background image

036-21506-003-C-0405

14

Unitary Products Group

ROOF CURBS

 - Eight and fourteen-inch high roof curbs 

provide a water-tight seal between the unit and the fin-
ished roof. These full perimeter curbs meet the require-
ments of the National Roofing Contractors Association 
(NRCA) and are shipped knocked-down for field assem-
bly.

Roof curbs are designed to fit inside the base rails of the 
unit and include both a wood nailing strip and duct 
hanger supports.

HIGH ALTITUDE NATURAL GAS

 - Burner orifices and 

pilot orifices are provided for proper furnace operation at 
altitudes up to 6,000 feet.

PROPANE

 - Burner orifices, pilot orifices and gas valve 

parts are provided to convert a natural gas furnace to 
propane.

HIGH ALTITUDE PROPANE 

- Burner orifices and pilot 

orifices are provided for proper furnace operation at alti-
tudes up to 6,000 feet. This accessory supplements the 
basic propane conversion kit.

LOW NOX KIT

 - Required to reduce the emission of 

nitrogen oxides below 40 nano grams per joule.

POWER EXHAUST

 - Our single input economizer 

options are available with power exhaust. Whenever the 
outdoor air intake dampers are opened for free cooling, 
the exhaust fan will be energized to prevent the condi-
tioned space from being over-pressurized during econo-
mizer operation.

The power exhaust option can only be used on bot-
tom duct configurations.

BAROMETRIC RELIEF DAMPER

 - This damper acces-

sory can be used to relieve internal building air pressure 
on units with an economizer without power exhaust. This 
accessory includes a rain hood, a bird screen and a fully 
assembled damper. With bottom duct connections, the 
damper should be mounted over the opening in the 
return air panel. With horizontal ductwork, the accessory 
should be mounted on the return air duct.

ENTHALPY ACCESSORY CONTROL KIT

 - This kit 

contains the required components to convert a single 
enthalpy economizer to dual enthalpy.

BURGLAR BARS

 - Mount in the supply and return 

openings to prevent entry into the duct work.

FLUE EXHAUST EXTENSION KIT

 - In locations with 

wind or weather conditions which may interfere with 
proper exhausting of furnace combustion products, this 
kit can be installed to prevent the flue exhaust from 
entering nearby fresh air intakes.

CO

2

 SENSOR

 - Senses CO

2

 levels and automatically 

overrides the economizer when levels rise above the 
present limits.

COIL GUARD

 - Customers can purchase a coil guard kit 

to protect the condenser coil from damage. This is not a 
hail guard kit.

HAIL GUARD

 - Hail Guard kit is available to prevent unit 

from hail damage. This is a sloped hood that fits above 
the coil.

GAS PIPING KIT

 - This kit supplies all necessary fittings 

and shut off valve.

Summary of Contents for CSA DH 036

Page 1: ...l units include Powder Paint finish that meets ASTM B 117 750 hour salt spray standards Permanently lubricated motors Bottom or side air discharge configuration capability field convertible Manufactur...

Page 2: ...ITY RATINGS ARI 210 240 15 3 GAS HEAT RATINGS 15 4 DH036 COOLING CAPACITIES 3 TON 16 5 DH048 COOLING CAPACITIES 4 TON 17 6 DH060 COOLING CAPACITIES 5 TON 18 7 SUPPLY AIR BLOWER PERFORMANCE 3 TON BELT...

Page 3: ...Options See Next Page Product Generation 1 First Generation 2 Second Generation Voltage 1 208 230 1 60 2 208 230 3 60 4 460 3 60 5 575 3 60 Airflow D H N04 A 2 N AA 1 048 Nominal Cooling Capacity MBH...

Page 4: ...ase Monitor CQ CPC Controller DFS APS Technicoat Evap Cond Coils Coil Guard CR CPC Controller DFS APS Technicoat Evap Cond Coils Phase Monitor Coil Guard CS CPC Controller DFS APS SS Drain Pan CT CPC...

Page 5: ...Controller DFS APS SS Drain Pan Phase Monitor Coil Guard HU Honeywell Excel 10 Controller DFS APS SS Drain Pan Technicoat Cond Coils HV Honeywell Excel 10 Controller DFS APS SS Drain Pan Technicoat Ev...

Page 6: ...Intelli Comfort Controller LB Simplicity Intelli Comfort Controller Phase Monitor LC Simplicity Intelli Comfort Controller Coil Guard LD Simplicity Intelli Comfort Controller Phase Monitor Coil Guard...

Page 7: ...S Drain Pan Dirty Filter Switch Hinged Filter Door Toolless Access Panels BN SS Drain Pan Phase Monitor Coil Guard Dirty Filter Switch Hinged Filter Door Toolless Access Panels BS Bottom Drain Connect...

Page 8: ...FS APS SS Drain Pan Phase Monitor Coil Guard Technicoat Evap and Cond Coils Hinged Filter Door Toolless Access Panels GA Honeywell Excel 10 Controller with Dirty Filter Switch Air Proving Switch Hinge...

Page 9: ...Access Panels UG Technicoat Condenser Coil Coil Guard Dirty Filter Switch Hinged Filter Door Toolless Access Panels UH Technicoat Condenser Coil Phase Monitor Coil Guard Dirty Filter Switch Hinged Fil...

Page 10: ...cess Panels XA Intelli Comfort w Mod Link Controller Hinged Filter Door Toolless Access Panels XB Intelli Comfort w Mod Link Controller Phase Monitor Hinged Filter Door Toolless Access Panels XC Intel...

Page 11: ...uration of cooling and heat Safety Monitoring The control board monitors the high and low pressure switches the freezestats the gas valve if applicable and the temperature limit switch on gas heat uni...

Page 12: ...EATERS Wired for single point power supply These nickel chromium heater elements are pro vided with limit and automatic reset capability to prevent operation at excessive temperatures FILTER OPTIONS S...

Page 13: ...ctors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment COIL GUARD Customers can purchase a coil guard kit to protect the condenser...

Page 14: ...pressurized during econo mizer operation The power exhaust option can only be used on bot tom duct configurations BAROMETRIC RELIEF DAMPER This damper acces sory can be used to relieve internal buildi...

Page 15: ...way of knowing the details of each system This constitutes and expectation to any specification or guaran tee requiring a dBA value or sound data in any other form than sound power level ratings 2 At...

Page 16: ...19 5 34 9 3 73 34 9 34 9 34 9 30 5 26 0 21 5 17 0 72 46 5 3 62 29 7 25 8 21 8 17 8 13 8 42 9 3 83 28 0 24 0 20 0 16 0 12 0 67 41 6 3 53 36 0 32 0 28 0 24 0 20 1 16 1 12 1 38 6 3 74 34 8 30 8 26 8 22...

Page 17: ...9 34 29 24 19 62 39 3 6 39 39 40 35 30 25 20 35 3 9 35 35 37 32 27 22 57 38 3 6 38 38 38 33 28 23 18 34 3 8 34 34 34 29 24 19 72 49 3 8 35 31 26 21 17 45 4 1 33 29 24 20 15 67 44 3 7 43 39 34 30 25 20...

Page 18: ...5 1 53 50 44 38 32 26 20 62 55 4 7 55 55 54 48 42 36 30 49 5 0 49 49 49 43 37 31 25 57 54 4 7 54 54 53 47 41 35 29 49 5 0 49 49 49 43 37 31 25 72 65 4 9 44 39 33 28 23 60 5 2 42 36 31 26 20 67 57 4 8...

Page 19: ...0 916 730 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 1050 1100...

Page 20: ...RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 1050 1100 1085 1500...

Page 21: ...1071 1030 1103 1100 1134 1140 1164 1175 1197 1205 1600 1020 900 1056 965 1088 1035 1118 1065 1145 1105 1170 1130 1198 1150 1500 1004 860 1038 880 1070 925 1101 980 1130 1045 1158 1075 1184 1110 0 60 0...

Page 22: ...ERFORMANCE Tables 3 The pressure through the economizer is greater for 100 outdoor air than for 100 return air If the resistance of the return air duct system is less than 0 25 IWG the unit will deliv...

Page 23: ...121 121 0RGHO 7RQQDJH 9ROWDJH 5 DFK 5 DFK ORZHU 0RWRU RPSUHVVRUV 2 DQ 0RWRU RQY 2XWOHW PSV 0LQLPXP LUFXLW PSDFLW PSV 0D XVH 5 5 6L H PSV OHFWULF HDWHU 0RGHO 1R HDWHU N HDWHU PSV 5 7 SH SHU 1 7KHVH HOH...

Page 24: ...1 121 121 ODEL 4ONNAGE 6OLTAGE INIMUM IRCUIT MPACITY MPS AX USE 2 2 3IZE MPS 2 ACH 2 ACH LOWER OTOR ONV UTLET MPS LECTRIC EATER ODEL O EATER K7 OMPRESSORS EATER MPS AN OTOR 5 7 SH SHU 1 7KHVH HOHFWULF...

Page 25: ...Rows Deep 2 2 2 Fins Per Inch 18 18 18 Face Area Sq Ft 17 1 17 1 17 1 COMPRESSOR Qty Per Unit Recip Type 1 1 1 AIR FILTERS Quantity Per Unit 15 X 20 X 1 or 2 2 2 2 Quantity Per Unit 14 X 25 X 1 or 2...

Page 26: ...Y2 W1 W2 G LED 1 LED 2 COM A1 A2 T T B R Y1 Y2 G C X OCC W2 W1 THERMOSTAT1 TERMINALS UNIT TERMINAL STRIP TB1 24 VOLT TRANSFORMER TO REMOTE SENSOR 2TH040702224 IF USED NOT USED ADD JUMPER ADD JUMPER 4...

Page 27: ...036 21506 003 C 0405 Unitary Products Group 27 FIGURE 3 UNIT DIMENSIONS 3 5 TON COOLING ONLY ELECTRIC HEAT FRONT VIEW FIGURE 4 UNIT DIMENSIONS 3 5 TON COOLING GAS HEAT FRONT VIEW...

Page 28: ...036 21506 003 C 0405 28 Unitary Products Group FIGURE 5 UNIT WITH ECONOMIZER RAINHOOD FIGURE 6 UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD DETAIL A DETAIL B...

Page 29: ...NTRY See Detail B MOUNTING BRACKET FOR DICONNECT SWITCH Shipped attached to the blower housing inside the blower compartment FIELD SUPPLIED DISCONNECT SWITCH LOCATION BLOWER MOTOR ACCESS FILTER ACCESS...

Page 30: ...036 21506 003 C 0405 30 Unitary Products Group FIGURE 9 TYPICAL APPLICATIONS...

Page 31: ...S WEIGHT DISTRIBUTION UNIT TOTAL A B C D E F DH036 Cooling Electric 565 84 83 82 104 105 107 DH036N04 625 93 92 91 115 117 118 DH036N08 635 94 93 92 117 119 120 DH048 Cooling Electric 610 91 89 88 112...

Page 32: ...5 TON BASIC UNIT DH Cooling Only 565 610 645 DH Gas Electric N04 625 N06 670 N08 635 705 N10 680 715 OPTIONS Economizer 50 26 18 23 28 92 10 5 Motorized Damper Electric Heater 5 7 kW 10 15 kW 20 30 k...

Page 33: ...factory wired piped charged with R 22 refrigerant and factory tested prior to shipment All unit wiring shall be both numbered and color coded All units the cooling performance shall be rated in accord...

Page 34: ...purge logic energy saving direct spark ignition and redun dant main gas valve Venter wheel shall be constructed of stainless steel for corrosion resistance The heat exchanger shall be of the tubular t...

Page 35: ...o pre selected positions regardless of the outdoor air enthalpy Dampers return to the fully closed position when the indoor fan motor is de energized Dampers shall fully close on power loss OTHER PRE...

Page 36: ...o change without notice Printed in U S A 036 21506 003 C 0405 Copyright 2005 by Unitary Products Group All rights reserved Supersedes 036 21506 003 B 0504 Unitary 5005 Norman Products York OK Group Dr...

Reviews: