262260-YTG-E-1008

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

SINGLE PACKAGE GAS/ELECTRIC UNITS

AND SINGLE PACKAGE

AIR CONDITIONERS

DH 180, 210, 240 & 300

15, 17.5, 20 & 25 NOMINAL TONS

10.8 EER (15 TONS), 10.2 EER (17.5 TONS), 9.7 EER (20 
TONS) AND 9.6 EER (25 TONS)

®  

TECHNICAL GUIDE

DESCRIPTION

YORK Sunline Ultra™ units are convertible single package 
high efficiency rooftops. All models have independent dual 
refrigerant circuits for efficient part load operation. Although 
the units are primarily designed for curb mounting on a roof, 
they can also be slab-mounted at ground level or set on steel 
beams above a finished roof.

All units include:

Powder Paint finish that meets ASTM-B-117 1000 hour 
salt spray standards

Two-stage cooling provided by dual independent refriger-
ation circuits with expansion valves, filter-driers, high and 
low pressure/loss of charge switches and freezestats

Hermetically sealed scroll compressors with crankcase 
heaters

Two-stage heating provided by dual independent heat 
exchangers with aluminized steel tubes, redundant gas 
valves, spark ignition with induced draft logic

Permanently lubricated motors

Bottom or side air discharge configuration capability 
(field convertible)

Belt drive blower motor with high static drive options

Constant supply air volume (CV) with optional variable 
air volume (VAV)

Manufactured under the quality standards of ISO9001

Twenty-four volt control circuit with compressor lock-out

Zero-25% fixed air damper with hood

Copper tube/aluminum fin coils

Hinged filter access and tool free latched doors optional

Hinged tool free blower, blower motor, filters and electri-
cal panel access optional

Rigging holes in base rails for lifting

Single point power connection

Complete factory package - tested, charged and wired

CSA agency approvals on all units

WARRANTY

Factory Limited Parts Warranty

One-year parts warranty

A Five-year parts warranty on the compressor and

 

electric heat elements.

Ten-year parts warranty on the gas-fired heat

 

exchangers.

Summary of Contents for DH 180

Page 1: ...cally sealed scroll compressors with crankcase heaters Two stage heating provided by dual independent heat exchangers with aluminized steel tubes redundant gas valves spark ignition with induced draft...

Page 2: ...17 5 TON COOLING ONLY 210 MBH BOTTOM DUCT CONNECTIONS 21 11 SUPPLY AIR BLOWER PERFORMANCE 20 TON COOLING ONLY 240 MBH BOTTOM DUCT CONNECTIONS 22 12 SUPPLY AIR BLOWER PERFORMANCE 15 TON GAS HEAT 180 M...

Page 3: ...r all units These four digits will not be assigned until a quote is requested or an order placed CPC Controller DFS APS Johnson Controller UNT 1126 N2 protocol DFS APS Honeywell Controller DFS APS Nov...

Page 4: ...ypass valve is available for low cooling load applications Simplicity Controls Simplicity control boards have standardized a number of features previously available only as options or by utilizing add...

Page 5: ...motor actuator capa ble of introducing up to 100 outdoor air with nominal 1 leakage type dampers The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is c...

Page 6: ...rogrammed from the factory An optional factory installed manual bypass switch available with factory installed VFD can be found in the Blower Motor Access compartment The switch can be used to either...

Page 7: ...anced Rooftop building auto mation system controller is factory installed Includes supply air sensor return air sensor dirty filter indicator switch and air proving switch HONEYWELL BAS CONTROL The Ho...

Page 8: ...natural gas furnace to propane HIGH ALTITUDE PROPANE Burner orifices and pilot orifices are provided for proper furnace operation at alti tudes up to 6 000 feet This accessory supplements the basic p...

Page 9: ...power input in watts expressed in Btuh per watt Btuh watt IPLV3 3 IPLV Integrated part load value COOLING ONLY DH180C00 1784 4 Deduct 2 MBH 208V 10 8 11 3 DH210C00 205 10 2 10 8 DH240C00 223 9 7 10 2...

Page 10: ...7 119 5 82 2 186 8 12 3 186 8 186 8 186 8 149 5 112 2 75 0 57 191 0 10 5 191 0 191 0 191 0 153 8 116 5 79 3 183 7 12 3 183 7 183 7 183 7 146 5 109 2 71 9 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON...

Page 11: ...77 194 0 18 0 138 6 91 2 62 0 72 179 0 17 1 151 3 122 2 93 0 63 8 67 164 0 16 2 164 0 153 2 124 0 94 8 65 7 62 154 0 16 3 154 0 154 0 154 0 124 8 95 7 66 5 57 150 0 16 6 150 0 150 0 150 0 120 8 91 7 6...

Page 12: ...183 0 139 5 96 0 215 3 15 2 215 3 215 3 215 3 171 9 128 4 84 9 57 222 0 13 9 222 0 222 0 222 0 178 5 135 0 91 6 212 7 15 2 212 7 212 7 212 7 169 3 125 8 82 3 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR...

Page 13: ...4 76 4 216 8 23 0 173 6 106 4 72 4 72 211 0 20 7 182 0 148 0 114 0 80 0 198 6 22 5 177 0 143 0 109 0 74 9 67 192 1 20 2 192 1 185 6 151 6 117 6 83 6 180 4 22 0 180 4 179 5 145 5 111 5 77 5 62 179 1 19...

Page 14: ...8 133 1 269 2 12 4 269 2 269 2 269 2 219 6 169 9 120 2 57 278 9 10 6 278 9 278 9 278 9 229 2 179 5 129 8 267 1 12 2 267 1 267 1 267 1 217 4 167 7 118 0 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON CO...

Page 15: ...235 0 22 8 228 5 150 8 100 0 72 224 0 22 4 220 8 181 9 143 0 104 1 67 213 0 22 0 213 0 213 0 186 0 147 1 108 2 62 210 0 21 6 210 0 210 0 209 0 170 1 131 2 92 4 57 208 0 21 4 208 0 208 0 208 0 169 1 1...

Page 16: ...5 6 93 5 291 6 21 8 291 6 291 6 282 0 219 9 157 8 95 7 57 288 7 20 1 288 7 288 7 288 7 226 6 164 5 102 4 286 1 21 8 286 1 286 1 286 1 224 0 161 9 99 8 AIR ON EVAPORATOR COIL TEMPERATURE OF AIR ON COND...

Page 17: ...0 77 310 4 29 4 227 1 134 6 86 0 72 282 2 28 6 240 5 191 9 143 3 94 7 67 254 0 27 8 254 0 249 2 200 6 152 0 103 4 62 249 7 27 2 249 7 249 7 248 4 199 8 151 2 102 6 57 244 9 27 3 244 9 244 9 234 9 186...

Page 18: ...the static pressure and BHP Since no temperature data is given we will assume an air temperature of 70 F Table 8 shows the correction factor to be 0 832 Corrected static pressure 1 5 x 0 832 1 248 IWC...

Page 19: ...262260 YTG E 1008 Johnson Controls Unitary Products 19 FIGURE 2 ALTITUDE TEMPERATURE CONVERSION FACTOR...

Page 20: ...0 0 9 5 2 4 7 0 7 5 7 5 1 208 VOLT AND HIGH STATIC DRIVE 965 6 0 1 2 2 9 2 6 1 0 3 6 3 2 0 8 4 0 3 6 0 5 4 7 4 2 0 4 5 0 4 4 980 5 5 1 3 3 0 2 7 1 1 3 7 3 3 0 9 4 1 3 7 0 6 4 8 4 3 0 5 5 1 4 6 1025 4...

Page 21: ...4 5 9 5 0 980 5 0 1 6 5 3 4 5 1 4 5 8 4 9 1 2 6 3 5 3 0 7 6 9 5 8 1010 4 0 1 8 5 8 4 9 1 7 6 3 5 3 1 5 6 9 5 8 1 0 7 5 6 3 1020 3 5 1 9 6 1 5 1 1 8 6 5 5 5 1 6 7 1 6 0 1 1 7 8 6 6 1035 3 0 2 0 6 2 5...

Page 22: ...9 1 2 6 3 5 3 0 7 6 9 5 8 0 2 7 3 6 1 1010 4 0 1 8 5 8 4 9 1 7 6 3 5 3 1 5 6 9 5 8 1 0 7 5 6 3 0 5 7 9 6 7 1020 3 5 1 9 6 1 5 1 1 8 6 5 5 5 1 6 7 1 6 0 1 1 7 8 6 6 0 6 8 3 7 0 1035 3 0 2 0 6 2 5 2 1 9...

Page 23: ...8 3 4 1 0 4 4 3 9 0 8 5 0 4 5 0 6 5 6 5 0 208 VOLT AND HIGH STATIC DRIVE 965 6 0 1 2 2 7 2 5 0 9 3 2 2 9 0 6 3 7 3 3 0 4 4 4 3 9 0 2 5 0 4 5 980 5 5 1 3 2 9 2 6 1 0 3 4 3 0 0 7 3 8 3 4 0 5 4 5 4 0 0 3...

Page 24: ...5 1 0 2 6 9 5 8 980 5 0 1 9 4 5 3 8 1 5 5 4 4 5 1 0 6 3 5 3 0 4 7 2 6 1 995 4 5 2 1 4 5 3 9 1 6 5 5 4 7 1 1 6 4 5 4 0 5 7 5 6 3 1025 3 5 2 3 4 9 4 1 1 8 5 8 4 9 1 3 6 7 5 7 0 7 8 0 6 7 1050 2 5 2 5 5...

Page 25: ...980 5 0 1 9 4 5 3 8 1 5 5 4 4 5 1 0 6 3 5 3 0 4 7 2 6 1 0 1 8 5 7 1 995 4 5 2 1 4 5 3 9 1 6 5 5 4 7 1 1 6 4 5 4 0 5 7 5 6 3 0 2 8 6 7 3 1025 3 5 2 3 4 9 4 1 1 8 5 8 4 9 1 3 6 7 5 7 0 7 8 0 6 7 1050 2...

Page 26: ...7 11 2 1215 4 0 2 7 8 6 7 0 2 1 10 4 8 5 1 4 12 3 10 1 0 6 14 3 11 7 1255 3 0 3 0 9 1 7 4 2 4 11 0 9 0 1 7 12 9 10 6 0 9 15 0 12 3 1290 2 0 3 2 9 5 7 8 2 7 11 5 9 4 2 0 13 5 11 1 1 2 15 6 12 8 1330 1...

Page 27: ...TION RESISTANCE IWG CFM 15 TON 17 5 TON 20 TON 25 TON 4500 6000 7200 6000 8000 9000 6000 7000 9400 7500 10000 12500 WET COIL 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 ELECTRIC HEAT OPTIONS DH mo...

Page 28: ...5 6 190 4 5 20 0 0 0 None 86 6 110 E18 13 5 1 37 5 86 6 110 E36 27 2 74 9 118 7 125 E54 40 6 2 112 7 165 9 175 E72 54 1 2 150 2 175 2 200 230 3 60 25 6 190 4 3 20 0 0 0 None 86 2 110 E18 18 0 1 43 3 8...

Page 29: ...86 6 102 9 110 575 12 4 80 1 7 10 0 0 0 None 41 3 50 E18 18 0 1 17 3 41 3 50 E36 36 0 2 34 6 55 8 60 E54 54 0 2 52 0 64 5 70 E72 72 0 2 69 3 81 8 90 TABLE 21 DH 300 ELECTRICAL DATA HIGH STATIC MOTOR...

Page 30: ...6 190 4 5 20 0 10 0 None 96 6 110 E18 13 5 1 37 5 96 6 110 E36 27 2 74 9 131 2 150 E54 40 6 2 112 7 178 4 200 E72 54 1 2 150 2 187 7 200 230 3 60 25 6 190 4 3 20 0 10 0 None 96 2 110 E18 18 0 1 43 3...

Page 31: ...86 6 109 1 110 575 12 4 80 1 7 10 0 4 0 None 45 3 50 E18 18 0 1 17 3 45 3 50 E36 36 0 2 34 6 60 8 70 E54 54 0 2 52 0 69 5 70 E72 72 0 2 69 3 86 8 90 TABLE 24 DH 300 ELECTRICAL DATA HIGH STATIC MOTOR...

Page 32: ...e heating is not required on units with a single stage electric heater 4Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers when the thermostat switches to the set back...

Page 33: ...25 X 2 or 4 4 4 4 Quantity Per Unit 18 X 24 X 2 or 4 5 Total Face Area sq ft 15 0 20 0 20 0 20 0 CHARGE Refrigerant 22 lbs oz System 1 23 10 24 0 24 2 21 1 System 2 21 10 24 8 27 2 21 1 TABLE 28 OPERA...

Page 34: ...illustrate Bottom Duct openings Power and Gas Piping Connection locations 12 1 2 9 1 4 8 1 8 9 3 4 3 3 4 B POWER WIRING ENTRY A CONTROL WIRING ENTRY CONDENSER COILS OPTIONAL COIL GUARD KIT COMPRESSOR...

Page 35: ...n The covering consists of a heavy black paper composition 3 Replace the side supply and return air compartment panels For side duct applications 1 Replace the side panels on the supply and return air...

Page 36: ...CLEARANCES LOCATION CLEARANCE Front 36 Rear 24 Less Economizer 49 With Economizer Left Side Filter Access 24 Less Economizer 36 With Economizer 3 Right Side Cond Coil 36 Below Unit1 1 Units may be in...

Page 37: ...262260 YTG E 1008 Johnson Controls Unitary Products 37 FIGURE 7 UNIT CENTER OF GRAVITY 17 5 20 25 Ton FIGURE 8 TYPICAL UNIT APPLICATIONS...

Page 38: ...563 DH240N32 2340 548 596 623 573 DH300C00 2345 461 502 720 662 DH300N24 2545 501 545 781 718 DH300N32 2585 509 553 794 729 TABLE 33 DH 180 210 240 300 6 POINT LOAD WEIGHT DISTRIBUTION UNIT MODEL OPE...

Page 39: ...ducts allows ductwork penetration between roof joists that are spaced on 72 centers NOTE Ducts can be installed into the curb from the roof All electrical and gas line connections can be made inside t...

Page 40: ...S CONTROL TERMINAL BLOCK TERMINALS ON A LIMITED NUMBER OF THERMOSTATS 3 1 2 4 3 1 2 4 Second stage heating not required on single stage heating units Second stage cooling not required on single stage...

Page 41: ...ct connections for down discharge supply return or horizontal discharge supply return and be available with factory installed options or field installed accessories The units shall be factory wired pi...

Page 42: ...on thermostat evaporator coil If any of the above safety devices trip a LED light emitting diode indicator shall flash a diagnostic code that indicates which safety switch has tripped d Unit shall inc...

Page 43: ...oor return air streams are available to provide free cooling based on single enthalpy or dual enthalpy configura tions respectively If free cooling is available a call for cooling shall modulate the e...

Page 44: ...COIL GUARD KIT Guard for cooling coil OTHER FACTORY INSTALLED OPTIONS POWER EXHAUST OPTION To work in conjunction with economizers STAINLESS STEEL HEAT EXCHANGER STAINLESS STEEL DRAIN PAN TECHNICOAT P...