background image

035-19047-002-A-1103

4

Unitary Products Group

EXPLAIN UNIT FUNCTION

When the system is functioning properly, show the
owner the location of all disconnect switches and the
thermostat. Explain how to start and stop the unit and
how to adjust temperature settings within the limitations
of the system. Advise that the flue exhaust hood sur-
face and the immediate area will experience high tem-
peratures during the heating cycle, and that all
unauthorized personnel and debris must be kept away
from this area.

GENERAL MAINTENANCE

In order to insure long and trouble free service from
your system, we recommend periodic inspection,
cleaning, lubrication and adjustment by your installing
Dealer/Contractor. Be sure to ask about this service.
For those who prefer to do-it-yourself, please follow the
instructions listed below to care for your system.

Snow or debris should not be allowed to accumulate in
or around the unit. Do not permit overhanging struc-
tures or shrubs to obstruct outdoor air discharge, com-
bustion air inlets or vent outlets on your unit. These
provide air for combustion and ventilation. Adequate air
is important to the safe and proper operation of the
unit.

HEATING SYSTEM INSPECTION

It is the owner's responsibility to insure that an annual
inspection of the entire heating portion of the unit is
made by a qualified service technician. This should
include inspection of the burner, heating element and
flue for any corrosion or soot accumulation which may
require cleaning and also checking  of burner and con-
trols for proper operation.

In addition, at least once during the heating season,
the owner shall make a visual inspection of the flue out-
let for evidence of black soot or blockage of flue outlet
by leaves or other debris. If any soot is found, it is rec-
ommended a qualified service technician be called
immediately. If any blockage is found, it must be
cleared immediately.

Check for obvious signs of deterioration of the unit.
Check that the return and supply ducts attached to the
unit are sound and air tight. Check that the unit's physi-
cal support, concrete slab or roof curb, is sound and
not in need of repair. Make sure there are no gaps
between the roof curb and the unit where rain could
leak into the building.

Start the furnace. The vent motor should start, the
igniter will start to spark and ignite the burner. If it does
not, contact a qualified service technician for assis-
tance. Check the appearance of the main burner flame.
The flame should have a blue appearance.  (See Fig-
ure 3.)  

BURNER CHECK

Periodically (at least annually at the beginning of each
heating season) make a visual check of the main
burner flame to determine if the burners need cleaning. 

CLEANING BURNERS

Remove them from the furnace as explained the in
BURNER/ORIFICE INSTRUCTIONS section in the
Unit Installation Instructions. Clean burners with wire
brush and  vacuum as needed.

CLEANING FLUE PASSAGES & HEATING ELEMENTS

With proper combustion adjustment, the heat
exchanger tubes of a gas-fired furnace will seldom
need cleaning.  If the tubes should become sooted,
they can be cleaned as follows:

1.

Remove the burner assembly as outlined in 
“BURNER/ORIFICES INSTRUCTIONS” of the unit 
Installation Instructions.

2.

Remove the screws holding the flue collector box.  
Carefully remove the flue collector box.

3.

Remove the flue baffles from the tube interiors.

4.

Using a wire brush on a flexible wand, brush out 
the inside of each heat exchanger from the burner 
inlet and flue outlet ends.

5.

Brush out the inside of the flue collector box and 
the flue baffles.

6.

Run the wire brush into the flue exhaust tube from 
the flue collector end.  Do not damage the flue 
exhaust screen, remove if necessary.

7.

If soot build-up is particularly bad, remove the draft 
motor and clean the wheel and housing.

8.

After brushing is complete, blow away all brushed 
areas with air or nitrogen.  Vacuum as needed.

9.

Replace parts in the reverse order that they were 
removed in Steps 1 through 3.

10. Assure that all seams on the vent side of the com-

bustion system are airtight.  Apply a high tempera-
ture (500°F+) sealing compound where needed.

FIGURE 3-

TYPICAL FLAME

H E A T   E X C H A N G E R   T U B E

G A S

S U P P L Y

P I P E

B U R N E R

B U R N E R   B R A C K E T

I G N I T O R

B U R N E R   F L A M E

( B L U E   O N L Y )

Summary of Contents for DF078 Series

Page 1: ...HNICIAN 6 REPLACEMENT PARTS 7 The manufacturer recommends that the User read all sections of this manual and keep the manual for future reference FIRE OR EXPLOSION HAZARD Failure to follow safety warn...

Page 2: ...ent is well supported and there are no signs of deterioration The manufacturer recommends that main burner ignition device and controls are inspected by a qualified service techni cian before each hea...

Page 3: ...erate properly The gas supply to the furnace should be shut off and no attempt should be made to place the furnace in operation The system should be inspected by a qualified service technician Refer t...

Page 4: ...Check that the unit s physi cal support concrete slab or roof curb is sound and not in need of repair Make sure there are no gaps between the roof curb and the unit where rain could leak into the bui...

Page 5: ...osition Slide filters all the way into the filter racks provided When more than one filter in a filter rack is required they must butt each other when sliding into position Replace the filter access p...

Page 6: ...coil should be done Cleaning should be as often as necessary to keep the coil clean Clean any debris and dirt from the outside coil face with a brush being careful not to damage the fins If extremely...

Page 7: ...____________________________________ The owner should keep this information in a place where it can be found if needed for warranty purposes SINGLE PACKAGE AIR CONDITIONER GAS ELECTRIC 6 5 TON REPLACE...

Page 8: ...o change without notice Printed in U S A 035 19047 002 A 1103 Copyright by Unitary Products Group 2003 All rights reserved Supersedes 035 19047 001 B 1102 Unitary 5005 Norman Products York OK Group Dr...

Reviews: