Unitary Products Group

Coils:

a.

Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless 
internally enhanced copper tubes with all joints 
brazed. Special Phenolic coating shall be available 
as a factory option.

b.

Evaporator and Condenser coils shall be of the 
direct expansion, draw-thru, design.  

Refrigerant Circuit and Refrigerant Safety Components shall 
include:

a.

Thermal expansion devices (TXV’s).

b.

Filter drier/strainer to eliminate any moisture or for-
eign matter.

c.

Accessible service gage connections on both suc-
tion and liquid lines to charge, evacuate, and mea-
sure refrigerant pressure during any necessary 
servicing or troubleshooting, without losing charge.

d.

The refrigeration system shall provide at least 15°F 
of sub-cooling at design conditions.

UNIT CONTROLS

a.

Unit shall be complete with self-contained low-volt-
age control circuit protected by a resetable circuit 
breaker on the 24-volt transformer side.

b.

Unit shall incorporate a lockout circuit which pro-
vides reset capability at the space thermostat or 
base unit, should any of the following standard 
safety devices trip and shut off compressor.

c.

Loss-of-charge/Low-pressure switch.

d.

High-pressure switch.

e.

Freeze-protection thermostat, evaporator coil. 

f.

If any of the above safety devices trip, a LED (light-
emitting diode) indicator shall flash a diagnostic 
code that indicates which safety switch has tripped.

g.

Unit shall incorporate “AUTO RESET” compressor 
over temperature, over current protection.

h.

Unit shall operate with conventional thermostat 
designs and have a low voltage terminal strip for 
easy hook-up.

i.

Unit control board shall have on-board diagnostics 
and fault code display.

j.

Standard controls shall include anti-short cycle and 
low voltage protection, and permit cooling operation 
down to 0°F.

k.

Control board shall monitor each refrigerant safety 
switch independently.

l.

Control board shall retain last 5 fault codes in non 
volatile memory which will not be lost in the event of 
a power loss.

GAS HEATING SECTION

Shall be designed with induced draft combustion with post 
purge logic, energy saving direct spark ignition, and redun-
dant main gas valve. Venter wheel shall be constructed of 
stainless steel for corrosion resistance. The heat exchanger 
shall be of the tubular type, constructed of T1-40 aluminized 
steel for corrosion resistance and allowing minimum mixed 
air entering temperature of 25°F. Burners shall be of the 
inshot type, constructed of aluminum coated steel and con-
tain air mixture adjustments. All gas piping shall enter the unit 
cabinet at a single location through either the side or curb 
without any field modifications. An integrated control board 
shall provide timed control of evaporator fan functioning and 
burner ignition. Heating section shall be provided with the fol-
lowing minimum protection:

a.

Primary and auxiliary high-temperature limit 
switches.

b.

Induced draft motor speed sensor.

c.

Flame roll out switch (manual reset).

d.

Flame proving controls. 

ELECTRIC HEATING SECTION

An electric heating section, with nickel chromium elements, 
shall be provided in a range of 5 thru 30 KW, offering two 
stages of capacity - 16 KW and above on 208/230 volt heaters 
and 20 KW and above on 460 and 575 volt heaters. The heat-
ing section shall have a primary limit control(s) and automatic 
reset to prevent the heating element system from operating at 
an excessive temperature. The heating section assembly 
shall slide out of the unit for easy maintenance and service. 
Units with Electric Heating shall be wired for a single point 
power supply with branch circuit fusing (where required).

UNIT OPERATING CHARACTERISTICS

a.

Unit shall be capable of starting and running at 125°F 
outdoor temperature, exceeding maximum load crite-
ria of ARI Standard 210/240. The compressor, with 
standard controls, shall be capable of operation 
down to 0°F outdoor temperature. Unit shall be pro-
vided with fan time delay to prevent cold air delivery 
before heat exchanger warms up (Gas heat only).

ELECTRICAL REQUIREMENTS

All unit power wiring shall enter unit cabinet at a single factory 
provided location and be capable of side or bottom entry, to 
minimize roof penetrations and avoid unit field modifications. 
Separate side and bottom openings shall be provided for the 
control wiring.

STANDARD LIMITED WARRANTIES

Compressor 5 Years

Heat Exchanger 10 Years

Electric Heat Element 5 Years

Other Parts 1 Year

Summary of Contents for CSA DH 036

Page 1: ...l units include Powder Paint finish that meets ASTM B 117 750 hour salt spray standards Permanently lubricated motors Bottom or side air discharge configuration capability field convertible Manufactur...

