I. General

A. Units shall be manufactured in a facility registered under

the ISO 9002 manufacturing quality standard.

B. Units shall be UL listed to US and Canadian safety

standards.

C. Unit shall be packaged to allow outdoor storage.

D. Warranty shall be a full year limited parts warranty on the

complete unit with an additonal 4-year warranty on the
compressor.

E. Unit shall be rated in accordance with ARI 360.

II. Unit Cabinet

A. Cabinet shall be constructed of 18 gauge, zinc-coated

steel, finished with a powder paint process capable of
withstanding a minimum of 750 salt spray hours
according to ASTM B117.

B. Cabinet screws shall comply with the ASTM B117 salt

spray test for a minimum of 750 hours.

C. Panels shall be removable for easy access to all internal

components during maintenance and service.

D. Cabinet shall feature a separate access panel for the

controls so that unit airflow need not be disturbed during
servicing.

E. Permanently attached base rails shall have 3-way fork lift

access and lifting holes for ease of installation.

III. Compressor

A. Compressors shall be hermetic scroll.

B. Compressor shall feature motor overload protection.

C. A crankcase heater shall keep refrigerant from diluting

the compressor oil in the sump.  Crankcase heater shall
be field replaceable without removal of the charge.

D. Neoprene isolators shall be used to minimize the trans-

mission of sound and vibration.

E. Compressor sets shall have two stages, with unloading

accomplished through turning off one compressor.

IV. Condenser and Fans

A. Fan motors shall be  direct-drive with propeller-type con-

denser fans which discharge air vertically upward.

B. Fan motors shall  have permanently lubricated ball-bear-

ings for longer wear during start and stop cycles and
shall have inherent overload protection.

C. Coil shall be constructed of rifled copper tubing mechani-

cally expanded and bonded to louvered aluminum fins.
Coil shall include an integral subcooler.

V. Refrigeration Components - Refrigeration system
shall contain the following:

High and low pressure cut-outs

Suction and liquid line service valves to ease installation
and recovery of refrigerant

External ports to accomodate gauge lines, allowing for easy
servicing

Filter drier shipped in unit for field installation

Holding charge of R-22 

VI. Controls - Unit controls shall include:

A. 24 volt control circuit with terminal blocks.

B. Color-coded wiring for easy service and troubleshooting

C Independent line break thermal protection for the

condenser fans.

D. 5 minute anti-short cycle timer to protect the compressor

from frequent cycling.

E. Unit safety lockouts which automatically reset from the

thermostat once the anti-short cycle timer is satisfied.
Safety lockouts will also generate a 24 volt signal to the
"X" terminal, allowing notification to the user via the
thermostat fault light (if present).  These safety lockouts
shall include:

1. High refrigerant pressure
2. Low refrigerant pressure. Low refrigerant pressure shall

be bypassed for the first 120 seconds (approximate) of
operation to eliminate nuisance trips.

F. Compressor motor protection to automatically shutdown

the unit in the event of motor overcurrent or low control
voltage conditions.  Unit shall automatically restart after
satisfying the anti-short cycle timer.

G. Low ambient operation down to 35 

°

F without a low

ambient kit.  (Operation down to 0 

°

F with the optional

low ambient kit.)

VII. Electrical 

A. Units shall be ______ volts, 3 phase, with a single power

point connection.

B. Unit control circuit shall have a 24 volt transformer, sized

sufficiently to operate the indoor fan.

C. All condenser fan motors and the secondary of each

transformer shall be grounded.

VIII. Accessories and Options

A. Head Pressure Control

Shall include a condenser fan motor and  a pressure
controller, allowing operation of the condensing unit
down to 0

°

F.

GUIDE SPECIFICATION - H*CE180 THROUGH 240

550.23-TG3Y

Unitary Products Group

9

Summary of Contents for H3CE180

Page 1: ...d copper tubes and louvered aluminum fins for durability and long lasting efficient operation Permanently attached base rails with fork lift slots and lifting holes This design allows for 3 way fork l...

Page 2: ...Rated in accordance with ARI 370 3 All ratings were determined with 25 feet of interconnecting tubing and with the air handler in the horizontal position For the 180 a 5 8 inch liquid line and an insu...

Page 3: ...D F A N M O T O R A C C E S S E X T E R N A L P R E S S U R E G A U G E F I T T I N G S C O N T R O L B O X A C C E S S 9 1 3 2 7 6 7 8 7 1 3 2 3 9 7 8 1 3 1 4 3 0 3 4 2 4 1 2 1 2 1 8 C D F E F E F A...

Page 4: ...ing Condenser Air Ent Power Air Temperature Entering Evaporator Dry Bulb Power Air Temperature Entering Evaporator Dry Bulb Evaporator Input 86 80 74 68 Input 86 80 74 68 CFM WB kW Total Sens Total Se...

Page 5: ...L3EU240 105 F Air Entering Condenser 115 F Air Entering Condenser Air Ent Power Air Temperature Entering Evaporator Dry Bulb Power Air Temperature Entering Evaporator Dry Bulb Evaporator Input 86 80 7...

Page 6: ...M O S T A T 2 T H 0 4 7 0 1 2 2 4 E V A P O R A T O R B L O W E R M O T O R C O N T A C T O R R C Y 2 Y 1 G 2 4 V X L L Y 2 C O M P R E S S O R 2 4 V L O C K O U T S I G N A L 2 V A M A X C O M P R E...

Page 7: ...e call for cooling has been removed When Y1 is returned to 0 volts the LOR coil is no longer energized closing the LOR 1 contacts and removing the lock out SUCTION LINE DATA1 2 LIQUID LINE DATA REFRIG...

Page 8: ...ontinues to lock out after resuming operation call a service technician to diagnose and repair the unit CAUTION Repeatedly resetting the lock out may cause damage to the unit Second Stage of Cooling T...

Page 9: ...xpanded and bonded to louvered aluminum fins Coil shall include an integral subcooler V Refrigeration Components Refrigeration system shall contain the following High and low pressure cut outs Suction...

Page 10: ...to provide further coil protection D Phenolic Coating on Condenser Coil Condenser coils shall be dipped in a four coat phenolic coating process to provide longer life in corrosive condi tions GUIDE SP...

Page 11: ...550 23 TG3Y Unitary Products Group 11...

Page 12: ...592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1998 All Rights Reserved Codes EBY EGY 550 23 TG3Y Supersedes 550 23...

Reviews: