224
7. If the Cooling overload protection power turn-off continuously occurs for six times, it should not be resumed
automatically, and you should press the ON/OFF button to resume if the fault keeps on. During the process of
running, if the running time of compressor exceeds the
Ǐ
t
overload protection times zero clearing time
ǐ
, the times of overload
protection power turn-off should be cleared to recount. The mode of stopping the machine or transferring to
supply air will clear the trouble times immediately (if the trouble can not be resumed, transferring mode will not
clear it).
Overload protection function at the mode of heating
1. Starting estimation
:
After the compressor stopped working for 180s, if T
inner pipe
˘ Ǐ
T
heating
overload frequency-limited temperature
ǐ
(the
temperature of hysteresis is 2
ć
), the machine is allowed to start, otherwise it should not be started, and should
be stopped to treat according to the overload protection:
Clear the trouble at the mode of power turn-off / heating, and the protection times are not counted.
2. Raising the frequency slowly:
During the raising process of pipe temperature and frequency, if the
Ǐ
T
Slowly raising frequency temperature of heating overload
ǐ
≤
T
inner pipe
˘Ǐ
T
heating overload frequency-limited temperature
ǐ
, the frequency raising speed should be executed according to
the
Ǐ
F
slowly raising speed of
preventing protection frequency
ǐ
; If T
inner pipe
˘Ǐ
T
Slowly raising frequency temperature of heating overload
ǐ
, you
should exit the slowly raising control.
1. Frequency limited
If
Ǐ
T
heating overload frequency-limited temperature
ǐ
≤
T
inner pipe
˘
Ǐ
T
heating overload
frequency reducing temperature at normal speed
ǐ
, you should
limit the frequency raising of compressor.
2. Reducing frequency at normal speed and stopping machine:
If
Ǐ
T
heating overload
frequency reducing temperature at normal speed
ǐ
≤
T
inner pipe
˘
Ǐ
T
heating overload frequency reducing temperature at high speed
ǐ
,
you should adjust the compressor frequency by reducing 8Hz/90s till the lower limit; After it was running 90s at
the lower limit, if
Ǐ
T
heating overload
frequency reducing temperature at normal speed
ǐ
≤
T
inner pipe
, then overload protects machine
stopping;
3. Reducing frequency at high speed and power turn-off:
If
Ǐ
T
heating overload
frequency reducing temperature at high speed
ǐ
≤
T
inner pipe
˘Ǐ
T
heating overload power turn-off temperature
ǐ
you should
adjust the compressor frequency by reducing 30Hz/90s till the lower limit; After it was running 90s at the lower
limit, if
Ǐ
T
heating overload
frequency reducing temperature at normal speed
ǐ
≤
T
outer pipe
, then Cooling overload protects machine
stopping;
4. Power turn-off:
If the
Ǐ
T
heating overload power turn-off temperature
ǐ
≤
T
inner pipe
, then overload protects machine stopping; If T
inner pipe
˘Ǐ
T
heating overload frequency-limited temperature
ǐ
and the compressor has been stopped working for 3 minutes, the machine
should be allowed to operate.
5. If the overload protection power turn-off continuously occurs for six times, it should not be resumed
automatically, and you should press the ON/OFF button to resume if the fault keeps on. During the process of
running, if the running time of compressor exceeds the
Ǐ
t
overload protection times zero clearing time
ǐ
, the times of overload
protection power turn-off should be cleared to recount. The mode of stopping the machine or transferring to
supply air will clear the trouble times immediately (if the trouble can not be resumed, transferring mode will not
clear it).
(3) Protective function for discharge temperature of compressor
1. Starting estimation:
After the compressor stopped working for 180s, if T
Discharge
˘Ǐ
T
Discharge limited temperature
ǐ
(the temperature of
hysteresis is 2
ć
), the machine is allowed to start, otherwise it should not be started, and should be stopped to
treat according to the discharge temperature:
The machine should be stopped or transferred to supply air, the trouble should be cleared immediately, and the
protection times are not counted.
2. Raising the frequency slowly:
During the process of raising frequency, if the
Ǐ
T
Slowly raising frequency temperature during discharging
ǐ
≤
T
Discharge
˘Ǐ
T
Limited
frequency temperature during discharging
ǐ
, the frequency raising speed should be executed according to the
Ǐ
F
Preventing
protection frequency raising speed
ǐ
; If T
Discharge
˘Ǐ
T
Slowly raising frequency temperature during discharging
ǐ
, you should exit the slowly
raising control.
3. Frequency limited
If
Ǐ
T
Limited frequency temperature during discharging
ǐ
≤
T
Discharge
˘
Ǐ
T
frequency reducing temperature at normal speed during discharging
ǐ
, you should
limit the frequency raising of compressor.
4. Reducing frequency at normal speed and stopping machine:
If
Ǐ
T
frequency reducing temperature at normal speed during discharging
ǐ
≤
T
Discharge
˘
Ǐ
T
frequency reducing temperature at high speed during discharging
ǐ
,
you should adjust the compressor frequency by reducing 8Hz/90s till the lower limit; After it was running 90s at
the lower limit, if
Ǐ
T
frequency reducing temperature at normal speed during discharging
ǐ
≤
T
Discharge
, you should discharge to protect
machine stopping;
Operation
33
Summary of Contents for EVJC 12
Page 2: ...74 74...
Page 30: ...102...
Page 32: ...104 www johnsoncontrols com...
Page 34: ...106 by johnson controls 2...
Page 46: ...118...
Page 48: ...120 www johnsoncontrols com...
Page 49: ...121 High Wall EVHC 09 to 12 DSAAAR SERVICE MANUAL SM EVHC D 09 12GB 05 10 EVHC 09 EVHC 12...
Page 65: ...137 LULQJ LDJUDP Schematic Diagram Indoor Unit Schematic Diagram...
Page 66: ...138 Schematic Diagram Outdoor Unit...
Page 69: ...141 TOP VIEW Schematic Diagram BOTTOM VIEW 1 3 4 5 6 2 7 8 9 10 11 12 Outdoor Unit...
Page 113: ...185 Exploded View Exploded View Indoor Unit...
Page 114: ...186 Exploded View Outdoor Unit...
Page 118: ...190 High Wall EVHC 18 to 24 DSAAAR SERVICE MANUAL SM EVHC D 18 24GB 05 10 EVHC 18 EVHC 24...
Page 132: ...204 LPHQVLRQV Dimensions QGRRU 8QLW Tube exit Air inlet Right Left Ceiling W D H 02 18K 24K...
Page 133: ...205 890 340 955 560 380 424 700 60cm 60cm 60cm 60cm LPHQVLRQV Outdoor Unit Bolt Nut Spanner...
Page 140: ...212 TOP VIEW Schematic Diagram BOTTOM VIEW 1 2 3 4 5 6 7 8 9 7 8 9 10 11 12 13 1 2 3 4 5 6 10...
Page 142: ...214 Schematic Diagram Key testing spot bottom...
Page 197: ...269 Exploded View Exploded View Indoor Unit 78 Model EVKC 18 DS...
Page 198: ...270 Exploded View Model EVKC 24 DS 79...
Page 199: ...271 Exploded View Outdoor Unit 80...