.5

30.4

40.5

37.2

33.8

30.9

S.C.

26.6

26.6

26.9

26.8

27.8

27.9

28.1

28.1

29.1

29.1

29.3

29.3

K.W

1.94

1.94

1.95

1.94

1.97

1.97

1.98

1.97

2.00

2.01

2.01

2.01

85

T.C.

37.8

34.5

31.4

28.4

38.1

34.9

31.8

28.9

38.3

35.2

32.1

29.4

S.C.

25.9

25.8

26.2

26.1

27.1

27.2

27.4

27.3

28.3

28.3

28.5

28.5

K.W

2.15

2.22

2.12

2.10

2.19

2.18

2.16

2.15

2.21

2.21

2.19

2.17

95

T.C.

35.7

32.6

29.7

26.9

35.9

33.0

30.0

27.5

36.3

33.3

30.2

28.0

S.C.

25.2

25.2

25.4

25.3

26.4

26.4

26.6

26.6

27.7

27.6

27.8

27.1

K.W

2.35

2.32

2.29

2.26

2.39

2.36

2.33

2.30

2.42

2.39

2.36

2.33

105

T.C.

33.5

30.7

27.9

25.4

33.9

31.0

28.1

25.9

34.1

31.2

28.5

26.4

S.C.

24.4

24.4

24.6

24.6

25.7

25.6

25.8

25.1

26.9

26.8

27.0

25.5

K.W

2.53

2.50

2.45

2.40

2.57

2.53

2.49

2.45

2.61

2.57

2.52

2.49

115

T.C.

31.4

28.7

26.0

23.9

31.7

28.9

26.4

24.4

31.9

29.1

26.8

24.8

S.C.

23.8

23.7

23.8

23.1

25.0

24.8

25.0

23.6

26.1

26.0

26.0

24.0

K.W

2.71

2.66

2.59

2.54

2.75

2.70

2.64

2.59

2.79

2.74

2.68

2.63

125

T.C.

29.3

26.7

24.1

22.4

29.5

26.8

24.7

22.9

29.7

27.0

25.1

23.2

S.C.

23.2

23.0

23.0

21.6

24.3

24.0

24.2

22.1

25.3

25.2

25.0

22.5

K.W

2.89

2.82

2.74

2.68

2.93

2.87

2.80

2.74

2.97

2.91

2.83

2.78

NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

N1VSD20

G2FD060S24

1.00

1.00

1.07

F2FV060

1.00

1.00

1.07

F2RP/F2FP060

0.97

1.00

0.96

G1HD060

0.97

1.00

1.13

G1FA060S21,24

0.97

1.00

1.13

G2FD060S24

0.97

1.00

1.13

G1UA060S21,24

0.97

1.00

1.13

Variable Speed 

Furnace

Coil

T.C.

S.C.

KW

P1DUC20V096

G1FA060S21

1.00

1.00

1.11

P1DUC20V096

G1UA060S21

1.00

1.00

1.11

P1XUC20V095

G1FA060S21

1.00

1.00

1.12

P1XUC20V095

G1UA060S21

1.00

1.00

1.12

P1XUD20V112

G1FA060S24

1.00

1.00

1.07

P1XUD20V112

G1UA060S24

1.00

1.00

1.07

P1XUD20V112

G2FD060S24

1.00

1.00

1.07

P1XUD20V112

G2FD061H24

1.03

1.02

1.11

Summary of Contents for H4TS024

Page 1: ...ssor is protected against high and low pressure Hard start components are included to ensure start up under adverse conditions All models have standard crankcase heat for added protection OPTIMUM PERFORMANCE The solid state electronic con trolboard optimizes the compressor staging based on load requirements provides a 5 minute anti short cycle timer for the compressor and simplifies troubleshootin...

Page 2: ...P 1 1 1 1 1 FIN INCH 20 20 20 20 20 LIQUID LINE OD 3 8 3 8 3 8 3 8 3 8 VAPOR LINE OD 3 4 3 4 7 8 7 8 7 8 UNIT CHARGE LBS OZ 3 6 0 6 4 7 0 9 12 9 2 CHARGE PER FOOT OZ 68 68 70 70 70 OPERATING WEIGHT LBS 145 145 200 250 252 1 Rated in accordance with ARI Standard 110 utilizaton range A 2 Dual element fuses or HACR circuit breaker 3 The Unit Charge is correct for the outdoor unit matched indoor coil ...

