PHYSICAL AND ELECTRICAL DATA

MODEL

H4TS024

H4TS030

H4TS036

H4TS048

H4TS060

UNIT SUPPLY VOLTAGE

208/230-1-60

NORMAL VOLTAGE RANGE 

1

187 to 252

MIN. CIRCUIT AMPACITY

13.4

15.3

18.6

32.8

35.3

MAX. OVERCURRENT DEVICE AMPS 

2

20

25

30

50

60

COMPRESSOR TYPE

BRISTOL TS

COMPRESSOR AMPS

RATED LOAD

10.3

11.7

13.5

25.7

27.0

LOCKED ROTOR

64

65

84

135

147

CRANKCASE HEATER

YES

YES

YES

YES

YES

FAN MOTOR AMPS

RATED LOAD

.5

.5

.7

.7

1.5

FAN DIAMETER INCHES

18

18

24

24

24

FAN MOTOR

RATED HP

1/12

1/12

1/10

1/10

1/4

NOMINAL RPM

1100

1100

825

825

850

NOMINAL CFM

1850

1850

2800

2800

3200

COIL

FACE AREA SQ. FT

14.2

14.2

20.0

24.0

24.0

COIL ROWS DEEP

1

1

1

1

1

FIN / INCH

20

20

20

20

20

LIQUID LINE OD

3/8

3/8

3/8

3/8

3/8

VAPOR LINE OD

3/4

3/4

7/8

7/8

7/8

UNIT CHARGE, (LBS - OZ)

3

6 - 0 

6 - 4

7 - 0

9 - 12

9 - 2

CHARGE PER FOOT, OZ

.68

.68

.70

.70

.70

OPERATING WEIGHT LBS.

145

145

200

250

252

1

Rated in accordance with ARI Standard 110, utilizaton range “A”.

2

Dual element fuses or HACR circuit breaker.

3 The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or sub-

tract the amount of refrigerant calculated, using the difference in length multiplied by the per foot value.

48" OVERHEAD
CLEARANCE

C

B

A

5-1/2

2-3/8

3-1/8

VAPOR 
CONNECTION

LIQUID CONNECTION

AIR IN
4 SIDES

DIMENSIONS

UNIT

MODEL

DIMENSIONS

(INCHES)

REFRIGERANT 

CONNECTION 

LINE SIZE

1

B

C

Liquid

Vapor

024

30-1/8

24

24

3/8

3/4

030

30-1/8

24

24

036

31-7/8

35

35

7/8

048

37-7/8

35

35

060

37-7/8

35

35

Summary of Contents for H4TS024

Page 1: ...ssor is protected against high and low pressure Hard start components are included to ensure start up under adverse conditions All models have standard crankcase heat for added protection OPTIMUM PERFORMANCE The solid state electronic con trolboard optimizes the compressor staging based on load requirements provides a 5 minute anti short cycle timer for the compressor and simplifies troubleshootin...

Page 2: ...P 1 1 1 1 1 FIN INCH 20 20 20 20 20 LIQUID LINE OD 3 8 3 8 3 8 3 8 3 8 VAPOR LINE OD 3 4 3 4 7 8 7 8 7 8 UNIT CHARGE LBS OZ 3 6 0 6 4 7 0 9 12 9 2 CHARGE PER FOOT OZ 68 68 70 70 70 OPERATING WEIGHT LBS 145 145 200 250 252 1 Rated in accordance with ARI Standard 110 utilizaton range A 2 Dual element fuses or HACR circuit breaker 3 The Unit Charge is correct for the outdoor unit matched indoor coil ...

Page 3: ...0 13 7 2 1185 35 0 26 0 11 3 G2FD042S21 1 770 20 0 16 0 15 0 13 7 2 1185 35 0 26 0 11 3 G2FD048S21 1 770 20 6 16 6 16 0 14 4 2 1185 36 0 26 6 12 5 H4TS048 N VSC16 5 7 5 10 15 20 21 G2FD048S21 1 1050 25 0 20 0 15 2 14 1 2 1605 47 5 35 0 10 4 N VSD20 5 7 5 10 15 20 24 G2FD048S24 1 1050 25 0 20 0 15 3 14 2 2 1570 47 5 35 0 10 5 G2FD060S24 1 1050 25 0 21 0 15 5 14 0 2 1570 49 5 37 0 10 7 H4TS060 N VSD...

Page 4: ...A048S17 1 670 15 0 12 2 14 0 12 7 2 1035 29 6 21 6 11 3 G2FD030S17 1 670 15 4 12 2 13 7 13 0 2 1035 29 8 21 6 11 0 G2FD036S17 1 670 15 0 12 0 14 1 13 2 2 1035 29 6 21 6 11 0 G2FD046S17 1 670 15 0 12 0 14 5 13 5 2 1035 29 6 21 6 11 2 P1XUC16V075 21 G1UA036S21 1 690 15 0 12 0 14 5 13 0 2 1065 29 6 21 6 11 0 G1FA036S21 1 690 15 0 12 0 14 5 13 0 2 1065 29 6 21 6 11 0 G1UA048S21 1 690 15 4 12 2 14 5 13...

Page 5: ...5 5 14 2 2 1200 37 0 27 0 11 6 H4TS048 P1XUC16V075 P1XUC20V095 P1DUC20V096 21 G1UA048S21 1 1050 24 0 19 0 14 5 13 5 2 1500 47 5 35 0 10 2 G1FA048S21 1 1050 24 0 19 0 14 5 13 5 2 1500 47 5 35 0 10 2 G1UA060S21 1 1050 25 0 20 0 14 7 13 3 2 1500 49 0 36 0 10 4 G1FA060S21 1 1050 25 0 20 0 14 7 13 3 2 1500 49 0 36 0 10 4 G2FD048S21 1 1050 24 0 19 0 14 7 13 9 2 1500 47 5 35 0 10 2 P1XUD20V112 24 G1UA060...

Page 6: ...10 4 9 6 8 8 K W 0 99 0 97 0 96 0 94 1 00 0 97 0 96 0 95 1 02 1 00 0 99 0 98 115 T C 12 4 11 3 10 5 9 7 12 5 11 6 10 7 9 8 12 6 11 7 10 8 9 9 S C 9 5 9 4 8 8 8 1 9 9 9 7 8 9 8 2 10 4 9 8 9 0 8 3 K W 1 05 1 03 1 01 1 00 1 06 1 03 1 02 1 00 1 08 1 07 1 05 1 03 125 T C 11 5 10 5 9 8 9 1 11 6 11 0 10 0 9 2 11 8 11 0 10 1 9 2 S C 9 2 9 1 8 2 7 6 9 6 9 3 8 3 7 7 10 1 9 2 8 4 7 8 K W 1 10 1 09 1 06 1 06 ...

Page 7: ...9 18 0 K W 2 17 2 11 2 06 2 00 2 19 2 13 2 08 2 03 2 21 2 16 2 10 2 06 115 T C 23 9 21 9 19 9 18 0 24 1 22 0 20 0 18 4 24 2 22 3 20 2 18 7 S C 16 0 16 0 16 2 16 1 16 6 16 6 16 8 16 7 17 2 17 3 17 3 17 0 K W 2 30 2 23 2 16 2 11 2 32 2 25 2 19 2 13 2 34 2 28 2 21 2 17 125 T C 22 3 20 4 18 7 16 7 22 5 20 4 18 7 17 3 22 6 20 8 18 8 17 5 S C 15 5 15 5 15 7 15 5 16 0 16 1 17 2 19 1 16 7 16 8 16 7 16 0 K...

Page 8: ...2 6 11 5 14 8 13 6 12 6 11 6 15 1 14 0 12 8 11 8 S C 12 1 11 5 10 3 9 6 12 4 11 3 10 5 9 5 12 5 11 5 10 5 9 7 K W 1 40 1 37 1 35 1 32 1 42 1 40 1 37 1 36 1 47 1 46 1 41 1 40 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1VSB12 G2FD030S17 0 91 0 90 1 02 N1VSB12 G2FD036S17 0 94 0 91 1 01 N1VSC16 G2FD036S21 0 94 0 99 0 99 F2FP040 ...

Page 9: ...4 8 22 5 29 3 27 2 24 8 22 5 29 7 27 6 25 1 23 0 S C 21 3 21 1 21 7 21 7 21 7 21 9 22 0 22 1 23 0 23 1 23 3 23 2 K W 3 93 3 83 3 62 3 78 3 94 3 85 3 78 3 69 4 00 3 90 3 81 3 75 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1VSB12 G2FD030S17 0 95 0 92 0 97 N1VSB12 G2FD036S17 0 98 0 94 1 00 N1VSC16 G2FD036S21 0 98 0 99 1 00 F2FP0...

Page 10: ... 14 1 18 4 16 9 15 5 14 2 18 6 17 1 15 9 14 6 S C 14 8 14 6 14 7 13 5 15 5 15 4 15 3 13 7 16 8 16 7 15 2 14 1 K W 1 72 1 72 1 70 1 68 1 73 1 73 1 72 1 70 1 77 1 77 1 76 1 75 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1VSB12 G2FD036S17 0 91 0 96 1 03 N1VSC16 G2FD042S21 0 97 0 96 1 02 N1VSC16 G2FD036S21 0 97 0 96 1 02 N1VSD20 ...

Page 11: ... 7 24 1 32 4 29 9 27 0 25 1 32 9 29 8 27 2 25 4 S C 23 3 23 3 23 3 23 3 24 6 24 8 24 8 24 6 26 0 25 6 25 7 24 2 K W 3 46 3 40 3 30 3 20 3 51 3 43 3 33 3 27 3 55 3 48 3 39 3 32 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1VSB12 G2FD036S17 0 94 0 96 1 06 N1VSC16 G2FD036S21 0 97 0 98 1 07 N1VSC16 G2FD042S21 0 97 0 98 1 08 N1VSD2...

Page 12: ... 19 3 19 1 18 7 17 3 K W 1 92 1 88 1 85 1 83 1 95 1 92 1 89 1 86 1 99 1 95 1 93 1 90 125 T C 21 4 19 4 17 4 16 3 21 4 19 7 17 8 16 6 21 6 19 7 18 5 16 8 S C 16 8 16 6 16 5 15 5 17 8 17 5 17 5 15 9 18 7 18 4 17 5 16 1 K W 2 03 1 98 1 94 1 92 2 06 2 02 1 98 1 96 2 09 2 05 2 03 1 99 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1V...

Page 13: ... 34 1 34 0 34 5 34 4 K W 5 13 4 95 4 78 4 61 5 21 5 03 4 87 4 71 5 28 5 11 4 95 4 79 125 T C 42 9 39 2 35 8 32 2 43 2 39 5 36 0 33 0 43 6 39 7 36 4 33 3 S C 30 2 30 1 31 0 30 3 31 7 31 5 31 9 32 6 33 1 32 9 33 3 32 9 K W 5 41 5 20 4 83 4 82 5 49 5 28 5 11 4 94 5 55 5 37 5 19 5 01 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH 1000 CFM Air Handler Coil T C S C KW N1V...

Page 14: ... 33 9 31 0 28 1 25 9 34 1 31 2 28 5 26 4 S C 24 4 24 4 24 6 24 6 25 7 25 6 25 8 25 1 26 9 26 8 27 0 25 5 K W 2 53 2 50 2 45 2 40 2 57 2 53 2 49 2 45 2 61 2 57 2 52 2 49 115 T C 31 4 28 7 26 0 23 9 31 7 28 9 26 4 24 4 31 9 29 1 26 8 24 8 S C 23 8 23 7 23 8 23 1 25 0 24 8 25 0 23 6 26 1 26 0 26 0 24 0 K W 2 71 2 66 2 59 2 54 2 75 2 70 2 64 2 59 2 79 2 74 2 68 2 63 125 T C 29 3 26 7 24 1 22 4 29 5 26...

Page 15: ...7 0 61 8 56 7 51 8 47 4 S C 40 6 40 7 41 0 40 9 42 7 42 7 43 4 43 5 44 0 44 1 44 5 44 5 K W 6 03 5 77 5 54 5 31 6 15 5 90 5 65 5 45 6 21 5 97 5 71 5 49 115 T C 57 2 52 3 47 6 43 2 57 9 53 1 48 4 44 2 58 0 53 4 48 6 45 2 S C 39 3 39 2 39 6 39 5 41 7 41 9 42 0 41 9 42 6 42 9 43 1 43 6 K W 6 39 6 10 5 84 5 58 6 50 6 23 5 94 5 72 6 57 6 28 6 01 5 83 125 T C 53 5 48 9 44 5 40 4 54 4 50 0 45 3 41 4 54 2...

Page 16: ...rk OK Group Drive 73069 MATCHING INDOOR COMPONENTS G1UA 1 2 CASED UPFLOW G2FD MULTI POSITION UPFLOW HORIZONTAL AND DOWNFLOW Available with factory installed horizontal drain pan ADD ON COILS FOR FURNACE APPLICATIONS G1FA FULL CASED UPFLOW AIR HANDLERS FOR NON FURNACE APPLICATIONS N AH OR N VS MODULAR BLOWER UPFLOW HORIZONTAL AND DOWNFLOW F RC F FC OR F RC F FP FAN COIL UNITS UPFLOW HORIZONTAL G FD...

Reviews: