6
P5415467
under pressure and never open pressurized system parts.
●
Before installation is complete, make sure that the refrigerant leak test has been performed. If
refrigerant gases escape into the air, turn OFF the main switch, extinguish any open flames and
contact your service contractor. Refrigerant (Fluorocarbon) for this unit is odorless. If the refrigerant
should leak and come into contact with open flames, toxic gas could be generated. Also, because the
fluorocarbons are heavier than air, they settle to the floor, which could cause asphyxiation.
●
When installing the unit, and connecting refrigerant piping, keep all piping runs as short as
possible, and make sure to securely connect the refrigerant piping before the compressor starts
operating. If the refrigerant piping is not connected and the compressor activates with the stop
valve opened, the refrigerant cycle will become subjected to extremely high pressure, which can
cause an explosion or fire.
●
Tighten the flare nut with a torque wrench in the specified manner. Do not apply excessive force to the
flare nut when tightening. If you do, the flare nut can crack and refrigerant leakage may occur.
●
When maintaining, relocating, and disposing of the unit, dismantle the refrigerant piping after the
compressor stops.
●
When pipes are removed out from under the piping cover, after the insulation work is completed,
cover the gap between the piping cover and pipes by a packing (field-supplied). If the gap is not
covered, the unit may be damaged if snow, rain water or small animals enter the unit.
●
Do not apply an excessive force to the spindle valve at the end of opening. Otherwise, the spindle
valve flies out due to refrigerant pressure. At the run test, fully open the gas and liquid valves,
otherwise, these devices will be damaged. (It is closed before shipment.)
●
If the arrangement for outdoor units is incorrect, it may cause flowback of the refrigerant and result in
failure of the outdoor unit.
●
The refrigerant system may be damaged if the slope of the piping connection kit e15
o
.
Electrical Precautions
Take the following precautions to reduce the risk of electric shock, fire or
explosion resulting in serious injury or death.
●
Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram
and these instructions when wiring. Improper connections and inadequate grounding can cause
serious injury or death.
●
Perform all electrical work in strict accordance with this installation and maintenance manual and all
the relevant regulatory standards.
●
Before servicing, open and tag all disconnect switches. Never assume electrical power is
disconnected. Check with meter and equipment.
●
Only use electrical protection equipment and tools suited for this installation.
●
Use specified cables between units.
●
The new air conditioner may not function normally in the following instances:
▫
If electrical power for the new air conditioner is supplied from the same transformer as the device*
referred to below.
▫
If the power source cables for this device* and the new air conditioner unit are located in close
proximity to each other.
Device*: (Example): A lift, container crane, rectifier for electric railway, inverter power
device, arc furnace, electric furnace, large-sized induction motor and large-sized switch.
Regarding the cases mentioned above, surge voltage may be inducted into the power supply
cables for the packaged air conditioner due to a rapid change in power consumption of the
device and an activation of a switch.
Check field regulations and standards before performing electrical work in order to protect the
power supply for the new air conditioner unit.