036-21023-005 Rev. A (0802)
2
Unitary Products Group
PHYSICAL AND ELECTRICAL DATA
MODEL
H4TS024
H4TS030
H4TS036
H4TS048
H4TS060
UNIT SUPPLY VOLTAGE
208/230-1-60
NORMAL VOLTAGE RANGE
1
187 to 252
MIN. CIRCUIT AMPACITY
13.4
15.3
18.6
32.8
35.3
MAX. OVERCURRENT DEVICE AMPS
2
20
25
30
50
60
COMPRESSOR TYPE
BRISTOL TS
COMPRESSOR AMPS
RATED LOAD
10.3
11.7
13.5
25.7
27.0
LOCKED ROTOR
64
65
84
135
147
CRANKCASE HEATER
YES
YES
YES
YES
YES
FAN MOTOR AMPS
RATED LOAD
.5
.5
.7
.7
1.5
FAN DIAMETER INCHES
18
18
24
24
24
FAN MOTOR
RATED HP
1/12
1/12
1/10
1/10
1/4
NOMINAL RPM
1100
1100
825
825
850
NOMINAL CFM
1850
1850
2800
2800
3200
COIL
FACE AREA SQ. FT
14.2
14.2
20.0
24.0
24.0
COIL ROWS DEEP
1
1
1
1
1
FIN / INCH
20
20
20
20
20
LIQUID LINE OD
3/8
3/8
3/8
3/8
3/8
VAPOR LINE OD
3/4
3/4
7/8
7/8
7/8
UNIT CHARGE, (LBS - OZ)
3
6 - 0
6 - 4
7 - 0
9 - 12
9 - 2
CHARGE PER FOOT, OZ
.68
.68
.70
.70
.70
OPERATING WEIGHT LBS.
145
145
200
250
252
1
Rated in accordance with ARI Standard 110, utilizaton range “A”.
2
Dual element fuses or HACR circuit breaker.
3 The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or sub-
tract the amount of refrigerant calculated, using the difference in length multiplied by the per foot value.
48" OVERHEAD
CLEARANCE
C
B
A
5-1/2
2-3/8
3-1/8
VAPOR
CONNECTION
LIQUID CONNECTION
AIR IN
4 SIDES
DIMENSIONS
UNIT
MODEL
DIMENSIONS
(INCHES)
REFRIGERANT
CONNECTION
LINE SIZE
A
1
B
C
Liquid
Vapor
024
30-1/8
24
24
3/8
3/4
030
30-1/8
24
24
036
31-7/8
35
35
7/8
048
37-7/8
35
35
060
37-7/8
35
35