ACCESSORIES (FIELD-INSTALLED)

Three-Phase Electric Heaters are available in several
capacities to provide maximum flexibility. The heater can be
selected to precisely meet the supplemental heating
requirement of the conditioned space.

These heaters are designed for easy field-installation over the
supply air opening of the indoor unit. They have been tested by
Underwriters’ Laboratories and will be shipped with a UL label.
Every heater will be fully protected against excessive current
and temperature by fuses and two high limit thermostats.

Units with Electric Heat will require only one power supply for
both the heating elements and the supply air blower motor, and
the power wiring can be protected by either dual element/time
delay fuses or an inverse time circuit breaker.

Supply Air Plenums and Return Air Grilles (expanded metal)
are available for free-standing indoor units located in the
conditioned space. Both accessories are finished to match the
exterior of the basic unit, and both can be applied with either
vertical or horizontal units. The supply air plenums are fully
insulated and have double-deflection, adjustable grilles.

Base Sections are available to raise vertical indoor units above
the floor. Outdoor air may be introduced through these bases
by cutting an access opening for the outdoor air duct
connection. These bases are finished to match the exterior of
the basic unit. They may have to be insulated in the field for
certain applications.

Decorative Coil Guards can be field installed to enhance
protection of the unit.

Thermostats with either manual or automatic changeover are
available for precise control of the temperature within the
conditioned space. The manual thermostat has a four-position
selector switch - COOL, OFF, HEAT, and EMERGENCY HEAT,
and three stages of control - one stage of cooling and two
stages of heating. The automatic thermostat has a
three-position selector switch - OFF, AUTOMATIC and
EMERGENCY HEAT, and four stages of control - two stages
of cooling and two stages of heating.

Both thermostats have a two-position fan switch, AUTO and
ON to provide intermittent or continuous blower operation.

NOTE:

The automatic changeover thermostat must be used
on units equipped with a field-supplied economizer.

The first cooling stage of the automatic thermostat will
only control the position of the reversing valve; the
system will still operate with only one stage of cooling.

The EMERGENCY HEAT position on the selector
switch and the second stage of heating will only
function on systems with an electric heat accessory.

STATIC RESISTANCES FOR UNIT ACCESSORIES (IWG)

Unit Model

Accessory

CFM

2400

2700

3000

3300

3600

FEH090

ELECTRIC HEAT 

10 KW

0.01

0.01

0.01

0.02

0.02

16 KW

0.01

0.02

0.02

0.03

0.04

26 KW

0.03

0.04

0.05

0.06

0.07

36 KW

0.05

0.07

0.08

0.10

0.11

Supply Air Plenum

0.03

0.03

0.04

0.05

0.06

Return Air Grille

0.02

0.03

0.04

0.05

0.06

CFM

3200

3600

4000

4400

4800

FEH120

ELECTRIC HEAT 

10 KW

0.02

0.02

0.03

0.03

0.04

16 KW

0.03

0.04

0.05

0.06

0.07

26 KW

0.06

0.07

0.09

0.11

0.13

36 KW

0.09

0.11

0.14

0.17

0.20

Supply Air Plenum

0.05

0.06

0.07

0.08

0.10

Return Air Grille

0.05

0.06

0.07

0.08

0.10

515.41-TG1Y

Unitary Products Group

7

Summary of Contents for E1FB120

Page 1: ... heating cycles To eliminate the costly cabinet deterioration problems usually associated with outdoor equipment all sheet metal parts are constructed of commercial grade G90 galvanized steel After fabrication each part is thoroughly cleaned to remove any grease or dirt from its surfaces The parts that will be exposed to the weather are then coated with a desert sand powder paint to assure a quali...

Page 2: ... and defrost cycles condensate will drip from the underside of the unit coils and that this condensate will freeze when the temperature of the outdoor air is below 32 F A gravel bed or some other means of handling this condensate may have to be provided These indoor units are built in a single cabinet with two condensate drain pans This allows the units to be installed in either the vertical or ho...

Page 3: ...H120 121 9 0 117 3 0 63 2 1 Outdoor Unit Sound Rating2 bels E2FB090 8 6 E1FB120 9 0 1Ratings are in accordance with ARI Standard 240 2Sound ratings are in accordance with ARI Standard 270 3Deduct 1 MBH when a unit operates at 208 volts Air Temperature on OUTDOOR Coil F Air Temperature on INDOOR Coil F Minimum Maximum Minimum Maximum Cool Heat Cool Heat Cool Heat Cool Heat 40 db 0 db1 115 db 75 db ...

Page 4: ... 71 9 8 51 119 0 101 2 8 88 110 5 96 3 9 93 93 9 91 0 11 00 80 65 5 64 0 60 9 88 0 83 2 77 8 76 55 8 53 7 49 9 74 9 70 0 64 7 72 46 1 43 3 38 9 61 7 56 9 51 5 80 62 82 5 76 8 5 40 74 3 73 7 6 91 66 0 66 0 8 05 106 5 105 8 8 60 98 8 98 8 9 61 84 0 84 0 10 65 76 67 8 64 3 58 2 92 6 87 5 81 9 72 58 8 54 9 49 5 79 5 74 3 68 7 68 49 7 45 5 40 8 66 3 61 2 55 6 72 57 74 0 73 1 4 91 66 5 66 5 6 42 59 6 59...

Page 5: ... 8 4 98 70 5 5 41 81 0 6 07 91 5 6 86 102 0 7 65 70 20 8 3 53 30 4 4 16 40 0 4 75 51 8 5 15 63 6 5 58 73 2 6 25 82 8 7 05 92 4 7 84 80 17 5 3 72 26 2 4 35 35 0 4 95 45 8 5 36 56 8 5 79 65 5 6 47 74 3 7 26 83 0 8 06 E1FB120 F3EH120 4000 Supply Air CFM2 50 HZ 60 25 9 4 66 42 5 5 34 59 0 6 01 75 4 6 67 92 0 7 35 108 5 8 02 125 0 8 68 141 5 9 35 70 24 1 4 76 39 6 5 49 55 1 6 23 70 6 6 96 86 1 7 70 101...

Page 6: ... diagram inside the motor terminal box when the motor leads have to be reconnected for a 208 or 230 volt power supply Motor Specifications 1750 RPM inherently protected 208 230 460 3 60 or 380 415 3 50 1 15 service factor solid base permanently lubricated 56 frame llllball bearings RPM range for the standard drive components Exceeds the BHP limitations of the standard blower motor SUPPLY AIR PLENU...

Page 7: ...an be field installed to enhance protection of the unit Thermostats with either manual or automatic changeover are available for precise control of the temperature within the conditioned space The manual thermostat has a four position selector switch COOL OFF HEAT and EMERGENCY HEAT and three stages of control one stage of cooling and two stages of heating The automatic thermostat has a three posi...

Page 8: ...CCESS 1 3 8 OD SUCTION CONN 5 8 OD LIQUID CONN COMPRESSOR AND CONDENSER FAN MOTOR ACCESS 7 8 KNOCKOUT ACCESSORY WIRING ENTRY 1 3 8 DIA POWER WIRING ENTRY 7 8 DIA CONTROL WIRING ENTRY 32 1 2 5 4 1 8 2 5 CONTROL BOX ACCESS 31 3 4 42 3 4 AIR ON 3 SIDES EFB090 7 1 2 Ton AIR OUT AIR IN AIR OUT 2 3 4 32 2 1 4 32 1 2 70 1 8 8 3 4 5 3 8 CONTROL BOX ACCESS GUAGE LINE ACCESS 39 1 3 8 OD VAPOR LINE 5 8 OD LI...

Page 9: ...ectric heater a supply air plenum or a base is used 2This dimension is required for removal of the coil Only 26 is required for normal servicing 3Although no clearance is required for service and operation some clearance may be required for routing the power wiring and the control wiring 4Allow enough clearance to trap the condensate drain line MINIMUM CLEARANCES Side with RETURN AIR opening 24 Si...

Page 10: ...ACCESSORY DIMENSIONS Nom KW Model Number 10 2HS04501025 46 50 16 2HS04501625 46 50 26 2HS04502625 46 50 36 2HS04503625 46 50 515 41 TG1Y 10 Unitary Products Group ...

Page 11: ...h 3 x 24 3 x 32 Finned Length inches 45 5 45 5 Face Area square feet 7 6 10 1 Tube Copper OD inches 3 8 3 8 Fins Aluminum per inch 13 13 Centrifugal Blower Forward Curve Diameter x Width inches 15 X 15 15 X 15 Blower Motor1 Nominal Rating HP 1 1 2 2 Filters Throwaway Quantity Per Unit 16 x 25 x 1 4 4 Total Face Area square feet 11 1 11 1 Refrigerant 22 Lbs Holding Charge2 Pumpdown Capacity5 12 0 1...

Page 12: ...6 280 415 3 50 37 4 51 8 60 6 283 F3EH120 10 208 3 60 20 8 35 4 40 8 133 230 3 60 24 1 38 6 40 8 134 460 3 60 12 0 19 3 20 12 216 380 3 50 9 5 16 9 20 12 203 415 3 50 10 4 18 6 20 12 202 16 208 3 60 33 4 51 1 60 6 144 230 3 60 38 5 56 6 60 4 230 460 3 60 19 2 28 3 30 10 235 380 3 50 15 2 24 0 25 10 229 415 3 50 16 6 26 4 30 10 227 26 208 3 60 54 2 77 1 80 3 191 230 3 60 62 5 86 6 90 2 241 460 3 60...

Reviews: