ELECTRIC HEATING (DJ***C/E MODELS) 

Nickel chromium electric heating elements shall be provided 
as required by the application with 1 or 2 stage control, as 
required, from 13.5 KW to 72 KW capacities. The heating 
section shall have a primary limit control(s) and automatic 
reset to prevent the heating element system from operating 
at an excessive temperature. Units with Electric Heating shall 
be wired for a single point power supply with branch circuit 
fusing (where required). 

UNIT OPERATING CHARACTERISTICS

Unit shall be capable of starting and running at 125° F 
outdoor temperature, exceeding maximum load criteria of 
ARI Standard 340/360. The compressor, with standard 
controls, shall be capable of operation down to 25° F outdoor 
temperature. Accessory low ambient kit shall be available for 
operation to 0° F. Unit shall be provided with fan time delay to 
prevent cold air delivery before heat exchanger warms up 
(Gas heat only). 

ELECTRICAL REQUIREMENTS

All unit power wiring shall enter unit cabinet at a single factory 
provided location and be capable of side or bottom entry, to 
minimize roof penetrations and avoid unit field modifications. 
Separate side and bottom openings shall be provided for the 
control wiring. 

STANDARD LIMITED WARRANTIES

Compressor 5 Years

Heat Exchanger 10 Years

Electric Heat Element 5 Years

Other Parts 1 Year

OPTIONAL OUTDOOR AIR

 (Shall be made available by 

either/or): 

ELECTRONIC ENTHALPY AUTOMATIC ECONO-
MIZER

 - Outdoor and return air dampers that are inter-

locked and positioned by a fully-modulating, spring-
return damper actuator. The maximum leakage rate for 
the outdoor air intake dampers shall not exceed 2% 
when dampers are fully closed and operating against a 
pressure differential of 0.5 IWG. A unit-mounted potenti-
ometer shall be provided to adjust the outdoor and return 
air damper assembly to take in CFM of outdoor air to 
meet the minimum ventilation requirement of the condi-
tioned space during normal operation. During econo-
mizer operation, a mixed-air temperature control shall 
modulate the outdoor and return air damper assembly to 
prevent the supply air temperature from dropping below 
55°F. Changeover from compressor to economizer oper-
ation shall be provided by an integral electronic enthalpy 
control that feeds input into the basic module. The out-
door intake opening shall be covered with a rain hood 
that matches the exterior of the unit. Water eliminator/fil-

ters shall be provided. Simultaneous economizer/com-
pressor operation is also possible. Dampers shall fully 
close on power loss.

BAS-READY ECONOMIZER -

 Outdoor and return air 

dampers that are interlocked and positioned by a fully-
modulating, spring return damper actuator. The maxi-
mum leakage rate for the outdoor air intake dampers 
shall not exceed 2% when dampers are fully closed and 
operating against a pressure differential of 0.5 IWG.

For units with optional VAV or Simplicity® Intelli-Com-
fort™ control, free-cooling shall be available while the 
outdoor dry bulb temperature (OAT) remains below a 
programmable set-point of the controller. Field-installed 
humidity sensors for either outdoor air or outdoor & 
return air streams are available to provide free-cooling 
based on single-enthalpy or dual-enthalpy configura-
tions, respectively. If free-cooling is available, a call for 
cooling shall modulate the economizer in order to main-
tain a supply air temperature (SAT) programmable set-
point. With the use of a field-installed indoor air quality 
sensor, the controller shall provide Demand Ventilation 
by modulating the economizer dampers to allow more 
outside airflow upon detection of elevated indoor CO

2

 

concentrations above a programmable set-point. With an 
additional field-installed outdoor air quality sensor, Differ-
ential Demand Ventilation shall be provided.

The outdoor intake opening shall be covered with a rain 
hood that matches the exterior of the unit. Water elimina-
tor/filters shall be provided.

Simultaneous economizer/compressor operation is also 
possible. Dampers shall fully close on power loss.

MOTORIZED OUTDOOR AIR DAMPERS

 - Outdoor and 

return air dampers that are interlocked and positioned by 
a 2-position, spring-return damper actuator. The maxi-
mum leakage rate for the outdoor air intake dampers 
shall not exceed 2% when dampers are fully closed and 
operating against a pressure differential of 0.5 IWG. A 
unit-mounted potentiometer shall be provided to adjust 
the outdoor and return air damper assembly to take in 
the design CFM of outdoor air to meet the ventilation 
requirements of the conditioned space during normal 
operation. Whenever the indoor fan motor is energized, 
the dampers open up to one of two pre-selected posi-
tions - regardless of the outdoor air enthalpy. Dampers 
return to the fully closed position when the indoor fan 
motor is de-energized. Dampers shall fully close on 
power loss. 

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE

ROOF CURB

 - 14" high, full perimeter curb with wood 

nailer (shipped knocked-down). 

100% BAROMETRIC RELIEF DAMPER

 - Contains a 

rain hood, air inlet screen, exhaust damper and mount-
ing hardware. Used to relieve internal air pressure 
through the unit. 

Summary of Contents for DJ 300

Page 1: ...ow pressure loss of charge switches and freezestats Scroll compressors Two stage heating provided by dual independent heat exchangers with aluminized steel tubes redundant gas valves spark ignition wi...

Page 2: ...FOR DJ300 13 Tbl Pg 8 ALTITUDE CORRECTION FACTORS 14 9 SUPPLY AIR BLOWER PERFORMANCE 15 TON COOLING ONLY 180 MBH BOTTOM DUCT CONNECTIONS 16 10 SUPPLY AIR BLOWER PERFORMANCE 17 5 TON COOLING ONLY 210...

Page 3: ...Switch Hinged Filter Door Tool Free Access Panels BG Coil Guard Dirty Filter Switch Hinged Filter Door Tool Free Access Panels BH Phase Monitor Coil Guard Dirty Filter Switch Hinged Filter Door Tool F...

Page 4: ...compressor discharge bypass valve is available for low cooling load applications Simplicity Controls Simplicity control boards have standardized a number of features previously available only as optio...

Page 5: ...rs The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling The rainhood is painted to match the basic un...

Page 6: ...modate other vendor s drives depend ing on their size In order to utilize the unit s mounting bracket the maximum recommended drive dimensions are as follows For 5 hp motor applications 13 H x 6 W x 7...

Page 7: ...is factory installed Includes air supply sensor return air sensor dirty filter indicator switch and air proving switch YORK COMMERCIAL COMFORT SYSTEM YCCS Provides rooftop system integration for YCCS...

Page 8: ...alti tudes up to 6 000 feet This accessory supplements the basic propane conversion kit SIDE DUCT FLANGES One inch flanges replace the supply and return air panels on the rear of the unit to accommod...

Page 9: ...2 2 EER Energy Efficiency Ratio at full load the cooling capacity in Btu s per hour Btuh divided by the power input in watts expressed in Btuh per watt Btuh watt IPLV3 3 IPLV Integrated Part Load Valu...

Page 10: ...18 3 105 4 92 6 79 8 5250 72 189 7 14 51 123 4 108 2 93 1 77 9 62 7 178 3 15 95 118 9 103 7 88 6 73 4 58 2 67 172 3 14 24 154 6 139 5 124 3 109 1 94 0 78 8 63 6 161 8 15 70 150 1 134 9 119 8 104 6 89...

Page 11: ...6 111 5 94 4 77 3 6500 72 218 3 17 77 143 8 125 0 106 3 87 5 68 7 204 8 19 63 137 9 119 1 100 3 81 6 62 8 67 202 6 17 33 183 9 165 1 146 4 127 6 108 8 90 1 71 3 189 9 19 18 178 3 159 5 140 8 122 0 10...

Page 12: ...112 7 7000 72 250 6 20 15 162 5 142 2 122 0 101 8 81 6 236 4 21 79 157 8 137 5 117 3 97 1 76 9 67 231 3 19 69 206 2 185 9 165 7 145 5 125 3 105 1 84 9 218 5 21 50 199 2 179 0 158 8 138 6 118 4 98 1 7...

Page 13: ...1 136 7 8750 72 306 8 27 83 201 3 176 1 150 8 125 5 100 2 286 9 30 20 195 1 169 8 144 6 119 3 94 0 67 293 9 27 37 259 0 233 7 208 5 183 2 157 9 132 7 107 4 280 1 29 98 253 1 227 9 202 6 177 3 152 0 12...

Page 14: ...the static pressure and BHP Since no temperature data is given we will assume an air temperature of 70 F Table 8 shows the correction factor to be 0 832 Corrected static pressure 1 5 x 0 832 1 248 IWC...

Page 15: ...261660 YTG D 0708 Johnson Controls Unitary Products 15 FIGURE 2 ALTITUDE TEMPERATURE CONVERSION FACTOR...

Page 16: ...0 0 9 5 2 4 7 0 7 5 7 5 1 208 VOLT AND HIGH STATIC DRIVE 965 6 0 1 2 2 9 2 6 1 0 3 6 3 2 0 8 4 0 3 6 0 5 4 7 4 2 0 4 5 0 4 4 980 5 5 1 3 3 0 2 7 1 1 3 7 3 3 0 9 4 1 3 7 0 6 4 8 4 3 0 5 5 1 4 6 1025 4...

Page 17: ...4 5 9 5 0 980 5 0 1 6 5 3 4 5 1 4 5 8 4 9 1 2 6 3 5 3 0 7 6 9 5 8 1010 4 0 1 8 5 8 4 9 1 7 6 3 5 3 1 5 6 9 5 8 1 0 7 5 6 3 1020 3 5 1 9 6 1 5 1 1 8 6 5 5 5 1 6 7 1 6 0 1 1 7 8 6 6 1035 3 0 2 0 6 2 5...

Page 18: ...9 1 2 6 3 5 3 0 7 6 9 5 8 0 2 7 3 6 1 1010 4 0 1 8 5 8 4 9 1 7 6 3 5 3 1 5 6 9 5 8 1 0 7 5 6 3 0 5 7 9 6 7 1020 3 5 1 9 6 1 5 1 1 8 6 5 5 5 1 6 7 1 6 0 1 1 7 8 6 6 0 6 8 3 7 0 1035 3 0 2 0 6 2 5 2 1 9...

Page 19: ...8 3 4 1 0 4 4 3 9 0 8 5 0 4 5 0 6 5 6 5 0 208 VOLT AND HIGH STATIC DRIVE 965 6 0 1 2 2 7 2 5 0 9 3 2 2 9 0 6 3 7 3 3 0 4 4 4 3 9 0 2 5 0 4 5 980 5 5 1 3 2 9 2 6 1 0 3 4 3 0 0 7 3 8 3 4 0 5 4 5 4 0 0 3...

Page 20: ...5 1 0 2 6 9 5 8 980 5 0 1 9 4 5 3 8 1 5 5 4 4 5 1 0 6 3 5 3 0 4 7 2 6 1 995 4 5 2 1 4 5 3 9 1 6 5 5 4 7 1 1 6 4 5 4 0 5 7 5 6 3 1025 3 5 2 3 4 9 4 1 1 8 5 8 4 9 1 3 6 7 5 7 0 7 8 0 6 7 1050 2 5 2 5 5...

Page 21: ...980 5 0 1 9 4 5 3 8 1 5 5 4 4 5 1 0 6 3 5 3 0 4 7 2 6 1 0 1 8 5 7 1 995 4 5 2 1 4 5 3 9 1 6 5 5 4 7 1 1 6 4 5 4 0 5 7 5 6 3 0 2 8 6 7 3 1025 3 5 2 3 4 9 4 1 1 8 5 8 4 9 1 3 6 7 5 7 0 7 8 0 6 7 1050 2...

Page 22: ...9 7 0 3 13 7 11 2 1215 4 0 2 7 8 6 7 0 2 1 10 4 8 5 1 4 12 3 10 1 0 6 14 3 11 7 1255 3 0 3 0 9 1 7 4 2 4 11 0 9 0 1 7 12 9 10 6 0 9 15 0 12 3 1290 2 0 3 2 9 5 7 8 2 7 11 5 9 4 2 0 13 5 11 1 1 2 15 6...

Page 23: ...CE IWG CFM 15 TON 17 5 TON 20 TON 25 TON 4500 6000 7200 6000 7500 9000 6000 8000 9400 7500 10000 12500 WET INDOOR COIL 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 ELECTRIC HEAT OPTIONS 18 KW 0 3 0...

Page 24: ...100 1 1 7 2 0 0 None 0 0 36 1 45 E18 18 0 1 21 7 36 1 45 E36 36 0 2 43 3 63 1 70 E54 54 0 2 65 0 74 0 90 E72 72 0 2 86 6 95 6 110 575 8 3 78 0 9 5 9 0 0 None 0 0 28 2 35 E18 18 0 1 17 3 29 0 35 E36 3...

Page 25: ...17 3 114 1 9 10 0 0 0 None 0 0 56 5 70 E18 18 0 1 21 7 56 5 70 E36 36 0 2 43 3 66 6 70 E54 54 0 2 65 0 77 5 90 E72 72 0 2 86 6 99 1 110 575 13 5 80 1 5 8 2 0 0 None 0 0 44 6 50 E18 18 0 1 17 3 44 6 5...

Page 26: ...100 1 1 7 2 5 0 None 0 0 41 1 50 E18 18 0 1 21 7 42 3 50 E36 36 0 2 43 3 69 4 70 E54 54 0 2 65 0 80 2 90 E72 72 0 2 86 6 101 9 110 575 8 3 78 0 9 5 9 4 0 None 0 0 32 2 40 E18 18 0 1 17 3 34 0 40 E36 3...

Page 27: ...7 3 114 1 9 10 0 5 0 None 0 0 61 5 70 E18 18 0 1 21 7 61 5 70 E36 36 0 2 43 3 72 9 80 E54 54 0 2 65 0 83 7 90 E72 72 0 2 86 6 105 4 110 575 13 5 80 1 5 8 2 4 0 None 0 0 48 6 60 E18 18 0 1 17 3 48 6 60...

Page 28: ...1 3 3 4 3 4 NOM CFM TOTAL Each 4 000 4 000 5 000 5 000 CONDENSER COIL ROWS DEEP 2 FINS PER INCH 20 FACE AREA Sq Ft 63 8 COMPRESSOR Qty Per Unit SCROLL 2 FILTERS QUANTITY PER UNIT 12 X 24 X 2 12 TOTAL...

Page 29: ...e unit control box 3Second stage heating is not required on units with a single stage electric heater 4Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers when the therm...

Page 30: ...ESS DOT PLUG For pressure drop reading BLOWER COMPARTMENT ACCESS Auxiliary C GAS SUPPLY ENTRY CONTROL BOX ACCESS VENT AIR OUTLET HOODS BLOWER MOTOR ACCESS Location of Optional VFD Bypass BLOWER ACCESS...

Page 31: ...er exhaust option The covering consists of a heavy black paper composition 3 Replace the side supply and return air compartment panels For side duct applications 1 Replace the side panels on the suppl...

Page 32: ...CLEARANCES LOCATION CLEARANCE Front 36 Rear 24 Less Economizer 49 With Economizer Left Side Filter Access 24 Less Economizer 36 With Economizer 3 Right Side Cond Coil 36 Below Unit1 1 Units may be in...

Page 33: ...261660 YTG D 0708 Johnson Controls Unitary Products 33 FIGURE 7 UNIT CENTER OF GRAVITY FIGURE 8 TYPICAL UNIT APPLICATIONS ROOF JACK INSTALLATION ROOF CURB INSTALLATION SLAB ON GROUND INSTALLATION...

Page 34: ...899 899 481 300 Elec 2846 496 927 927 496 180 Gas 2660 302 316 453 590 565 434 210 Gas 2928 340 340 488 636 636 488 240 Gas 2960 344 344 493 643 643 493 300 Gas 3046 354 354 508 661 661 508 180 Elec 2...

Page 35: ...ll dimension of the ducts allows duct work penetration between roof joists that are spaced on 72 centers Note Ducts can be installed into the curb from the roof All electrical and gas line connections...

Page 36: ...K TERMINALS ON A LIMITED NUMBER OF THERMOSTATS 3 1 2 4 3 1 2 4 Second stage heating not required on single stage heating units Second stage cooling not required on single stage cooling units Jumper is...

Page 37: ...10 5 They shall have built in field convertible duct connections for down discharge supply return or horizontal discharge supply return and be available with factory installed options or field instal...

Page 38: ...resetable circuit breaker on the 24 volt transformer side b Unit shall incorporate a lockout circuit which pro vides reset capability at the space thermostat or base unit should any of the following s...

Page 39: ...vided Simultaneous economizer com pressor operation is also possible Dampers shall fully close on power loss BAS READY ECONOMIZER Outdoor and return air dampers that are interlocked and positioned by...

Page 40: ...e requirements WOOD SKID Allows unit to be handled with 90 forks ECONOMIZER MOTORIZED DAMPER RAIN HOOD DJN E C300 only Contains all hood panels and the hardware for assembling ANTI RECYCLE TIMER Assur...

Reviews: