036-21371-001-B-0203

                                                                                                                                                                                                                                           

8

Unitary Products Group

These ratings are based on an outdoor relative humidity of 72%. They include an allowance for defrost but not for the supply air blower motor heat. Refer to the 
BLOWER PERFORMANCE table for the KW rating of the supply air blower motor at the design conditions. Convert this KW rating to MBH using the following 
equation and add this equivalent heat to the heating capacity.

Blower Motor Heat (MBH) = Blower Motor KW x (3.415 MBH/KW)

Use the following equation to determine the C.O.P. at any operating condition.

C.O.P. = Total MBH (including Blower Motor Heat)/[Total KW (including Blower Motor KW) x 3.415]

correct the MBH and KW ratings with the following factors for different supply air CFM’s.
These ratings include the compressor KW and the following KW for the outdoor fan motor(s).

NOTE: Apply these factors to the above ratings before correcting for the supply air blower heat and power requirements.
.

Blower motor KW is not included. Refer to the SUPPLY AIR BLOWER PERFORMANCE table for the KW rating of the supply air blower motor at the design 
conditions and add this power requirement to the KW rating.

UNIT MODEL EA090

OUTDOOR TEMPERATURE (F) (72% RH)

CFM

ID DB

0

10

20

30

40

50

60

70

2400

60 MBH

12.237

28.142

44.048

59.954

75.859

91.765

107.671

123.576

2400

KW

2.090

3.179

4.268

5.357

6.447

7.536

8.625

9.714

2400

70 MBH

9.673

25.579

41.485

57.390

73.296

89.201

105.107

121.013

2400

KW

2.576

3.665

4.754

5.844

6.933

8.022

9.111

10.201

2400

80 MBH

9.589

25.495

41.401

57.306

73.212

89.118

105.023

120.929

2400

KW

3.352

4.441

5.530

6.619

7.709

8.798

9.887

10.976

3300

60 MBH

13.565

29.471

45.377

61.282

77.188

93.094

108.999

124.905

3300

KW

1.417

2.506

3.595

4.685

5.774

6.863

7.952

9.041

3300

70 MBH

10.826

26.732

42.637

58.543

74.449

90.354

106.260

122.166

3300

KW

1.852

2.941

4.030

5.119

6.209

7.298

8.387

9.476

3300

80 MBH

10.916

26.822

42.727

58.633

74.539

90.444

106.350

122.256

3300

KW

2.679

3.768

4.857

5.946

7.035

8.125

9.214

10.303

3600

60 MBH

14.284

30.189

46.095

62.001

77.906

93.812

109.718

125.623

3600

KW

1.353

2.442

3.531

4.620

5.710

6.799

7.888

8.977

3600

70 MBH

11.720

27.626

43.531

59.437

75.343

91.248

107.154

123.060

3600

KW

1.839

2.928

4.018

5.107

6.196

7.285

8.374

9.464

3600

80 MBH

11.636

27.542

43.448

59.353

75.259

91.165

107.070

122.976

3600

KW

2.615

3.704

4.793

5.883

6.972

8.061

9.150

10.239

THE MBH AND KW VALUES DO NOT INCLUDE THE SUPPLY AIR BLOWER MOTOR.
FOR NET CAPACITY, ADD THE SUPPLY AIR BLOWER MOTOR HEAT (MBH = 3.415 x KW)

Correction Factor

80

90

100

110

120

MBH
KW

0.96

1.030

0.98

1.015

1.00

1.000

1.02

0.985

1.04

0.970

Outdoor Unit Size

7-1/2 Ton

Outdoor Fan Motor KW - 60 HZ

0.96

Summary of Contents for EA090

Page 1: ...ve and a distributor that are only used during the heating cycle plus a check valve to pro vide the proper flow of refrigerant through the unit during both the cool ing and heating cycles To eliminate...

Page 2: ...ing 14 7 Accessory Dimensions 15 LIST OF TABLES Table Page No Description No 1 ARI Ratings 4 2 System Application Data 4 3 Refrigerant Piping Limitations 4 4 Cooling Capacity EA090 6 5 Heating Capacit...

Page 3: ...avel bed or some other means of handling this condensate may have to be provided INDOOR UNITS These indoor units are shipped for vertical installation but may be field converted for horizontal applica...

Page 4: ...Coil F Air Temperature on INDOOR Coil F Minimum Maximum minimum Maximum Cool Heat Cool heat Cool Heat Cool Heat 40 db 0 db1 115 db 75 db 57 wb 50 db2 72 wb 80 db 1 Below 0 F the control circuit will l...

Page 5: ...ing permits the outdoor unit to be mounted 60 feet over or under the indoor unit without any danger of flashing liquid refrigerant during the heating or the cooling cycle Refer to the REFRIGERANT PIPI...

Page 6: ...9 79 9 3 68 61 54 48 41 34 27 62 79 8 2 79 75 68 61 55 48 41 76 9 0 76 73 66 60 53 46 39 57 83 8 3 82 76 69 62 55 48 42 78 9 1 78 72 65 58 51 44 37 72 95 8 6 63 55 46 38 30 91 9 4 61 53 45 36 28 67 85...

Page 7: ...actor 0 963 0 935 0 981 0 981 0 965 0 992 1 000 1 000 1 000 1 015 1 049 1 008 1 030 1 098 1 019 Nominal Rating 86 83 80 77 74 71 68 72 85 10 2 52 45 38 31 24 67 74 10 1 66 59 53 46 39 32 25 62 74 9 8...

Page 8: ...BH 12 237 28 142 44 048 59 954 75 859 91 765 107 671 123 576 2400 KW 2 090 3 179 4 268 5 357 6 447 7 536 8 625 9 714 2400 70 MBH 9 673 25 579 41 485 57 390 73 296 89 201 105 107 121 013 2400 KW 2 576...

Page 9: ...tor Pulley Fixed Blower Pulley Belt Pitch Diameter in Bore in Pitch Diameter in Bore in Designation Pitch Length in FA090 1 1 2 690 920 2 8 3 8 7 8 7 5 1 A36 37 3 Motor Specifications 1750 RPM inheren...

Page 10: ...40 19 9 32 50 52 78 10 5 3300 845 65 101 26 38 21 10 46 73 29 44 19 9 35 55 56 85 10 5 3600 920 71 110 28 41 22 11 50 79 32 47 20 10 38 60 60 91 11 6 1 Adjusting the vertical louvers will vary the thr...

Page 11: ...connection These bases are finished to match the exterior of the basic unit They may have to be insulated in the field for certain applications Decorative Coil Guards can be field installed to enhance...

Page 12: ...ES OUTDOOR UNITS A I R OU T A I R I N A I R OU T 2 3 4 3 2 2 1 4 3 2 1 2 7 0 1 8 8 3 4 5 3 8 C ON T R OL B OX A C C E S S GU A GE L I N E A C C E S S 3 9 1 3 8 OD V A P OR L I N E 5 8 OD L I QU I D L...

Page 13: ...an electric heater a supply air plenum or a base is used Side with PIPING CONNECTIONS 52 2 2 This dimension is required for removal of the coil Only 26 is required for normal servicing Side opposite P...

Page 14: ...its require dual element time delay fuses Circuit breakers can be used in lieu of fuses for indoor units with an electric heat accessory 1 Only required when an electric heat accessory is used 2 Only...

Page 15: ...l wiring per basic unit instruction Form 035 18475 000 DO NOT route any field control wiring through the plenum WITHOUT ELECTRIC HEAT Install the power and the control wiring per basic unit instructio...

Page 16: ...D inches 3 8 Fins Aluminum per inch 13 Centrifugal Blower Forward Curve Diameter x Width inches 15 X 15 Blower Motor1 Nominal Rating HP 1 1 2 Filters Throwaway Quantity Per Unit 16 x 25 x 1 4 Total Fa...

Page 17: ...3 0 TABLE 13 ELECTRICAL DATA OUTDOOR UNIT Model EFB Compressor Outdoor Fan Motor Min Circuit Amps Max Fuse Size Min Wire Size 1 AWG Power Supply RLA LRA Power Factor Power Supply Qty FLA Each 090A 25...

Page 18: ...60 62 5 83 2 90 4 460 3 60 31 3 41 7 45 8 36 208 3 60 75 1 99 110 3 230 3 60 86 6 113 3 125 2 460 3 60 43 3 56 7 60 6 1 Unit with an electric heat accessory will always be wired for a single power su...