 The low pressure bypass timer 1TR leaves the 1TR-1 contacts
closed upon the start of a call for cooling until its 90 second
(nominal) timer has expired.  This bypasses the low pressure
switch during start up.  After the time delay has elapsed, 1TR-1
contacts are opened, once again allowing low pressure to
trigger the lock out circuit if the low pressure switch opens.

During a lock out, the LOR-2 contacts are closed, energizing
the X terminal on the terminal board for lighting a lock out
warning light.

Resetting the Lock Out

  The lock out may be reset by:

Turning the thermostat switch to OFF, or

Momentarily adjusting the cooling set point to its maximum
allowed value.

If the unit does not resume operation after the anti-short cycle
timer expires or if it continues to lock out after resuming
operation, call a service technician to diagnose and repair the
unit.

CAUTION: Repeatedly resetting the lock out may cause

damage to the unit.

Second Stage of Cooling

The second stage of cooling will only be enabled if the first
stage of cooling is on, closing auxiliary contact 1M-AC1.   A call
for cooling at terminal Y2 energizes Relay RY2, closing contact
RY2-1, and energizing time delay relay 4TR if contact 1M-AC1
is closed.  If time delay relay 4TR is satisfied, it will energize its
output terminal Y2, which is connected to compressor 2 control
module terminal M1.

If the compressor 2 control module is satisfied, it will energize
time delay relay TDR.  After 4 seconds, TDR energizes
compressor 2 contactor 2M.When 2M is energized on
H3CE240 units, auxiliary contact 2M-AC1 is closed, powering
terminal 2 for opening the stage 2 solenoid in air handlers which
feature a stage 2 solenoid.

550.23-TG3Y

8

Unitary Products Group

Summary of Contents for H3CE180

Page 1: ...d copper tubes and louvered aluminum fins for durability and long lasting efficient operation Permanently attached base rails with fork lift slots and lifting holes This design allows for 3 way fork l...

Page 2: ...Rated in accordance with ARI 370 3 All ratings were determined with 25 feet of interconnecting tubing and with the air handler in the horizontal position For the 180 a 5 8 inch liquid line and an insu...

Page 3: ...D F A N M O T O R A C C E S S E X T E R N A L P R E S S U R E G A U G E F I T T I N G S C O N T R O L B O X A C C E S S 9 1 3 2 7 6 7 8 7 1 3 2 3 9 7 8 1 3 1 4 3 0 3 4 2 4 1 2 1 2 1 8 C D F E F E F A...

Page 4: ...ing Condenser Air Ent Power Air Temperature Entering Evaporator Dry Bulb Power Air Temperature Entering Evaporator Dry Bulb Evaporator Input 86 80 74 68 Input 86 80 74 68 CFM WB kW Total Sens Total Se...

Page 5: ...L3EU240 105 F Air Entering Condenser 115 F Air Entering Condenser Air Ent Power Air Temperature Entering Evaporator Dry Bulb Power Air Temperature Entering Evaporator Dry Bulb Evaporator Input 86 80 7...

Page 6: ...M O S T A T 2 T H 0 4 7 0 1 2 2 4 E V A P O R A T O R B L O W E R M O T O R C O N T A C T O R R C Y 2 Y 1 G 2 4 V X L L Y 2 C O M P R E S S O R 2 4 V L O C K O U T S I G N A L 2 V A M A X C O M P R E...

Page 7: ...e call for cooling has been removed When Y1 is returned to 0 volts the LOR coil is no longer energized closing the LOR 1 contacts and removing the lock out SUCTION LINE DATA1 2 LIQUID LINE DATA REFRIG...

Page 8: ...ontinues to lock out after resuming operation call a service technician to diagnose and repair the unit CAUTION Repeatedly resetting the lock out may cause damage to the unit Second Stage of Cooling T...

Page 9: ...xpanded and bonded to louvered aluminum fins Coil shall include an integral subcooler V Refrigeration Components Refrigeration system shall contain the following High and low pressure cut outs Suction...

Page 10: ...to provide further coil protection D Phenolic Coating on Condenser Coil Condenser coils shall be dipped in a four coat phenolic coating process to provide longer life in corrosive condi tions GUIDE SP...

Page 11: ...550 23 TG3Y Unitary Products Group 11...

Page 12: ...592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1998 All Rights Reserved Codes EBY EGY 550 23 TG3Y Supersedes 550 23...

Reviews: