Unitary Products Group

7

The capacities shown are gross ratings. For net capacities, determine the KW requirement of the supply air blower motor per the SUPPLY AIR BLOWER PER-
FORMANCE table. Convert KW to MBH by the following equation and deduct this equivalent heat from the gross cooling ratings.

Blower Motor Heat (MBH) = Blower Motor KW x 3.415

Apply the following correction factors to determine the unit performance at different CFM.
These ratings include the compressor KW and the following KW for the outdoor fan motor(s).

NOTE: Sensible capacity can never exceed total capacity. A higher 
corrected sensible capacity indicates a dry coil, and it should be 
reduced to the corrected total capacity.

Blower motor KW is not included. Refer to the SUPPLY AIR BLOWER PERFORMANCE table for the KW rating of the supply air blower motor at the design 
conditions and add this power requirement to the KW rating.

TABLE 4: COOLING CAPACITY - EA090 (CONT.)

% Nominal Supply Air CFM

80

90

100

110

120

Total Capacity Correction Factor
Sensible Capacity Correction Factor
Kilowatt Correction Factor

0.963
0.935
0.981

0.981
0.965
0.992

1.000
1.000
1.000

1.015
1.049
1.008

1.030
1.098
1.019

Nominal Rating

86 83 80 77 74 71 68

72

85

10.2

52 45 38 31 24

-

-

67

74

10.1

66 59 53 46 39 32 25

62

74

9.8

74 71 65 58 51 44 37

57

72

9.9

72 67 61 54 47 40 33

72

87

10.3

59 51 43 34 26

-

-

67

76

10.2

73 67 59 51 42 34 26

62

75

9.9

75 74 72 64 56 48 39

57

73

10.0

73 71 68 60 51 43 35

72

88

10.4

66 57 47 38 28

-

-

67

77

10.3

77 75 65 55 46 36 27

62

76

10.0

76 76 76 70 61 51 41

57

75

10.1

75 75 75 65 56 46 37

72

90

10.4

68 58 48 38 28

-

-

67

79

10.3

79 76 66 56 46 36 25

62

78

10.0

78 78 78 70 60 50 40

57

77

10.1

77 77 76 66 56 46 36

72

93

10.3

70 60 49 38 27

-

-

67

81

10.3

81 78 67 57 46 35 24

62

80

9.9

80 80 80 70 59 48 38

57

79

10.0

79 79 78 67 56 45 35

1 - These capacities are gross 
ratings.  For net capacity, deduct 
air blower motor, MBh = 3.415 x 
kW.  Refer to the appropriate 
Blower Performance Table for the 
kW of the supply air blower motor.

2 - These ratings include the 
condenser fan motors (total 1 kW) 
and the compressor motors but not 
the supply air blower motor.

3450

3600

2400

2850

3300

Air On 

Evaporaor Coil

Temperature of Air on Condenser Coil

125°F

Total

Capacity

1

(MBh)

Total

Input

2

(kW)

Sensible Capacity (MBh)

CFM WB(°F)

Return Dry Bulb (°F)

Outdoor Unit Size

7-1/2 Ton

Outdoor Fan Motor KW - 60 HZ

0.83

Summary of Contents for EA090

Page 1: ...ve and a distributor that are only used during the heating cycle plus a check valve to pro vide the proper flow of refrigerant through the unit during both the cool ing and heating cycles To eliminate...

Page 2: ...ing 14 7 Accessory Dimensions 15 LIST OF TABLES Table Page No Description No 1 ARI Ratings 4 2 System Application Data 4 3 Refrigerant Piping Limitations 4 4 Cooling Capacity EA090 6 5 Heating Capacit...

Page 3: ...avel bed or some other means of handling this condensate may have to be provided INDOOR UNITS These indoor units are shipped for vertical installation but may be field converted for horizontal applica...

Page 4: ...Coil F Air Temperature on INDOOR Coil F Minimum Maximum minimum Maximum Cool Heat Cool heat Cool Heat Cool Heat 40 db 0 db1 115 db 75 db 57 wb 50 db2 72 wb 80 db 1 Below 0 F the control circuit will l...

Page 5: ...ing permits the outdoor unit to be mounted 60 feet over or under the indoor unit without any danger of flashing liquid refrigerant during the heating or the cooling cycle Refer to the REFRIGERANT PIPI...

Page 6: ...9 79 9 3 68 61 54 48 41 34 27 62 79 8 2 79 75 68 61 55 48 41 76 9 0 76 73 66 60 53 46 39 57 83 8 3 82 76 69 62 55 48 42 78 9 1 78 72 65 58 51 44 37 72 95 8 6 63 55 46 38 30 91 9 4 61 53 45 36 28 67 85...

Page 7: ...actor 0 963 0 935 0 981 0 981 0 965 0 992 1 000 1 000 1 000 1 015 1 049 1 008 1 030 1 098 1 019 Nominal Rating 86 83 80 77 74 71 68 72 85 10 2 52 45 38 31 24 67 74 10 1 66 59 53 46 39 32 25 62 74 9 8...

Page 8: ...BH 12 237 28 142 44 048 59 954 75 859 91 765 107 671 123 576 2400 KW 2 090 3 179 4 268 5 357 6 447 7 536 8 625 9 714 2400 70 MBH 9 673 25 579 41 485 57 390 73 296 89 201 105 107 121 013 2400 KW 2 576...

Page 9: ...tor Pulley Fixed Blower Pulley Belt Pitch Diameter in Bore in Pitch Diameter in Bore in Designation Pitch Length in FA090 1 1 2 690 920 2 8 3 8 7 8 7 5 1 A36 37 3 Motor Specifications 1750 RPM inheren...

Page 10: ...40 19 9 32 50 52 78 10 5 3300 845 65 101 26 38 21 10 46 73 29 44 19 9 35 55 56 85 10 5 3600 920 71 110 28 41 22 11 50 79 32 47 20 10 38 60 60 91 11 6 1 Adjusting the vertical louvers will vary the thr...

Page 11: ...connection These bases are finished to match the exterior of the basic unit They may have to be insulated in the field for certain applications Decorative Coil Guards can be field installed to enhance...

Page 12: ...ES OUTDOOR UNITS A I R OU T A I R I N A I R OU T 2 3 4 3 2 2 1 4 3 2 1 2 7 0 1 8 8 3 4 5 3 8 C ON T R OL B OX A C C E S S GU A GE L I N E A C C E S S 3 9 1 3 8 OD V A P OR L I N E 5 8 OD L I QU I D L...

Page 13: ...an electric heater a supply air plenum or a base is used Side with PIPING CONNECTIONS 52 2 2 This dimension is required for removal of the coil Only 26 is required for normal servicing Side opposite P...

Page 14: ...its require dual element time delay fuses Circuit breakers can be used in lieu of fuses for indoor units with an electric heat accessory 1 Only required when an electric heat accessory is used 2 Only...

Page 15: ...l wiring per basic unit instruction Form 035 18475 000 DO NOT route any field control wiring through the plenum WITHOUT ELECTRIC HEAT Install the power and the control wiring per basic unit instructio...

Page 16: ...D inches 3 8 Fins Aluminum per inch 13 Centrifugal Blower Forward Curve Diameter x Width inches 15 X 15 Blower Motor1 Nominal Rating HP 1 1 2 Filters Throwaway Quantity Per Unit 16 x 25 x 1 4 Total Fa...

Page 17: ...3 0 TABLE 13 ELECTRICAL DATA OUTDOOR UNIT Model EFB Compressor Outdoor Fan Motor Min Circuit Amps Max Fuse Size Min Wire Size 1 AWG Power Supply RLA LRA Power Factor Power Supply Qty FLA Each 090A 25...

Page 18: ...60 62 5 83 2 90 4 460 3 60 31 3 41 7 45 8 36 208 3 60 75 1 99 110 3 230 3 60 86 6 113 3 125 2 460 3 60 43 3 56 7 60 6 1 Unit with an electric heat accessory will always be wired for a single power su...

Page 19: ...036 21371 001 B 0203 Unitary Products Group 19...

Page 20: ...change without notice Printed in U S A 036 21371 001 B 0203 Copyright by Unitary Products Group 42003 All rights reserved Supersedes 036 21371 001 A 0402 Unitary 5005 Norman Products York OK Group Dr...

Reviews: