5

AIR FILTERS

All units contain four (4) 20” x 25” x 2" filters. The filter
racks on these units will receive either 1" or 2" filters.
Filters can also be installed in the building at a suitable
return air location if an economizer or outside air
accessory is not used. Filters must always be used.
They should be inspected once a month and thor-
oughly cleaned or replaced if it appears they are begin-
ning to accumulate excessive dirt. 

To install the filters, remove the filter access panel as
shown in Figure 4.

NOTE:  

Filters must be installed with “Air Flow” arrows

pointing inward -- toward the indoor coil. In the
event the spacers in the filter section are
removed, they must be reinstalled in their origi-
nal position.

Slide filters all the way into the filter racks provided.
When more than one filter in a filter rack is required,
they must butt each other when sliding into position.
Replace the filter access panel. 

 

   

BLOWER ASSEMBLY

Even with good filters properly in place, blower wheels
and motors will become dust laden after many months
of operation. The entire blower assembly should be
inspected annually. If the motor and wheel are heavily
coated with dust, they can be brushed and cleaned
with a vacuum cleaner.

These units are supplied with blower shaft bearings
that do not require maintenance but may be lubricated 

if desired. Every three years, using a low pressure
grease gun, pump grease into the bearing grease fit-
ting until grease just begins to show at the seals. Do
not over lubricate. Use any lithium base grease recom-
mended for ball bearing service.

FIGURE 4-

FILTER ACCESS

I N D O O R   C O I L

F I L T E R S

F I L T E R   A C C E S S

P U L L S

Summary of Contents for DF078 Series

Page 1: ...HNICIAN 6 REPLACEMENT PARTS 7 The manufacturer recommends that the User read all sections of this manual and keep the manual for future reference FIRE OR EXPLOSION HAZARD Failure to follow safety warn...

Page 2: ...ent is well supported and there are no signs of deterioration The manufacturer recommends that main burner ignition device and controls are inspected by a qualified service techni cian before each hea...

Page 3: ...erate properly The gas supply to the furnace should be shut off and no attempt should be made to place the furnace in operation The system should be inspected by a qualified service technician Refer t...

Page 4: ...Check that the unit s physi cal support concrete slab or roof curb is sound and not in need of repair Make sure there are no gaps between the roof curb and the unit where rain could leak into the bui...

Page 5: ...osition Slide filters all the way into the filter racks provided When more than one filter in a filter rack is required they must butt each other when sliding into position Replace the filter access p...

Page 6: ...coil should be done Cleaning should be as often as necessary to keep the coil clean Clean any debris and dirt from the outside coil face with a brush being careful not to damage the fins If extremely...

Page 7: ...____________________________________ The owner should keep this information in a place where it can be found if needed for warranty purposes SINGLE PACKAGE AIR CONDITIONER GAS ELECTRIC 6 5 TON REPLACE...

Page 8: ...o change without notice Printed in U S A 035 19047 002 A 1103 Copyright by Unitary Products Group 2003 All rights reserved Supersedes 035 19047 001 B 1102 Unitary 5005 Norman Products York OK Group Dr...

Reviews: