MOTOR PROTECTOR DIP SWITCH SETTING WYE-DELTA START 50 HZ
YCAS STYLE F, WYE-DELTA START 50 HZ.
MODEL
VOLT
CHILLER
NO.
MOTOR PROTECTOR
NO.
CODE
NAMEPLATE
LEADS MP OL
RLA
PER
VALUE
PHASE
SET
DIP SWITCH SETTINGS ON MP (1 INDICATED ON)
THRU MP
128
64
32
16
8
4
2
1
0685
50
99
1
134
1
0
0
0
0
1
1
0
SYS 1 & 2
0685
50
162
2
219
1
1
0
1
1
0
1
1
SYS 3
0775
50
128
1
173
1
0
1
0
1
1
0
1
0835 SYS 1
50
163
2
220
1
1
0
1
1
1
0
0
0835
50
128
1
173
1
0
1
0
1
1
0
1
SYS 2 & 3
0905
50
163
2
220
1
1
0
1
1
1
0
0
0965
SYS
1 & 2
50
155
2
209
1
1
0
1
0
0
0
1
0965
SYS 3
50
148
2
200
1
1
0
0
1
0
0
0
1065
50
128
1
173
1
0
1
0
1
1
0
1
1135
50
162
2
219
1
1
0
1
1
0
1
1
SYS 1 & 2
1135
50
128
1
173
1
0
1
0
1
1
0
1
SYS 3 & 4
1215
50
162
2
219
1
1
0
1
1
0
1
1
* Indicates one lead/phase through motor protector.
Summary of Contents for eco YCAS Series
Page 65: ...65 YORK INTERNATIONAL FORM 201 18 NM9 602 This page intentionally left blank 7...
Page 77: ...77 YORK INTERNATIONAL FORM 201 18 NM9 602 This page intentionally left blank 7...
Page 81: ...81 YORK INTERNATIONAL FORM 201 18 NM9 602 LD04179 7...
Page 83: ...83 YORK INTERNATIONAL FORM 201 18 NM9 602 7 LD04181 Box Information continued from page 82...
Page 97: ...97 YORK INTERNATIONAL FORM 201 18 NM9 602 This page intentionally left blank 7...
Page 103: ...FORM 201 18 NM9 602 YORK INTERNATIONAL YORK INTERNATIONAL 103 103A LD04267 FORM 201 18 NM9 602...