Page 3: ...0 13 7 2 1185 35 0 26 0 11 3 G2FD042S21 1 770 20 0 16 0 15 0 13 7 2 1185 35 0 26 0 11 3 G2FD048S21 1 770 20 6 16 6 16 0 14 4 2 1185 36 0 26 6 12 5 H4TS048 N VSC16 5 7 5 10 15 20 21 G2FD048S21 1 1050 25 0 20 0 15 2 14 1 2 1605 47 5 35 0 10 4 N VSD20 5 7 5 10 15 20 24 G2FD048S24 1 1050 25 0 20 0 15 3 14 2 2 1570 47 5 35 0 10 5 G2FD060S24 1 1050 25 0 21 0 15 5 14 0 2 1570 49 5 37 0 10 7 H4TS060 N VSD...

Page 4: ...A048S17 1 670 15 0 12 2 14 0 12 7 2 1035 29 6 21 6 11 3 G2FD030S17 1 670 15 4 12 2 13 7 13 0 2 1035 29 8 21 6 11 0 G2FD036S17 1 670 15 0 12 0 14 1 13 2 2 1035 29 6 21 6 11 0 G2FD046S17 1 670 15 0 12 0 14 5 13 5 2 1035 29 6 21 6 11 2 P1XUC16V075 21 G1UA036S21 1 690 15 0 12 0 14 5 13 0 2 1065 29 6 21 6 11 0 G1FA036S21 1 690 15 0 12 0 14 5 13 0 2 1065 29 6 21 6 11 0 G1UA048S21 1 690 15 4 12 2 14 5 13...

Page 5: ...5 5 14 2 2 1200 37 0 27 0 11 6 H4TS048 P1XUC16V075 P1XUC20V095 P1DUC20V096 21 G1UA048S21 1 1050 24 0 19 0 14 5 13 5 2 1500 47 5 35 0 10 2 G1FA048S21 1 1050 24 0 19 0 14 5 13 5 2 1500 47 5 35 0 10 2 G1UA060S21 1 1050 25 0 20 0 14 7 13 3 2 1500 49 0 36 0 10 4 G1FA060S21 1 1050 25 0 20 0 14 7 13 3 2 1500 49 0 36 0 10 4 G2FD048S21 1 1050 24 0 19 0 14 7 13 9 2 1500 47 5 35 0 10 2 P1XUD20V112 24 G1UA060...

Page 6: ...10 4 9 6 8 8 K W 0 99 0 97 0 96 0 94 1 00 0 97 0 96 0 95 1 02 1 00 0 99 0 98 115 T C 12 4 11 3 10 5 9 7 12 5 11 6 10 7 9 8 12 6 11 7 10 8 9 9 S C 9 5 9 4 8 8 8 1 9 9 9 7 8 9 8 2 10 4 9 8 9 0 8 3 K W 1 05 1 03 1 01 1 00 1 06 1 03 1 02 1 00 1 08 1 07 1 05 1 03 125 T C 11 5 10 5 9 8 9 1 11 6 11 0 10 0 9 2 11 8 11 0 10 1 9 2 S C 9 2 9 1 8 2 7 6 9 6 9 3 8 3 7 7 10 1 9 2 8 4 7 8 K W 1 10 1 09 1 06 1 06 ...

Page 7: ...9 18 0 K W 2 17 2 11 2 06 2 00 2 19 2 13 2 08 2 03 2 21 2 16 2 10 2 06 115 T C 23 9 21 9 19 9 18 0 24 1 22 0 20 0 18 4 24 2 22 3 20 2 18 7 S C 16 0 16 0 16 2 16 1 16 6 16 6 16 8 16 7 17 2 17 3 17 3 17 0 K W 2 30 2 23 2 16 2 11 2 32 2 25 2 19 2 13 2 34 2 28 2 21 2 17 125 T C 22 3 20 4 18 7 16 7 22 5 20 4 18 7 17 3 22 6 20 8 18 8 17 5 S C 15 5 15 5 15 7 15 5 16 0 16 1 17 2 19 1 16 7 16 8 16 7 16 0 K...

Page 8: ...2 6 11 5 14 8 13 6 12 6 11 6 15 1 14 0 12 8 11 8 S C 12 1 11 5 10 3 9 6 12 4 11 3 10 5 9 5 12 5 11 5 10 5 9 7 K W 1 40 1 37 1 35 1 32 1 42 1 40 1 37 1 36 1 47 1 46 1 41 1 40 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1VSB12 G2FD030S17 0 91 0 90 1 02 N1VSB12 G2FD036S17 0 94 0 91 1 01 N1VSC16 G2FD036S21 0 94 0 99 0 99 F2FP040 ...

Page 9: ...4 8 22 5 29 3 27 2 24 8 22 5 29 7 27 6 25 1 23 0 S C 21 3 21 1 21 7 21 7 21 7 21 9 22 0 22 1 23 0 23 1 23 3 23 2 K W 3 93 3 83 3 62 3 78 3 94 3 85 3 78 3 69 4 00 3 90 3 81 3 75 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1VSB12 G2FD030S17 0 95 0 92 0 97 N1VSB12 G2FD036S17 0 98 0 94 1 00 N1VSC16 G2FD036S21 0 98 0 99 1 00 F2FP0...

Page 10: ... 14 1 18 4 16 9 15 5 14 2 18 6 17 1 15 9 14 6 S C 14 8 14 6 14 7 13 5 15 5 15 4 15 3 13 7 16 8 16 7 15 2 14 1 K W 1 72 1 72 1 70 1 68 1 73 1 73 1 72 1 70 1 77 1 77 1 76 1 75 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1VSB12 G2FD036S17 0 91 0 96 1 03 N1VSC16 G2FD042S21 0 97 0 96 1 02 N1VSC16 G2FD036S21 0 97 0 96 1 02 N1VSD20 ...

Page 11: ... 7 24 1 32 4 29 9 27 0 25 1 32 9 29 8 27 2 25 4 S C 23 3 23 3 23 3 23 3 24 6 24 8 24 8 24 6 26 0 25 6 25 7 24 2 K W 3 46 3 40 3 30 3 20 3 51 3 43 3 33 3 27 3 55 3 48 3 39 3 32 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1VSB12 G2FD036S17 0 94 0 96 1 06 N1VSC16 G2FD036S21 0 97 0 98 1 07 N1VSC16 G2FD042S21 0 97 0 98 1 08 N1VSD2...

Page 12: ... 19 3 19 1 18 7 17 3 K W 1 92 1 88 1 85 1 83 1 95 1 92 1 89 1 86 1 99 1 95 1 93 1 90 125 T C 21 4 19 4 17 4 16 3 21 4 19 7 17 8 16 6 21 6 19 7 18 5 16 8 S C 16 8 16 6 16 5 15 5 17 8 17 5 17 5 15 9 18 7 18 4 17 5 16 1 K W 2 03 1 98 1 94 1 92 2 06 2 02 1 98 1 96 2 09 2 05 2 03 1 99 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1V...

Page 13: ... 34 1 34 0 34 5 34 4 K W 5 13 4 95 4 78 4 61 5 21 5 03 4 87 4 71 5 28 5 11 4 95 4 79 125 T C 42 9 39 2 35 8 32 2 43 2 39 5 36 0 33 0 43 6 39 7 36 4 33 3 S C 30 2 30 1 31 0 30 3 31 7 31 5 31 9 32 6 33 1 32 9 33 3 32 9 K W 5 41 5 20 4 83 4 82 5 49 5 28 5 11 4 94 5 55 5 37 5 19 5 01 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1V...

Page 14: ... 33 9 31 0 28 1 25 9 34 1 31 2 28 5 26 4 S C 24 4 24 4 24 6 24 6 25 7 25 6 25 8 25 1 26 9 26 8 27 0 25 5 K W 2 53 2 50 2 45 2 40 2 57 2 53 2 49 2 45 2 61 2 57 2 52 2 49 115 T C 31 4 28 7 26 0 23 9 31 7 28 9 26 4 24 4 31 9 29 1 26 8 24 8 S C 23 8 23 7 23 8 23 1 25 0 24 8 25 0 23 6 26 1 26 0 26 0 24 0 K W 2 71 2 66 2 59 2 54 2 75 2 70 2 64 2 59 2 79 2 74 2 68 2 63 125 T C 29 3 26 7 24 1 22 4 29 5 26...

Page 15: ...7 0 61 8 56 7 51 8 47 4 S C 40 6 40 7 41 0 40 9 42 7 42 7 43 4 43 5 44 0 44 1 44 5 44 5 K W 6 03 5 77 5 54 5 31 6 15 5 90 5 65 5 45 6 21 5 97 5 71 5 49 115 T C 57 2 52 3 47 6 43 2 57 9 53 1 48 4 44 2 58 0 53 4 48 6 45 2 S C 39 3 39 2 39 6 39 5 41 7 41 9 42 0 41 9 42 6 42 9 43 1 43 6 K W 6 39 6 10 5 84 5 58 6 50 6 23 5 94 5 72 6 57 6 28 6 01 5 83 125 T C 53 5 48 9 44 5 40 4 54 4 50 0 45 3 41 4 54 2...

Page 16: ...rk OK Group Drive 73069 MATCHING INDOOR COMPONENTS G1UA 1 2 CASED UPFLOW G2FD MULTI POSITION UPFLOW HORIZONTAL AND DOWNFLOW Available with factory installed horizontal drain pan ADD ON COILS FOR FURNACE APPLICATIONS G1FA FULL CASED UPFLOW AIR HANDLERS FOR NON FURNACE APPLICATIONS N AH OR N VS MODULAR BLOWER UPFLOW HORIZONTAL AND DOWNFLOW F RC F FC OR F RC F FP FAN COIL UNITS UPFLOW HORIZONTAL G FD...

Reviews: