571921-UTG-A-0410
Johnson Controls Unitary Products
33
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO
GHGD60S41S4
EVAPORATOR COIL MODEL NO
AHX60
AIR TEMP.
ENTERING
OUTDOOR UNIT
AIR TEMP.
ENTERING
INDOOR COIL
ID CFM
1600
1800
2000
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
60
60
62.8
3.6
4.4
61.5
3.7
4.3
60.1
3.8
4.1
70
63.2
3.2
5.0
62.2
3.3
4.8
61.2
3.4
4.6
80
63.6
3.0
5.5
62.9
3.1
5.3
62.2
3.2
5.2
47
60
56.1
3.4
4.1
55.2
3.5
3.9
54.4
3.6
3.8
70
56.1
3.1
4.5
55.3
3.2
4.4
54.6
3.3
4.2
80
56.1
2.9
4.9
55.4
3.0
4.8
54.8
3.0
4.7
40
60
51.5
3.3
3.8
41.8
3.0
3.4
32.0
2.6
3.1
70
51.5
3.0
4.2
46.4
2.9
4.0
41.3
2.8
3.8
80
51.4
2.8
4.7
51.0
2.9
4.6
50.7
2.9
4.5
30
60
40.4
2.8
3.5
36.7
2.7
3.3
33.0
2.6
3.2
70
42.4
2.6
4.0
40.4
2.6
3.8
38.3
2.6
3.7
80
44.4
2.5
4.4
44.0
2.6
4.3
43.7
2.7
4.2
17
60
33.7
2.0
4.1
35.7
2.4
3.7
37.6
2.9
3.3
70
34.5
2.1
4.1
35.5
2.3
3.8
36.5
2.6
3.6
80
35.3
2.2
4.1
35.3
2.2
4.0
35.3
2.3
3.9
10
60
32.5
2.4
3.3
31.2
2.4
3.2
30.0
2.4
3.0
70
29.9
2.1
3.5
28.9
2.1
3.4
28.0
2.1
3.4
80
27.3
1.8
3.8
26.7
1.8
3.7
26.0
1.8
3.7
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handlers
Coils
MBH
KW
COP
–
FC/MC62
1.00
0.98
1.02
–
FC64
1.00
1.00
1.00
AHX60
–
1.00
1.00
1.00
F6FP060
–
1.00
1.01
0.99
MV20D
FC/MC62D
1.00
0.99
1.01
MV20D
FC64D
1.00
1.01
0.99
MA20D
FC/MC62D
1.00
0.98
1.02
MA20D
FC64D
1.00
1.00
1.00
Furnaces
Coils
MBH
KW
COP
T*(8,L)X*C20
FC/MC62D
1.00
1.00
1.00
T*9X*C20
FC/MC62D
1.00
0.98
1.02
T*9X*D20
FC/MC62D
1.00
0.99
1.01
T*(8,L)X*C20
FC64D
1.00
1.02
0.98
T*9X*C20
FC64D
1.00
1.01
0.99
T*9X*D20
FC64D
1.00
1.02
0.98
(T*(8,L)C/T*8V)*C20
FC/MC62D
1.00
0.98
1.02
(T*9C/T*9V)*C20
FC/MC62D
1.00
0.97
1.03
(T*9C/T*9V)*D20
FC/MC62D
1.00
0.97
1.03
(T*(8,L)C/T*8V)*C20
FC64D
1.00
1.01
0.99
(T*9C/T*9V)*C20
FC64D
1.00
0.99
1.01
(T*9C/T*9V)*D20
FC64D
1.00
1.00
1.00