13. Ensure that all seams on the vent side of the combustion

system are air tight. Apply a high temperature (+500

°

F)

sealing compound where needed.

WARNING: Troubleshooting of components necessarily re-

quires  opening the electrical control box with the
power connected to the unit.  Use extreme care
when working with live circuits! Check the unit
nameplate for the correct line voltage and set the
volt meter to the correct range before making any
connections with line terminals.

WARNING: Prior to any of the following maintenance proce-

dures, shut off all electric power to the unit to
prevent personal injury.

CAUTION: Label all wires prior to disconnection when servic-

ing controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after
servicing.

NOTE To find the Btu input, multiply the number of cubic feet of

gas consumed per hour by the Btu content of the gas in
your particular locality (contact your gas company for this
information - it varies widely from city to city.)

1. The indoor blower motor is a non-inherently protected

three-phase motor. Protection is provided by an overload
relay for overcurrent and fuses for short circuit. If the motor
fails to run, check the line voltage circuit and control voltage
circuit per the following procedure:

a. If the Indoor Blower Motor does not operate, check

visually that contactor M3 is pulled in. If so, check for
line voltage between all three phases at the line termi-
nals of the Blower Overload Relay (BOR). If line voltage
is found, check the leads to the blower motor for open
circuit. If line voltage is found at the motor leads (inside
the conduit box on the motor shell), disconnect the
motor and check for open windings per the motor wiring
diagram. If open windings are found, replace the motor.
If line voltage is not found at the BOR, trace the leads
back to the field supply terminal block, checking for an
open circuit or blown fuses.

b. If the contactor M3 is not pulled in, check for control

voltage (24V) at the M3 coil. If voltage is found, replace
the contactor. If control voltage is not found at M3, check
for voltage across terminals 95 & 96 of the BOR. If
voltage exists, the BOR is open on overload. The BOR
should be set to the auto reset position. The BOR must
cool down in order to reset. If the BOR will not reset,
replace the BOR. If the BOR resets and M3 pulls in, but
the indoor blower motor will still not run, refer to para.
(a) for troubleshooting the line voltage supply circuit. If
control voltage is not found at the BOR, trace the circuit
back to the relay board and thermostat per the unit
wiring diagram. Replace any defective components.

2. Draft motor operates and furnace lights but supply air

blower does not start after a short time delay with room
thermostat fan switch set to “AUTO”.

a. Set fan switch to “ON”. If blower motor runs, go to Step f.

If it does not, check to see if line voltage is being
supplied to the contacts of the contactor (M3), and if the
contactor is pulled in. Check for loose wiring.

b. If contactor (M3) is pulled in, proceed with the trou-

bleshooting steps indicated in Step 1 above.

c. If (M3) is pulled in and the blower motor still does not

run, replace the blower motor.

d. If (M3) is not pulled in, check for 24 volts at the (M3) coil.

If 24 volts is present, replace the (M3) contactor.

e. If 24 volts is not present at the (M3) coil, check for loose

24 volt wiring back to the relay board. Check control
wiring to the room thermostat. If all is fine, replace the
relay board.

f. If the blower motor runs with the fan switch in the “ON”

position but does not run soon after the furnace has
ignited with the fan switch in the “AUTO” position, check
for loose 24 volt wiring between the relay board in the
main control box, the Mate-N-Lok connector in the
partition between the evaporator and gas heat sections
and the time delay relay (ETD).

g. If all control wiring is fine, check for 24 volts at the relay

board. If 24 volts is present, replace the relay board. If
24 volts is not present, replace the (ETD) relay.

NOTE: The furnace may shut itself down on a high tempera-

ture condition during the procedure, but this will not
effect the test if it is done within 5 minutes of furnace
shut-down.

3. The supply air blower operates but the draft motor does not

when the room thermostat is set to call for heat and the fan
switch in the “ON” position.

a. The draft motor has inherent protection. If the motor shell

is hot to the touch, wait for the internal overload to reset.

b. If the motor shell is cold with the room thermostat calling

for heat, check for line voltage at the motor’s Mate-N-
Lok connector attached to the evaporator partition. If
line voltage is present, replace the draft motor.

c. If line voltage is not present, check for line voltage at the

heat relay (RW1) contacts in the main control box and
check to see if the (RW1) is pulled in.

d. If the (RW1) relay is pulled in, check for a loose line

voltage connection.

e. If the (RW1) relay is not pulled in, check for 24 volts at

the (RW1) coil. If 24 volts is present, replace the (RW1)
relay. If 24 volts is not present, check for a loose 24 volt
connection back to the relay board and check the con-
nections from the room thermostat to the relay board. If
all connections are correct, replace the relay board.

4. The draft motor runs but the furnace does not light and the

sparker does not spark.

a. The ignition control (IC1, IC2) may be locked out due to

either a flame roll out or 100% shut off. These safety
features are described above. If lock-out has occurred,
24V must be removed from the ignition controls. This is
done at the unit or by resetting the room thermostat.
After resetting 24V, check for proper furnace operation.

TROUBLESHOOTING

Cont’d.

530.18-N6Y

22

Unitary Products Group

Summary of Contents for D2CG180 & 240 (STY. B)

Page 1: ...rsion Accessory USA 530 18 N6 2V High Altitude Accessory Nat Gas 530 18 N6 3V High Altitude Accessory Propane 530 18 N13Y Coil Guard Installation Renewal Parts Refer to the Renewal Parts Manual for co...

Page 2: ...7 Four And Six Point Loads 12 8 Supply Air Blower Perf 15 Ton 13 9 Supply Air Blower Perf 20 Ton 14 10 Static Resistances 15 11 Power Exhaust Performance 15 12 Blower Motor and Drive Data 15 13 Limit...

Page 3: ...ame other than a YORK roof curb gasketing must be applied to all surfaces that come in contact with the unit underside 5 Maintain level tolerance to 1 2 inch maximum across the entire length or width...

Page 4: ...ductwork to accommodate the damper Using the holes in the hood flanges as a template drill 9 64 inch dia 26 drill holes into the ductwork and secure with the screws provided CAUTION If outdoor air in...

Page 5: ...ing to the unit waterproof type connectors MUST BE USED so that water or moisture cannot be drawn into the unit during normal operation The above waterproofing conditions will also apply when installi...

Page 6: ...or John Crane may be used 4 All piping should be cleaned of dirt and scale by hammering on the outside of the pipe and blowing out the loose dirt and scale Before initial start up be sure that all of...

Page 7: ...securing in place OPTIONAL ECONOMIZER MOTORIZED DAMPER RAIN HOOD The instruction for the optional economizer motorized damper rain hood can be found in form 44 320 2 Use these instructions when field...

Page 8: ...FIG 9 ENTHALPY SETPOINT ADJUSTMENT 530 18 N6Y 8 Unitary Products Group...

Page 9: ...6 0 43 3 COMPRESSOR Qty Per Unit 10 TON TANDEM 1 2 5 TON HERMETIC 1 AIR FILTERS QUANTITY PER UNIT 16 X 20 X 2 4 QUANTITY PER UNIT 16 X 25 X 2 4 QUANTITY PER UNIT 18 X 24 X 2 5 TOTAL FACE AREA sq ft 15...

Page 10: ...84 9 100 460 3 60 19 2 124 9 6 62 1 2 1 5 7 2 42 4 50 575 3 60 15 4 100 7 7 50 1 2 0 5 5 9 33 9 40 DCG240 208 230 3 60 38 4 248 38 4 248 1 4 1 4 2 7 5 21 0 19 4 115 1 111 6 125 460 3 60 19 2 124 19 2...

Page 11: ...ic meters gas meters regulators and relief equip R E T U R N A I R S U P P L Y A I R B O T T O M S U P P L Y A N D R E T U R N A I R O P E N I N G S S e e N o t e B P O W E R W I R I N G E N T R Y A C...

Page 12: ...NOTE These weights are with economizer and the largest blower motor available UNIT 6 POINT LOADS LBS TOTAL A B C D E F 180 2300 351 367 392 416 399 375 240 2500 334 350 426 502 481 407 NOTE These weig...

Page 13: ...7 3 0 2 7 0 4 3 5 3 1 915 5 0 1 1 2 6 2 4 0 8 3 1 2 8 0 5 3 6 3 2 0 2 4 1 3 7 965 4 0 1 2 2 7 2 5 0 9 3 2 2 9 0 6 3 7 3 3 0 4 4 4 3 9 0 2 5 0 4 5 980 3 5 1 3 2 9 2 6 1 0 3 4 3 0 0 7 3 8 3 4 0 5 4 5 4...

Page 14: ...4 1 1 5 0 4 2 0 6 5 9 5 0 0 1 6 7 5 7 950 3 5 1 7 4 2 3 6 1 3 5 1 4 3 0 8 6 0 5 1 0 2 6 9 5 8 965 2 5 1 9 4 5 3 8 1 5 5 4 4 5 1 0 6 3 5 3 0 4 7 2 6 1 0 1 8 5 7 1 995 2 0 2 1 4 6 3 9 1 6 5 5 4 7 1 1 6...

Page 15: ...65 1190 BK80 7 75 7 4 1 BX68 69 8 1 20 TON Stan dard 870 1025 7 5 213T 89 1VP68 6 75 5 5 6 52 1 3 8 BK120 11 75 11 4 1 3 16 BX83 84 8 1 High Speed Access 950 1120 BK110 10 75 10 4 1 3 16 BX81 81 8 1 1...

Page 16: ...rating efficiency ECONOMIZER SINGLE OR DUAL WITH POWER EXHAUST This system operates as specified above with one addition The power exhaust motor is energized whenever the economizer is chosen by the e...

Page 17: ...here are two separate gas valves in the furnace Each valve contains a main and a redundant valve The redundant valves are located upstream of the main gas valves Should either or both of the main gas...

Page 18: ...units If gas pressure is outside these limits contact the local gas utility for corrective action MANIFOLD GAS PRESSURE ADJUSTMENT Small adjustments to the high fire gas flow may be made by turning th...

Page 19: ...within the limitations shown in the Applications Data Table 2 Pulleys can be adjusted in half turn increments 3 The tension on the belt should be adjusted as shown in the Belt Adjustment figure Start...

Page 20: ...2 With the furnace turned on measure the time needed for one revolution of the hand on the smallest dial on the meter A typical gas meter usually has a 1 2 or a 1 cubic foot test dial 3 Using the numb...

Page 21: ...E Exercise care when cleaning the coil so that the coil fins are not damaged Do not permit the hot condenser air discharge to be obstructed by overhanging structures of shrubs BURNER PILOT Periodicall...

Page 22: ...tat fan switch set to AUTO a Set fan switch to ON If blower motor runs go to Step f If it does not check to see if line voltage is being supplied to the contacts of the contactor M3 and if the contact...

Page 23: ...T CHECKOUT b Check all wiring between the ignitor control and the gas valve Check to make sure the ground connections are intact c If the wiring is intact check for 24 volts across terminals PV and CO...

Page 24: ...and information from OUR current parts list for this unit are available to your servicing contractor through our local distributor The name and address of our nearest distributor may be obtained by co...

Reviews: