15
- Fig. 7 -
5.3.- Indoor coil condensed water drain
- The condensed water drain line
must
have a siphon for
correct discharge (see Fig. 7).
- The diameter of the tubing used must be at least equal to
the connection provided on the side of the unit.
- Use sealing putty on male threads.
- If it is necessary to install a drain line from the connection
of the unit to a nearby drain, maintain a minimum 2 cm.
pitch per each meter in length.
- It is recommended that the siphon be equipped with a plug
at the bottom for draining and cleaning.
- Prior to unit start-up, the siphon should be primed (filled
with water) and then checked during maintenance opera-
tions.
6 - Electrical characteristics and connections
6.1.- Basic units D4IC/D4IG/B4IH
6.2.- Units with backup heaters
- D4IC/B4IH
Heater power supply should be independent of general unit power supply and have its own automatic switch, as per the
following table:
6.3.- Power and control wiring
Job site wiring and grounding of the unit should be car-
ried out in compliance with national, local and city regula-
tions.
The voltage tolerances to be maintained at the compres-
sor terminals during start-up and operation appear on
the Identification Plate and in the Table of sections 6.1
and 7.
The inner wiring hose supplied with the unit is an integral
part of same. No variation at job site should be necessary
for compliance with electrical regulations.
An automatic and differential switch should be installed on
job site for the unit. This switch should be independent of
all other circuits. Should any of the cables supplied with
the unit need replacement, the replacement cable should
be of the type shown on the wiring diagram. See Wiring
Specifications Table.
The power supply line should be adequately sized for the
load.
Use copper wires only
. Each one of the units should
be connected to an independent circuit with an automatic
and differential switch, supplied directly from the main
panel.
Model
Power
supply
Compressor
Outdoor fan
motor
Indoor fan
motor
Total
nominal
Total
nominal
intensity
(unit)
amps
Total
maximum
intensity
(unit)
amps
Automatic
switch
(K curve)
amps
Min.
cable
section
mm²
Operating
intensity
each
Start
intensity
each
kW
each
Nominal
amps
each
kW
Nominal
amps
kW
DIC/BIH
360
400..50
21 (x)
167
1.5 (x)
2.8
9.2
16
42.4/4
87
108
125
50
480
400..50
21 (x2) +
8
167/272
1.5 (x4)
2.8
11
21
52.2/59.5
106
19
160
70
Important:
Automatic switch sizing and power supply and control cable sections are orientative and should be corrected in accordance with job site
conditions, length between units and legislation in force.
Notes:
1.- K curve (DIN, VDE 0660-104) 2.- Based on copper conductors
Model
Power
supply
V. Ph. Hz.
Electric heater
Maximum automatic
switch
(K curve)
1
Minimum
cable
section
(mm²)
Capacity
(kW)
Stages
Intensity
(A)
360/480
400..50
7
2
54
6
16
50
2
75
80
25
60
2
87
100
5
Notes:
1.- K curve (DIN, VDE 0660-104) 2.- Based on copper conductors, 105° C.
������
���������������
�
�
�
�
�������
��������
�����
����
132
75
min
50
Summary of Contents for D4IC-360
Page 2: ......
Page 43: ...43 20 Wiring diagrams 20 1 Cool only models D4IC 360 D4IC 360G50 400 3 50 1 of 3 ...
Page 44: ...44 D4IC 360G50 400 3 50 2 of 3 ...
Page 45: ...45 D4IC 360G50 400 3 50 3 of 3 ...
Page 46: ...46 20 2 Cool only models D4IC 480 D4IC 480G50 400 3 50 1 of 3 ...
Page 47: ...47 D4IC 480G50 400 3 50 2 of 3 ...
Page 48: ...48 D4IC 480G50 400 3 50 3 of 3 ...
Page 49: ...49 20 3 Heat pump models B4IH 360 400 3 50 1 of 3 ...
Page 50: ...50 B4IH 360 400 3 50 2 of 3 ...
Page 51: ...51 B4IH 360 400 3 50 3 of 3 ...
Page 52: ...52 20 4 Heat pump models B4IH 480 400 3 50 1 of 3 ...
Page 53: ...53 B4IH 480 400 3 50 2 of 3 ...
Page 54: ...54 B4IH 480 400 3 50 3 of 3 ...
Page 55: ...55 20 5 Cool only gas heating models D4IG 360 400 3 50 1 of 4 ...
Page 56: ...56 D4IG 360 400 3 50 2 of 4 ...
Page 57: ...57 D4IG 360 400 3 50 3 of 4 ...
Page 58: ...58 D4IG 360 400 3 50 4 of 4 ...
Page 59: ...59 20 5 Cool only gas heating models D4IG 480 400 3 50 1 of 4 ...
Page 60: ...60 D4IG 480 400 3 50 2 of 4 ...
Page 61: ...61 D4IG 480 400 3 50 3 of 4 ...
Page 62: ...62 D4IG 480 400 3 50 4 of 4 ...
Page 63: ...63 Configuration of switches Data and dimensions are subject to change without prior notice ...
Page 64: ...www johnsoncontrols com ...