Page 2: ...ITY RATINGS ARI 210 240 15 3 GAS HEAT RATINGS 15 4 DH036 COOLING CAPACITIES 3 TON 16 5 DH048 COOLING CAPACITIES 4 TON 17 6 DH060 COOLING CAPACITIES 5 TON 18 7 SUPPLY AIR BLOWER PERFORMANCE 3 TON BELT...

Page 3: ...Options See Next Page Product Generation 1 First Generation 2 Second Generation Voltage 1 208 230 1 60 2 208 230 3 60 4 460 3 60 5 575 3 60 Airflow D H N04 A 2 N AA 1 048 Nominal Cooling Capacity MBH...

Page 4: ...ase Monitor CQ CPC Controller DFS APS Technicoat Evap Cond Coils Coil Guard CR CPC Controller DFS APS Technicoat Evap Cond Coils Phase Monitor Coil Guard CS CPC Controller DFS APS SS Drain Pan CT CPC...

Page 5: ...Controller DFS APS SS Drain Pan Phase Monitor Coil Guard HU Honeywell Excel 10 Controller DFS APS SS Drain Pan Technicoat Cond Coils HV Honeywell Excel 10 Controller DFS APS SS Drain Pan Technicoat Ev...

Page 6: ...Intelli Comfort Controller LB Simplicity Intelli Comfort Controller Phase Monitor LC Simplicity Intelli Comfort Controller Coil Guard LD Simplicity Intelli Comfort Controller Phase Monitor Coil Guard...

Page 7: ...S Drain Pan Dirty Filter Switch Hinged Filter Door Toolless Access Panels BN SS Drain Pan Phase Monitor Coil Guard Dirty Filter Switch Hinged Filter Door Toolless Access Panels BS Bottom Drain Connect...

Page 8: ...FS APS SS Drain Pan Phase Monitor Coil Guard Technicoat Evap and Cond Coils Hinged Filter Door Toolless Access Panels GA Honeywell Excel 10 Controller with Dirty Filter Switch Air Proving Switch Hinge...

Page 9: ...Access Panels UG Technicoat Condenser Coil Coil Guard Dirty Filter Switch Hinged Filter Door Toolless Access Panels UH Technicoat Condenser Coil Phase Monitor Coil Guard Dirty Filter Switch Hinged Fil...

Page 10: ...cess Panels XA Intelli Comfort w Mod Link Controller Hinged Filter Door Toolless Access Panels XB Intelli Comfort w Mod Link Controller Phase Monitor Hinged Filter Door Toolless Access Panels XC Intel...

Page 11: ...uration of cooling and heat Safety Monitoring The control board monitors the high and low pressure switches the freezestats the gas valve if applicable and the temperature limit switch on gas heat uni...

Page 12: ...EATERS Wired for single point power supply These nickel chromium heater elements are pro vided with limit and automatic reset capability to prevent operation at excessive temperatures FILTER OPTIONS S...

Page 13: ...ctors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment COIL GUARD Customers can purchase a coil guard kit to protect the condenser...

Page 14: ...pressurized during econo mizer operation The power exhaust option can only be used on bot tom duct configurations BAROMETRIC RELIEF DAMPER This damper acces sory can be used to relieve internal buildi...

Page 15: ...way of knowing the details of each system This constitutes and expectation to any specification or guaran tee requiring a dBA value or sound data in any other form than sound power level ratings 2 At...

Page 16: ...19 5 34 9 3 73 34 9 34 9 34 9 30 5 26 0 21 5 17 0 72 46 5 3 62 29 7 25 8 21 8 17 8 13 8 42 9 3 83 28 0 24 0 20 0 16 0 12 0 67 41 6 3 53 36 0 32 0 28 0 24 0 20 1 16 1 12 1 38 6 3 74 34 8 30 8 26 8 22...

Page 17: ...9 34 29 24 19 62 39 3 6 39 39 40 35 30 25 20 35 3 9 35 35 37 32 27 22 57 38 3 6 38 38 38 33 28 23 18 34 3 8 34 34 34 29 24 19 72 49 3 8 35 31 26 21 17 45 4 1 33 29 24 20 15 67 44 3 7 43 39 34 30 25 20...

Page 18: ...5 1 53 50 44 38 32 26 20 62 55 4 7 55 55 54 48 42 36 30 49 5 0 49 49 49 43 37 31 25 57 54 4 7 54 54 53 47 41 35 29 49 5 0 49 49 49 43 37 31 25 72 65 4 9 44 39 33 28 23 60 5 2 42 36 31 26 20 67 57 4 8...

Page 19: ...0 916 730 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 1050 1100...

Page 20: ...RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 1050 1100 1085 1500...

Page 21: ...1071 1030 1103 1100 1134 1140 1164 1175 1197 1205 1600 1020 900 1056 965 1088 1035 1118 1065 1145 1105 1170 1130 1198 1150 1500 1004 860 1038 880 1070 925 1101 980 1130 1045 1158 1075 1184 1110 0 60 0...

Page 22: ...ERFORMANCE Tables 3 The pressure through the economizer is greater for 100 outdoor air than for 100 return air If the resistance of the return air duct system is less than 0 25 IWG the unit will deliv...

Page 23: ...121 121 0RGHO 7RQQDJH 9ROWDJH 5 DFK 5 DFK ORZHU 0RWRU RPSUHVVRUV 2 DQ 0RWRU RQY 2XWOHW PSV 0LQLPXP LUFXLW PSDFLW PSV 0D XVH 5 5 6L H PSV OHFWULF HDWHU 0RGHO 1R HDWHU N HDWHU PSV 5 7 SH SHU 1 7KHVH HOH...

Page 24: ...1 121 121 ODEL 4ONNAGE 6OLTAGE INIMUM IRCUIT MPACITY MPS AX USE 2 2 3IZE MPS 2 ACH 2 ACH LOWER OTOR ONV UTLET MPS LECTRIC EATER ODEL O EATER K7 OMPRESSORS EATER MPS AN OTOR 5 7 SH SHU 1 7KHVH HOHFWULF...

Page 25: ...Rows Deep 2 2 2 Fins Per Inch 18 18 18 Face Area Sq Ft 17 1 17 1 17 1 COMPRESSOR Qty Per Unit Recip Type 1 1 1 AIR FILTERS Quantity Per Unit 15 X 20 X 1 or 2 2 2 2 Quantity Per Unit 14 X 25 X 1 or 2...

Page 26: ...Y2 W1 W2 G LED 1 LED 2 COM A1 A2 T T B R Y1 Y2 G C X OCC W2 W1 THERMOSTAT1 TERMINALS UNIT TERMINAL STRIP TB1 24 VOLT TRANSFORMER TO REMOTE SENSOR 2TH040702224 IF USED NOT USED ADD JUMPER ADD JUMPER 4...

Page 27: ...036 21506 003 C 0405 Unitary Products Group 27 FIGURE 3 UNIT DIMENSIONS 3 5 TON COOLING ONLY ELECTRIC HEAT FRONT VIEW FIGURE 4 UNIT DIMENSIONS 3 5 TON COOLING GAS HEAT FRONT VIEW...

Page 28: ...036 21506 003 C 0405 28 Unitary Products Group FIGURE 5 UNIT WITH ECONOMIZER RAINHOOD FIGURE 6 UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD DETAIL A DETAIL B...

Page 29: ...NTRY See Detail B MOUNTING BRACKET FOR DICONNECT SWITCH Shipped attached to the blower housing inside the blower compartment FIELD SUPPLIED DISCONNECT SWITCH LOCATION BLOWER MOTOR ACCESS FILTER ACCESS...

Page 30: ...036 21506 003 C 0405 30 Unitary Products Group FIGURE 9 TYPICAL APPLICATIONS...

Page 31: ...S WEIGHT DISTRIBUTION UNIT TOTAL A B C D E F DH036 Cooling Electric 565 84 83 82 104 105 107 DH036N04 625 93 92 91 115 117 118 DH036N08 635 94 93 92 117 119 120 DH048 Cooling Electric 610 91 89 88 112...

Page 32: ...5 TON BASIC UNIT DH Cooling Only 565 610 645 DH Gas Electric N04 625 N06 670 N08 635 705 N10 680 715 OPTIONS Economizer 50 26 18 23 28 92 10 5 Motorized Damper Electric Heater 5 7 kW 10 15 kW 20 30 k...

Page 33: ...factory wired piped charged with R 22 refrigerant and factory tested prior to shipment All unit wiring shall be both numbered and color coded All units the cooling performance shall be rated in accord...