GUIDE SPECIFICATIONS

GENERAL

Units shall be manufactured by York International Unitary 
Products Group in an ISO 9001 certified facility.

York's Sunline Ultra

®

 units are convertible single package 

units. Although the units are primarily designed for curb 
mounting on a roof, they can also be slab-mounted at ground 
level or set on steel beams above a finished roof. Cooling 
only, cooling with gas heat and cooling with electric heat 
models are available with a wide variety of factory-mounted 
options and field-installed accessories to make them suitable 
for almost every application. All units are self-contained and 
assembled on full perimeter base rails with holes in the four 
corners for overhead rigging. Every unit is completely piped, 
wired, charged and tested at the factory to simplify the field 
installation and to provide years of dependable operation. All 
models (including those with an economizer) are suitable for 
either bottom or horizontal duct connections. Models with 
power exhaust are suitable for bottom duct connections only. 
For bottom duct, remove the sheet metal panels from the 
supply and return air openings through the base of the unit. 
For horizontal duct, remove the supply and return air panels 
on the rear of the unit. 

All non-Scroll compressors include crankcase heaters and all 
compressors have internal pressure relief. Every refrigerant 
circuit includes a liquid line filter-drier, a discharge line high 
pressure switch and a suction line with a freezestat and low 
pressure/loss of charge switch.The unit control circuit 
includes a 75 VA transformer, a 24-volt circuit breaker and a 
relay board with a compressor lockout circuit, a terminal strip 
for thermostat wiring, plus an additional set of pin connectors 
to simplify the interface of additional field controls. All units 
have long lasting powder paint cabinets with 750 hour salt 
spray test approval under ASTMB117 procedures. All models 
are CSA listed. All models include a 1-year limited warranty 
on the complete unit. Compressors and electric heater ele-
ments carry a 5-year warranty. Aluminized steel and Stainless 
steel tubular heat exchangers carry a 10-year warranty.

DESCRIPTION

Units shall be factory-assembled, single packaged, Electric 
Cooling/Gas Heat,  Electric Cooling/Optional Electric Heat 
and designed for outdoor mounted installation.

The 3 ton, 4 ton and 5 ton units shall have minimum SEER 
ratings of 12.2, 13.2 and 12.2 respectively. They shall have 
built-in field convertible duct connections for down discharge 
supply/return or horizontal discharge supply/return, and be 
available with factory installed options or field installed acces-
sories. The units shall be factory wired, piped, charged with 
R-22 refrigerant and factory tested prior to shipment. All unit 
wiring shall be both numbered and color coded. All units the 
cooling performance shall be rated in accordance with DOE 
and ARI test procedures. Units shall be CSA listed, classified 
to ANSI Z21.47, UL 1995/CSA No. 236 standards.

UNIT CABINET

Unit cabinet shall be constructed of G90 galvanized steel,
with exterior surfaces coated with a non-chalking, powdered 
paint finish, certified at 750 hours salt spray test per 
ASTMB117 standards. Indoor blower section shall be insu-
lated with a minimum 1/2” thick insulation, coated on the air-
side. Aluminum foil faced insulation shall be used in the 
furnace compartment and be fastened with ridged fasteners 
to prevent insulation from entering the air stream. Cabinet 
panels shall be “large” size, easily removable for servicing 
and maintenance. Full perimeter base rails shall be provided 
to assure reliable transit of equipment, overhead rigging and 
proper sealing on roof curb applications. Disposable 1" filters 
shall be furnished and be accessible through a removable 
access door, sealed airtight. Units filter track shall be 
designed to accommodate either 1" or 2" filters. Fan perfor-
mance measuring ports shall be provided on the outside of 
the cabinet to allow accurate air measurements of evaporator 
fan performance without removing panels or creating air by-
pass of the coils. Condensate pan shall be internally sloped 
and conform to ASHRAE 62-89 self-draining standards. Con-
densate connection shall be a minimum of 3/4” I.D. female 
and be a ridged mount connection.

INDOOR (EVAPORATOR) FAN ASSEMBLY

The indoor fan shall be a factory installed belt drive assembly 
that includes an adjustable pitch motor pulley. Job site 
selected (B.H.P.) brake horsepower shall not exceed the 
motors nameplate horsepower rating, plus the service factor. 
Units shall be designed not to operate above service factor. 
Fan wheel shall be double-inlet type with forward-curved 
blades, dynamically balanced to operate smoothly throughout 
the entire range of operation. Airflow design shall be constant 
air volume. Bearings shall be sealed and permanently lubri-
cated for longer life and no maintenance.

OUTDOOR (CONDENSER) FAN ASSEMBLY

The outdoor fan shall be of the direct-driven propeller type, 
discharge air vertically, have aluminum blades riveted to a 
corrosion resistant steel spider bracket and shall be dynami-
cally balanced for smooth operation. The outdoor fan motor 
shall be totally enclosed with permanently lubricated bear-
ings, internally protected against overload conditions and 
staged independently.

REFRIGERANT COMPONENTS

Compressor:

a.

Shall be  internally protected with internal high-pres-
sure relief and over temperature protection.

b.

Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be exter-
nally isolated on a dedicated, independent 
mounting.

Summary of Contents for CSA DH 036

Page 1: ...l units include Powder Paint finish that meets ASTM B 117 750 hour salt spray standards Permanently lubricated motors Bottom or side air discharge configuration capability field convertible Manufactur...

Page 2: ...ITY RATINGS ARI 210 240 15 3 GAS HEAT RATINGS 15 4 DH036 COOLING CAPACITIES 3 TON 16 5 DH048 COOLING CAPACITIES 4 TON 17 6 DH060 COOLING CAPACITIES 5 TON 18 7 SUPPLY AIR BLOWER PERFORMANCE 3 TON BELT...

Page 3: ...Options See Next Page Product Generation 1 First Generation 2 Second Generation Voltage 1 208 230 1 60 2 208 230 3 60 4 460 3 60 5 575 3 60 Airflow D H N04 A 2 N AA 1 048 Nominal Cooling Capacity MBH...

Page 4: ...ase Monitor CQ CPC Controller DFS APS Technicoat Evap Cond Coils Coil Guard CR CPC Controller DFS APS Technicoat Evap Cond Coils Phase Monitor Coil Guard CS CPC Controller DFS APS SS Drain Pan CT CPC...

Page 5: ...Controller DFS APS SS Drain Pan Phase Monitor Coil Guard HU Honeywell Excel 10 Controller DFS APS SS Drain Pan Technicoat Cond Coils HV Honeywell Excel 10 Controller DFS APS SS Drain Pan Technicoat Ev...

Page 6: ...Intelli Comfort Controller LB Simplicity Intelli Comfort Controller Phase Monitor LC Simplicity Intelli Comfort Controller Coil Guard LD Simplicity Intelli Comfort Controller Phase Monitor Coil Guard...

Page 7: ...S Drain Pan Dirty Filter Switch Hinged Filter Door Toolless Access Panels BN SS Drain Pan Phase Monitor Coil Guard Dirty Filter Switch Hinged Filter Door Toolless Access Panels BS Bottom Drain Connect...

Page 8: ...FS APS SS Drain Pan Phase Monitor Coil Guard Technicoat Evap and Cond Coils Hinged Filter Door Toolless Access Panels GA Honeywell Excel 10 Controller with Dirty Filter Switch Air Proving Switch Hinge...

Page 9: ...Access Panels UG Technicoat Condenser Coil Coil Guard Dirty Filter Switch Hinged Filter Door Toolless Access Panels UH Technicoat Condenser Coil Phase Monitor Coil Guard Dirty Filter Switch Hinged Fil...

Page 10: ...cess Panels XA Intelli Comfort w Mod Link Controller Hinged Filter Door Toolless Access Panels XB Intelli Comfort w Mod Link Controller Phase Monitor Hinged Filter Door Toolless Access Panels XC Intel...

Page 11: ...uration of cooling and heat Safety Monitoring The control board monitors the high and low pressure switches the freezestats the gas valve if applicable and the temperature limit switch on gas heat uni...

Page 12: ...EATERS Wired for single point power supply These nickel chromium heater elements are pro vided with limit and automatic reset capability to prevent operation at excessive temperatures FILTER OPTIONS S...

Page 13: ...ctors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment COIL GUARD Customers can purchase a coil guard kit to protect the condenser...

Page 14: ...pressurized during econo mizer operation The power exhaust option can only be used on bot tom duct configurations BAROMETRIC RELIEF DAMPER This damper acces sory can be used to relieve internal buildi...

Page 15: ...way of knowing the details of each system This constitutes and expectation to any specification or guaran tee requiring a dBA value or sound data in any other form than sound power level ratings 2 At...

Page 16: ...19 5 34 9 3 73 34 9 34 9 34 9 30 5 26 0 21 5 17 0 72 46 5 3 62 29 7 25 8 21 8 17 8 13 8 42 9 3 83 28 0 24 0 20 0 16 0 12 0 67 41 6 3 53 36 0 32 0 28 0 24 0 20 1 16 1 12 1 38 6 3 74 34 8 30 8 26 8 22...

Page 17: ...9 34 29 24 19 62 39 3 6 39 39 40 35 30 25 20 35 3 9 35 35 37 32 27 22 57 38 3 6 38 38 38 33 28 23 18 34 3 8 34 34 34 29 24 19 72 49 3 8 35 31 26 21 17 45 4 1 33 29 24 20 15 67 44 3 7 43 39 34 30 25 20...

Page 18: ...5 1 53 50 44 38 32 26 20 62 55 4 7 55 55 54 48 42 36 30 49 5 0 49 49 49 43 37 31 25 57 54 4 7 54 54 53 47 41 35 29 49 5 0 49 49 49 43 37 31 25 72 65 4 9 44 39 33 28 23 60 5 2 42 36 31 26 20 67 57 4 8...

Page 19: ...0 916 730 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 1050 1100...

Page 20: ...RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 1050 1100 1085 1500...

Page 21: ...1071 1030 1103 1100 1134 1140 1164 1175 1197 1205 1600 1020 900 1056 965 1088 1035 1118 1065 1145 1105 1170 1130 1198 1150 1500 1004 860 1038 880 1070 925 1101 980 1130 1045 1158 1075 1184 1110 0 60 0...

Page 22: ...ERFORMANCE Tables 3 The pressure through the economizer is greater for 100 outdoor air than for 100 return air If the resistance of the return air duct system is less than 0 25 IWG the unit will deliv...

Page 23: ...121 121 0RGHO 7RQQDJH 9ROWDJH 5 DFK 5 DFK ORZHU 0RWRU RPSUHVVRUV 2 DQ 0RWRU RQY 2XWOHW PSV 0LQLPXP LUFXLW PSDFLW PSV 0D XVH 5 5 6L H PSV OHFWULF HDWHU 0RGHO 1R HDWHU N HDWHU PSV 5 7 SH SHU 1 7KHVH HOH...

Page 24: ...1 121 121 ODEL 4ONNAGE 6OLTAGE INIMUM IRCUIT MPACITY MPS AX USE 2 2 3IZE MPS 2 ACH 2 ACH LOWER OTOR ONV UTLET MPS LECTRIC EATER ODEL O EATER K7 OMPRESSORS EATER MPS AN OTOR 5 7 SH SHU 1 7KHVH HOHFWULF...

Page 25: ...Rows Deep 2 2 2 Fins Per Inch 18 18 18 Face Area Sq Ft 17 1 17 1 17 1 COMPRESSOR Qty Per Unit Recip Type 1 1 1 AIR FILTERS Quantity Per Unit 15 X 20 X 1 or 2 2 2 2 Quantity Per Unit 14 X 25 X 1 or 2...

Page 26: ...Y2 W1 W2 G LED 1 LED 2 COM A1 A2 T T B R Y1 Y2 G C X OCC W2 W1 THERMOSTAT1 TERMINALS UNIT TERMINAL STRIP TB1 24 VOLT TRANSFORMER TO REMOTE SENSOR 2TH040702224 IF USED NOT USED ADD JUMPER ADD JUMPER 4...

Page 27: ...036 21506 003 C 0405 Unitary Products Group 27 FIGURE 3 UNIT DIMENSIONS 3 5 TON COOLING ONLY ELECTRIC HEAT FRONT VIEW FIGURE 4 UNIT DIMENSIONS 3 5 TON COOLING GAS HEAT FRONT VIEW...

Page 28: ...036 21506 003 C 0405 28 Unitary Products Group FIGURE 5 UNIT WITH ECONOMIZER RAINHOOD FIGURE 6 UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD DETAIL A DETAIL B...

Page 29: ...NTRY See Detail B MOUNTING BRACKET FOR DICONNECT SWITCH Shipped attached to the blower housing inside the blower compartment FIELD SUPPLIED DISCONNECT SWITCH LOCATION BLOWER MOTOR ACCESS FILTER ACCESS...

Page 30: ...036 21506 003 C 0405 30 Unitary Products Group FIGURE 9 TYPICAL APPLICATIONS...

Page 31: ...S WEIGHT DISTRIBUTION UNIT TOTAL A B C D E F DH036 Cooling Electric 565 84 83 82 104 105 107 DH036N04 625 93 92 91 115 117 118 DH036N08 635 94 93 92 117 119 120 DH048 Cooling Electric 610 91 89 88 112...

Page 32: ...5 TON BASIC UNIT DH Cooling Only 565 610 645 DH Gas Electric N04 625 N06 670 N08 635 705 N10 680 715 OPTIONS Economizer 50 26 18 23 28 92 10 5 Motorized Damper Electric Heater 5 7 kW 10 15 kW 20 30 k...

Page 33: ...factory wired piped charged with R 22 refrigerant and factory tested prior to shipment All unit wiring shall be both numbered and color coded All units the cooling performance shall be rated in accord...

Page 34: ...purge logic energy saving direct spark ignition and redun dant main gas valve Venter wheel shall be constructed of stainless steel for corrosion resistance The heat exchanger shall be of the tubular t...

Page 35: ...o pre selected positions regardless of the outdoor air enthalpy Dampers return to the fully closed position when the indoor fan motor is de energized Dampers shall fully close on power loss OTHER PRE...

Page 36: ...o change without notice Printed in U S A 036 21506 003 C 0405 Copyright 2005 by Unitary Products Group All rights reserved Supersedes 036 21506 003 B 0504 Unitary 5005 Norman Products York OK Group Dr...

Reviews: