background image

036-21342-002 Rev. E (0505)

2

Unitary Products Group

SYSTEM OPERATION

This heat pump model is equipped with both YorkGuard V
heat pump control and TS compressor control. The interface
control 6CF board is used to bypass the first stage of heat
when the outdoor temperature falls below certain tempera-
tures. The TS control board is used only to switch between 1
and 2 cylinder operation. The fault codes and pressure switch
on the TS control board are bypassed using the jumpers
between the test and "PS" pins.

1.

Anti-short Cycle Timer
The five-minute time delay on YorkGuard V will be used
to prevent the system from short cycling after the ther-
mostat off or power interrupt. This time delay can be
bypassed by temporarily shorting the test terminals on
YorkGuard V for 3 seconds. Since a jumper was factory
installed across the test pins on the TS control board, the
anti-short cycle timer on the TS control board is
bypassed.

2.

First Stage Cooling
This heat pump model is equipped with a Twin-Single
compressor. With a call for first stage cooling, the com-
pressor operates one cylinder. The run winding (R) is
connected through the upper left contactor (A) and to the
capacitor and the start winding (S) is connected to line
voltage. The system operates at low discharge pressure
and high suction pressure.

3.

Second Stage of Cooling
 With a call for second stage cooling, the TS control will
shut the compressor off for two seconds then energize
relays R1 and R2 on the TS control board. This will de-
energize (open) the upper left contactor (A) and energize
(close) the lower right contactor (B), connecting the com-
pressor run winding (R) to the line voltage and start
winding (S) to the capacitor. The compressor runs in the
reverse direction with two cylinders compared to the first
stage. The system will operate with two cylinders until
both first and second stage are satisfied. The Y2OUT
signal from the relay board causes the indoor blower to
function at high speed.

If the room thermostat calls for second stage cooling
(Y2) on two consecutive cooling cycles, the next call for
cooling for either first or second stage will energize the
unit in second stage mode. The above mode will be reset
to permit start up on the first stage with only a Y1 call
when the second stage operation cycle runs less than 15
minutes or when 24V to the TS control board is discon-
nected.

4.

6K Relay on the 6CF Control Board
The 6K relay on the 6CF interface board operates as fol-
lows. See Figure 1:

a.

If the YorkGuard V defrost control balance point set-
ting is 45°F, the 6K relay will be:

• Energized if liquid temperature goes below 35°F.

• De-energized if the liquid temperature goes above 

35°F AND the ambient is greater than 42°F for five 
minutes AND the unit is not in defrost.

b.

If the YorkGuard V defrost control balance point set-
ting is at anything but 45°F, the 6K relay will be:

• Energized if liquid temperature goes below 45°F.

• De-energized if the liquid temperature goes above 

45°F AND the ambient is greater than 55°F AND 
the unit is not in defrost.

5.

Heating mode with the de-energized 6K relay 
The TS compressor operates similar to the first and sec-
ond stage of cooling modes except there is no O input
from the thermostat, the reversing valve is not energized,
and the system operates in heating heat pump mode.
The YorkGuard V control and the liquid temperature will
not allow the system to go into the defrost mode.

6.

Heating mode with the energized 6K Relay
The energized 6K relay on the interface board (6CF) will
connect Y1 and Y2 and disconnect Y2OUT from the TS
control to the indoor blower if the J1 pin is not in the ON
position. The compressor will operate only in second
stage regardless of the first or second stage call from the
thermostat. The indoor blower will operate in low air
mode. The indoor discharge air temperature should be
about 10°F hotter than a normal heat pump. If high-
speed air is preferred, move J1 pin to the ON position at
the interface board (6CF). This will send the Y2OUT sig-
nal back to the indoor blower for the high speed air.

 FIGURE 1 :  6CF Interface Board

Y2

Y2 OUT

6K

NC

6K

NC

J1

6K

NO

R

Y2

Y1

Y2 OUT

24V (R) FROM
YORKGUARD

Summary of Contents for E4TS030

Page 1: ...been tested to provide 1 3 greater protection than conven tional units PROTECTED COMPRESSORS The Twin Single compres sor is protected against high pressure Hard start components are included to ensure...

Page 2: ...hermostat calls for second stage cooling Y2 on two consecutive cooling cycles the next call for cooling for either first or second stage will energize the unit in second stage mode The above mode will...

Page 3: ...2650 3200 3200 COIL FACE AREA SQ FT 20 0 20 0 20 0 20 0 ROWS DEEP 1 1 2 2 FIN INCH 16 16 13 13 LIQUID LINE OD 3 8 3 8 3 8 3 8 VAPOR LINE OD 7 8 7 8 7 8 7 8 UNIT CHARGE LBS OZ 3 3 The Unit Charge is c...

Page 4: ...TIONAL CHARGE OZ G1FA G1UA048S17 21 78 701 0 702 0 G1FA G1UA060S21 24 84 702 10 703 0 703 0 G1FA060S21 24T 84 703 0 703 0 G2FD046 S H 17 78 701 0 702 0 G2FD042 S H 21 78 701 0 G2FD048 S H 21 24 84 701...

Page 5: ...040 27400 22200 15 2 13 8 2 1605 49000 36400 11 6 E4TS060 F 2 3 FV060 10 15 20 25 24 1 1220 27800 23400 14 5 13 2 2 1875 55500 40500 10 4 N1VSD20 7 5 10 15 20 25 30 G2FD060S24 1 1200 27800 23400 14 5...

Page 6: ...1 1 640 20200 15200 14 1 12 5 2 1200 35800 25800 11 2 G2FD048S21 1 640 20400 15400 14 3 12 8 2 1200 36000 26000 11 3 G1UA060S21 1 640 21000 15800 14 6 13 1 2 1200 37000 26600 11 4 G1FA060S21 1 640 210...

Page 7: ...20V 24 G2FD060S24 1 1000 27000 20400 13 7 12 6 2 1800 55000 39600 10 0 G2FD061H24 1 1000 28000 20800 14 0 12 8 2 1800 56000 40000 10 2 P1XUD20V 24 G1UA060S24 1 990 27000 20400 13 8 12 5 2 1800 55500 4...

Page 8: ...1065 27000 16000 9 2 3 64 E4TS036 N1VSC16 5 7 5 10 15 20 21 G2FD048S21 1 770 19600 3 78 2 770 31600 19000 8 7 3 52 2 1185 35000 20800 9 2 3 54 N1VSD20 7 5 10 15 20 25 30 24 G2FD048S24 1 780 20000 3 8...

Page 9: ...540 12400 3 54 2 540 24200 14200 8 3 3 39 2 1050 26400 15400 8 6 3 58 G1FA048S17 1 540 12400 3 54 2 540 24200 14200 8 3 3 39 2 1050 26400 15400 8 6 3 58 P1XUC16V075 21 G2FD042S21 1 600 13000 3 70 2 60...

Page 10: ...2400 19000 8 1 3 44 2 1220 36000 21200 8 5 3 70 G1FA048S21 1 650 17200 3 52 2 650 32400 19000 8 1 3 44 2 1220 36000 21200 8 5 3 70 G2FD048S21 1 650 17400 3 54 2 650 32600 19400 8 2 3 48 2 1220 36200 2...

Page 11: ...0 3 64 2 715 33400 20200 8 7 3 64 2 1260 37000 22400 9 0 3 90 G1FA060S24 1 715 18800 3 64 2 715 33400 20200 8 7 3 64 2 1260 37000 22400 9 0 3 90 E4TS048 P1XUC16V075 21 G1UA060S21 1 880 20800 3 24 2 88...

Page 12: ...4 G2FD061H24 1 915 22600 3 40 2 915 45000 25600 8 0 3 44 2 1620 48500 27600 8 3 3 62 E4TS060 P1XDD20V112 G2FD060S24 1 1000 23400 3 38 2 1000 49500 26000 7 5 3 28 2 1800 54000 28400 7 9 3 46 G2FD061H24...

Page 13: ...90 23 26 17 97 23 41 K W 3 06 2 90 2 79 2 79 2 77 3 09 2 94 2 86 2 86 2 85 3 12 2 97 2 93 2 93 2 92 E4TS030S06A WITH N1VSC1606 G2FD048S21 LOW CFM 1 CYLINDER OPERATION CONDENSER ENTERING AIR TEMPERATU...

Page 14: ...5 3 54 3 42 3 33 3 33 3 24 115 T C 33 74 30 98 28 42 28 42 27 19 34 01 31 83 29 53 29 53 29 18 34 29 32 67 30 65 30 65 31 18 S C 16 85 22 69 26 44 21 15 26 79 18 07 24 40 27 91 22 31 28 98 19 30 26 12...

Page 15: ...27 17 56 14 12 18 17 11 73 15 40 17 40 13 89 18 84 12 54 16 87 17 24 13 66 19 51 K W 1 62 1 58 1 56 1 56 1 56 1 64 1 61 1 59 1 59 1 58 1 66 1 63 1 61 1 61 1 60 Air Handler Coil T C S C KW N1VSD20 G2FD...

Page 16: ...4 57 4 57 4 48 5 27 5 03 4 75 4 75 4 64 5 47 5 20 4 93 4 93 4 80 E4TS048S06A WITH N1VSD2006 G2FD060S24 LOW CFM 1 CYLINDER OPERATION CONDENSER ENTERING AIR TEMPERATURE ID CFM 850 1040 1140 ID DB F 80 8...

Page 17: ...81 125 T C 49 61 47 33 43 91 43 91 42 66 50 19 47 59 45 10 45 10 44 17 50 77 47 86 46 28 46 28 45 69 S C 26 29 36 41 43 93 35 07 40 19 27 46 38 64 45 25 35 77 42 94 28 63 40 87 46 58 36 46 45 69 K W...

Page 18: ...36 1 08 20 52 1 09 20 67 1 09 70 18 50 1 16 18 66 1 17 18 81 1 17 80 16 64 1 24 16 79 1 25 16 95 1 25 47 60 16 02 1 05 16 15 1 06 16 28 1 08 70 14 90 1 12 15 00 1 13 15 10 1 14 80 13 77 1 19 13 85 1 2...

Page 19: ...KW MBTUH KW N1VSB12 G2FD046S17 0 98 1 04 0 89 0 94 Variable Speed Furnace Coil MBTUH KW MBTUH KW P1XDB12V G2FD046S17 0 97 1 03 0 87 0 96 P1XUB12V G2FD046S17 0 97 1 02 0 87 0 95 P1XUB12V G1UA048S17 0...

Page 20: ...12 G2FD046S17 0 98 1 00 Variable Speed Furnace Coil MBTUH KW P1XDB12V G2FD046S17 0 87 0 94 P1XUB12V G2FD046S17 0 86 0 94 P1XUB12V G1UA048S17 0 87 0 94 P1XUB12V G1FA048S17 0 87 0 94 P1DUB16V G2FD046S17...

Page 21: ...1 1 87 70 27 16 2 00 28 00 2 00 28 83 2 00 80 24 88 2 12 25 62 2 12 26 36 2 13 47 60 25 88 1 80 26 28 1 81 26 68 1 81 70 23 31 1 90 23 80 1 91 24 29 1 91 80 20 73 1 99 21 32 2 00 21 90 2 01 35 60 22 7...

Page 22: ...12 53 2 72 12 80 2 81 E4TS060S06A WITH N1VSD2006 G2FD061S21 LOW CFM 1 CYLINDER OPERATION ID CFM 1000 1200 1350 OD DB ID DB F MBTUH1 2 KW MBTUH1 2 KW MBTUH1 2 KW 60 60 36 04 2 14 36 57 2 14 37 10 2 13...

Page 23: ...3 MATCHING INDOOR COMPONENTS G1UA UPFLOW G2FD MULTI POSITION UPFLOW HORIZONTAL AND DOWNFLOW G1FA FULL CASED AIR HANDLERS FOR NON FURNACE APPLICATIONS N1VS MODULAR BLOWER UPFLOW HORIZONTAL AND DOWNFLOW...

Page 24: ...e without notice Printed in U S A 036 21342 002 Rev E 0505 Copyright by York International Corp 2005 All rights reserved Supersedes 036 21342 002 Rev D 1104 Unitary 5005 Norman Product York OK Group D...

Reviews: