BLOWER MOTOR AND DRIVE DATA

RPM

CFM

ESP

2

BHP

KW

ESP

2

BHP

KW

ESP

2

BHP

KW

ESP

2

BHP

KW

ESP

2

BHP

KW

F3EH090

2400

2700

3000

3300

3600

600

0.30

0.62

0.79

0.21

0.70

0.76

0.09

0.78

0.89

-

-

-

-

-

-

655

0.43

0.70

0.86

0.39

0.78

0.83

0.26

0.87

0.97

0.11

0.96

1.07

-

-

-

700

0.52

0.77

0.93

0.48

0.85

0.90

0.40

0.95

1.06

0.28

1.06

1.16

0.14

1.17

1.26

800

0.82

0.97

1.10

0.81

1.06

1.07

0.74

1.18

1.27

0.63

1.30

1.38

0.51

1.42

1.49

880

1.10

1.11

1.24

1.09

1.24

1.21

1.02

1.37

1.45

0.91

1.50

1.55

0.78

1.64

1.70

900

1.15

1.15

1.27

1.14

1.28

1.24

1.07

1.42

1.49

0.97

1.55

1.60

0.87

1.70

1.74

1000

1.49

1.35

1.46

1.47

1.48

1.43

1.42

1.63

1.65

1.35

1.81

1.82

1.27

2.02

2.02

F3EH120

3200

3600

4000

4400

4800

700

0.39

1.01

1.17

0.26

1.17

1.27

0.05

1.33

1.38

-

-

-

-

-

-

800

0.75

1.25

1.38

0.63

1.42

1.51

0.43

1.60

1.64

0.22

1.80

1.78

-

-

-

900

1.08

1.48

1.60

0.98

1.70

1.77

0.81

1.92

1.93

0.61

2.18

2.09

0.34

2.45

2.23

950

1.29

1.61

1.71

1.19

1.86

1.90

1.02

2.12

2.07

0.86

2.39

2.23

0.56

2.67

2.42

1000

1.46

1.75

1.83

1.38

2.02

2.02

1.23

2.30

2.20

1.06

2.60

2.39

0.78

2.90

2.59

1Unit resistance is based on a wet indoor coil and clean filters.

2

Available static pressure in IWG to overcome the resistance of the duct system and any accessoires added to the unit. Refer to the table above for additional motor and drive data and to the

  table on page 7 for the resistance of these accessories.

3

Refer to Form 515.41-AD1 for blower performance curves.

SUPPLY AIR BLOWER PERFORMANCE

1,3

Indoor

Unit

Model

Motor*

HP

Blower

HP

Adjustable Motor Pulley

Fixed Blower Pulley

Belt

Pitch Diameter,

(in.)

Bore,

(in.)

Pitch Diameter,

(in.)

Bore,

(in.)

Designation

Pitch Length,

(in.)

FEH090

1-1/2

655-880

2.8 - 3.8

7/8

7.5

1

A36

37.3

FEH120

2

700-950

7.0

**These motors will always be wired for a 460 volt power supply. Refer to the wiring
   diagram inside the motor terminal box when the motor leads have to be reconnected
   for a 208 or 230 volt power supply.

*Motor Specifications:

1750 RPM

inherently protected

208/230/460-3-60**
 or 380/415-3-50

1.15 service factor

solid base

permanently lubricated

56 frame

llll

ball bearings

RPM range for the standard drive components.

Exceeds the BHP limitations of the standard blower motor.

SUPPLY AIR PLENUM PERFORMANCE

18˚

22-1/2˚

45˚

18˚

18˚

Indoor

Unit

Model

FEH

CFM

Face
Velo-

city

(FPM)

Angle of Deflection

Vertical

 Louvers

1

(Plan View)

Horizontal

Louvers

2

(Elevation

View)

Vertical

 Louvers

1

(Plan View)

Horizontal

Louvers

2

(Elevation

View)

Vertical

 Louvers

1

(Plan View)

Horizontal

Louvers

2

(Elevation

View)

Throw

(Feet)

3

Spread

(Feet)

3

Throw

(Feet)

3

Spread

(Feet)

3

Throw

(Feet)

3

Spread

(Feet)

3

Min.

Max.

Min.

Max. Drop (Feet)

4

Min.

Max.

Min.

Max. Drop (Feet)

4

Min.

Max.

Min.

Max. Drop (Feet)

4

090

2400

615

47

74

20

29

19

9

34

53

23

33

17

8

26

39

45

65

9

5

2700

690

53

83

22

32

20

10

39

59

25

36

18

9

29

45

48

71

10

5

3000

770

59

92

24

35

21

10

42

66

27

40

19

9

32

50

52

78

10

5

3300

845

65

101

26

38

21

10

46

73

29

44

19

9

35

55

56

85

10

5

3600

920

71

110

28

41

22

11

50

79

32

47

20

10

38

60

60

91

11

6

120

3200

820

63

98

25

37

21

10

45

70

29

43

19

9

34

53

54

82

10

5

3600

920

71

110

28

41

22

11

50

79

32

47

20

10

38

60

60

91

11

6

4000 1025

78

123

30

45

22

11

56

88

35

52

20

10

42

66

67

102

11

6

4400 1130

86

135

33

49

23

12

62

97

38

57

21

11

47

73

76

115

12

6

4800 1230

94

147

35

53

23

12

68

106

41

62

21

11

51

80

85

127

12

6

1Adjusting the vertical louvers will vary the throw, the spread and the drop.

2

Adjusting the horizontal louvers will only vary the drop.

3

The velocity of the air will be 125 ft./min. at the minimum distance and 80 ft./min. at the maximum distance.

4

The velocity of the conditioned air at the bottom of the drop will be 50 ft./min. Drafts will occur if the drop extends into the occupied level of the conditioned space.

515.41-TG1Y

6

Unitary Products Group

Summary of Contents for E1FB120

Page 1: ... heating cycles To eliminate the costly cabinet deterioration problems usually associated with outdoor equipment all sheet metal parts are constructed of commercial grade G90 galvanized steel After fabrication each part is thoroughly cleaned to remove any grease or dirt from its surfaces The parts that will be exposed to the weather are then coated with a desert sand powder paint to assure a quali...

Page 2: ... and defrost cycles condensate will drip from the underside of the unit coils and that this condensate will freeze when the temperature of the outdoor air is below 32 F A gravel bed or some other means of handling this condensate may have to be provided These indoor units are built in a single cabinet with two condensate drain pans This allows the units to be installed in either the vertical or ho...

Page 3: ...H120 121 9 0 117 3 0 63 2 1 Outdoor Unit Sound Rating2 bels E2FB090 8 6 E1FB120 9 0 1Ratings are in accordance with ARI Standard 240 2Sound ratings are in accordance with ARI Standard 270 3Deduct 1 MBH when a unit operates at 208 volts Air Temperature on OUTDOOR Coil F Air Temperature on INDOOR Coil F Minimum Maximum Minimum Maximum Cool Heat Cool Heat Cool Heat Cool Heat 40 db 0 db1 115 db 75 db ...

Page 4: ... 71 9 8 51 119 0 101 2 8 88 110 5 96 3 9 93 93 9 91 0 11 00 80 65 5 64 0 60 9 88 0 83 2 77 8 76 55 8 53 7 49 9 74 9 70 0 64 7 72 46 1 43 3 38 9 61 7 56 9 51 5 80 62 82 5 76 8 5 40 74 3 73 7 6 91 66 0 66 0 8 05 106 5 105 8 8 60 98 8 98 8 9 61 84 0 84 0 10 65 76 67 8 64 3 58 2 92 6 87 5 81 9 72 58 8 54 9 49 5 79 5 74 3 68 7 68 49 7 45 5 40 8 66 3 61 2 55 6 72 57 74 0 73 1 4 91 66 5 66 5 6 42 59 6 59...

Page 5: ... 8 4 98 70 5 5 41 81 0 6 07 91 5 6 86 102 0 7 65 70 20 8 3 53 30 4 4 16 40 0 4 75 51 8 5 15 63 6 5 58 73 2 6 25 82 8 7 05 92 4 7 84 80 17 5 3 72 26 2 4 35 35 0 4 95 45 8 5 36 56 8 5 79 65 5 6 47 74 3 7 26 83 0 8 06 E1FB120 F3EH120 4000 Supply Air CFM2 50 HZ 60 25 9 4 66 42 5 5 34 59 0 6 01 75 4 6 67 92 0 7 35 108 5 8 02 125 0 8 68 141 5 9 35 70 24 1 4 76 39 6 5 49 55 1 6 23 70 6 6 96 86 1 7 70 101...

Page 6: ... diagram inside the motor terminal box when the motor leads have to be reconnected for a 208 or 230 volt power supply Motor Specifications 1750 RPM inherently protected 208 230 460 3 60 or 380 415 3 50 1 15 service factor solid base permanently lubricated 56 frame llllball bearings RPM range for the standard drive components Exceeds the BHP limitations of the standard blower motor SUPPLY AIR PLENU...

Page 7: ...an be field installed to enhance protection of the unit Thermostats with either manual or automatic changeover are available for precise control of the temperature within the conditioned space The manual thermostat has a four position selector switch COOL OFF HEAT and EMERGENCY HEAT and three stages of control one stage of cooling and two stages of heating The automatic thermostat has a three posi...

Page 8: ...CCESS 1 3 8 OD SUCTION CONN 5 8 OD LIQUID CONN COMPRESSOR AND CONDENSER FAN MOTOR ACCESS 7 8 KNOCKOUT ACCESSORY WIRING ENTRY 1 3 8 DIA POWER WIRING ENTRY 7 8 DIA CONTROL WIRING ENTRY 32 1 2 5 4 1 8 2 5 CONTROL BOX ACCESS 31 3 4 42 3 4 AIR ON 3 SIDES EFB090 7 1 2 Ton AIR OUT AIR IN AIR OUT 2 3 4 32 2 1 4 32 1 2 70 1 8 8 3 4 5 3 8 CONTROL BOX ACCESS GUAGE LINE ACCESS 39 1 3 8 OD VAPOR LINE 5 8 OD LI...

Page 9: ...ectric heater a supply air plenum or a base is used 2This dimension is required for removal of the coil Only 26 is required for normal servicing 3Although no clearance is required for service and operation some clearance may be required for routing the power wiring and the control wiring 4Allow enough clearance to trap the condensate drain line MINIMUM CLEARANCES Side with RETURN AIR opening 24 Si...

Page 10: ...ACCESSORY DIMENSIONS Nom KW Model Number 10 2HS04501025 46 50 16 2HS04501625 46 50 26 2HS04502625 46 50 36 2HS04503625 46 50 515 41 TG1Y 10 Unitary Products Group ...

Page 11: ...h 3 x 24 3 x 32 Finned Length inches 45 5 45 5 Face Area square feet 7 6 10 1 Tube Copper OD inches 3 8 3 8 Fins Aluminum per inch 13 13 Centrifugal Blower Forward Curve Diameter x Width inches 15 X 15 15 X 15 Blower Motor1 Nominal Rating HP 1 1 2 2 Filters Throwaway Quantity Per Unit 16 x 25 x 1 4 4 Total Face Area square feet 11 1 11 1 Refrigerant 22 Lbs Holding Charge2 Pumpdown Capacity5 12 0 1...

Page 12: ...6 280 415 3 50 37 4 51 8 60 6 283 F3EH120 10 208 3 60 20 8 35 4 40 8 133 230 3 60 24 1 38 6 40 8 134 460 3 60 12 0 19 3 20 12 216 380 3 50 9 5 16 9 20 12 203 415 3 50 10 4 18 6 20 12 202 16 208 3 60 33 4 51 1 60 6 144 230 3 60 38 5 56 6 60 4 230 460 3 60 19 2 28 3 30 10 235 380 3 50 15 2 24 0 25 10 229 415 3 50 16 6 26 4 30 10 227 26 208 3 60 54 2 77 1 80 3 191 230 3 60 62 5 86 6 90 2 241 460 3 60...