036-21371-001-B-0203
10
Unitary Products Group
TABLE 8: SUPPLY AIR PLENUM PERFORMANCE DATA
INDOOR
UNIT
MODEL
FA
CFM
FACE
VELO
CITY
(FPM)
ANGLE OF DEFLECTION
VERTICAL
LOUVERS
1
(PLAN
VIEW)
HORIZONTAL
LOUVERS
2
(ELEVATION
VIEW)
VERTICAL
LOUVERS
1
(PLAN
VIEW)
HORIZON-
TAL
LOUVERS
2
(ELEVATION
VIEW)
VERTICAL
LOUVERS
1
(PLAN
VIEW)
HORIZONTAL
LOUVERS
2
(ELEVATION
VIEW)
THROW
(FEET
3
)
SPREAD
(FEET)
3
THROW
(FEET)
3
SPREAD
(FEET)
3
THROW
(FEET)
3
SPREAD
(FEET)
3
MIN.
MAX.
MIN.
MAX
DROP (FEET)
4
MIN.
MAX
MIN.
MAX DROP (FEET)
4
MIN.
MAX.
MIN.
MAX. DROP (FEET)
4
090
2400
615
47
74
20
29
19
9
34
53
23
33
17
8
26
39
45
65
9
5
2700
690
53
83
22
32
20
10
39
59
25
36
18
9
29
45
48
71
10
5
3000
770
59
92
24
35
21
10
42
66
27
40
19
9
32
50
52
78
10
5
3300
845
65
101
26
38
21
10
46
73
29
44
19
9
35
55
56
85
10
5
3600
920
71
110
28
41
22
11
50
79
32
47
20
10
38
60
60
91
11
6
1
Adjusting the vertical louvers will vary the throw, the spread and the drop.
2
Adjusting the horizontal louvers will only vary the drop.
3
The velocity of the air will be 125 ft./min. at the minimum distance and 80 ft./min. at the maximum distance.
4
The velocity of the conditioned air at the bottom of the drop will be 50 ft./min. Drafts will occur if the drop extends into the occu-
pied level of the conditioned space.
0 °
S P R E A D
2 2 - 1 / 2 °
S P R E A D
4 5 °
S P R E A D
0 °
S P R E A D
18˚
0 °
S P R E A D
18˚
0 °
S P R E A D
18˚
FIGURE 3: FA090 AIRFLOW CHART
7.5-ton Heat Pump
2400
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
1.1
Static
CFM
O turns
1 turn
2 turns
3 turns
4 turns
5 turns