STANDARD LIMITED WARRANTIES

Compressor 5 Years

Heat Exchanger 10 Years

Electric Heat Element 5 Years

Other Parts 1 Year

OPTIONAL OUTDOOR AIR 

(Shall be made available by 

either/or):

ELECTRONIC ENTHALPY AUTOMATIC ECONO-
MIZER

- Outdoor and return air dampers that are inter-

locked and positioned by a fully-modulating, spring 
return damper actuator. The maximum leakage rate for 
the outdoor air intake dampers shall not exceed 2% 
when dampers are fully closed and operating against a 
pressure differential of 0.5 IWG. A unit-mounted potenti-
ometer shall be provided to adjust the outdoor and return 
air damper assembly to take in CFM of outdoor air to 
meet the minimum ventilation requirement of the condi-
tioned space during normal operation. During econo-
mizer operation, a mixed-air temperature control shall 
modulate the outdoor and return air damper assembly to 
prevent the supply air temperature from dropping below 
55°F. Changeover from compressor to economizer oper-
ation shall be provided by an integral electronic enthalpy 
control that feeds input into the basic module. The out-
door intake opening shall be covered with a rain hood 
that matches the exterior of the unit. Water eliminator/fil-
ters shall be provided. Simultaneous economizer/com-
pressor operation is also possible. Dampers shall fully 
close on power loss.

MOTORIZED OUTDOOR AIR DAMPERS

 - Outdoor air 

dampers are positioned by a 2-position, spring-return 
damper actuator. The maximum leakage rate for the out-
door air intake dampers shall not exceed 2% when 
dampers are fully closed and operating against a pres-
sure differential of 0.5 IWG. A unit-mounted potentiome-
ter shall be provided to adjust the outdoor damper 
assembly to take in the design CFM of outdoor air to 
meet the ventilation requirements of the conditioned 
space during normal operation. Whenever the indoor fan 
motor is energized, the dampers open up to one of two 
pre-selected positions - regardless of the outdoor air 
enthalpy. Dampers return to the fully closed position 
when the indoor fan motor is de-energized. Dampers 
shall fully close on power loss.

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE

ROOF CURB

 - 14"and 8”  high, full perimeter curb with 

wood nailer (shipped knocked-down).

BAROMETRIC RELIEF DAMPER

 - Contains a rain 

hood, air inlet screen, exhaust damper and mounting 
hardware. Used to relieve internal air pressure through 
the unit.

PROPANE CONVERSION KIT

 - Contains new orifices 

and gas valve parts to convert from natural to L.P. gas. 
One per unit required.

HIGH ALTITUDE - NATURAL GAS

 - Contains orifices 

required for applications between 2000 and 6000 feet 
altitude.

HIGH ALTITUDE - PROPANE GAS

 - Contains orifices 

required for applications between 2000 and 6000 feet 
altitude. Must be used with propane conversion kit.

LOW NOX

 - Required to reduce the emission of nitrogen 

oxides below 40 nanograms per joule.

GAS PIPING

 - Contains 1/2” pipe nipples, fittings and 

gas cock (including panel assess gaskets) required for 
bottom gas supply connection with external shut off.

POWER EXHAUST OPTION

 - To work in conjunction 

with economizers.

ELECTRIC HEATERS

ECONOMIZER/MOTORIZED DAMPER RAIN HOOD

 -

Contains all hood panels and the hardware for assem-
bling.

MANUAL OUTDOOR AIR DAMPER

COIL GUARD KIT

 - Guard for cooling coil.

HAIL GUARD

FLUE EXHAUST EXTENSION

OTHER FACTORY INSTALLED OPTIONS

POWER EXHAUST OPTION

 - To work in conjunction 

with economizers.

STAINLESS STEEL HEAT EXCHANGER

STAINLESS STEEL DRAIN PAN

BOTTOM DRAIN CONNECTION

Summary of Contents for CSA 48

Page 1: ...or frame All units include Powder Paint finish that meets ASTM B 117 1000 hour salt spray standards Permanently lubricated motors Bottom or side air discharge configuration capability field convertibl...

Page 2: ...6 DH048 COOLING CAPACITIES 4 TON 10 7 DH060 COOLING CAPACITIES 5 TON 11 8 SUPPLY AIR BLOWER PERFORMANCE 3 TON BELT DRIVE SIDE DUCT APPLICATION 12 9 SUPPLY AIR BLOWER PERFORMANCE 4 TON BELT DRIVE SIDE...

Page 3: ...1 4 5 W Options 1 3 4 5 X Options 3 5 Y Options 4 5 Z Options 3 4 5 1 Disconnect 2 Non Pwr d Conv Outlet 3 Smoke Detector S A 4 Smoke Detector R A 5 Pwr d Conv Outlet Options SS Drain Pan Configurati...

Page 4: ...n their configuration of cooling and heat Safety Monitoring The control board monitors the high and low pressure switches the freezestats the gas valve if applicable and the temperature limit switch o...

Page 5: ...LIC COATED EVAPORATOR AND CON DENSER COILS Special coating process that utilizes Technicoat 10 1TM processes Coating is applied by total immersion of the complete coil for maximum protection ELECTRIC...

Page 6: ...C BAS CONTROL The Computer Process Controls Model 810 3060 ARTC Advanced Rooftop building auto mation system controller is factory installed Includes supply air sensor return air sensor dirty filter i...

Page 7: ...propane HIGH ALTITUDE PROPANE Burner orifices and pilot orifices are provided for proper furnace operation at alti tudes up to 6 000 feet This accessory supplements the basic propane conversion kit LO...

Page 8: ...2 CAPACITY RATINGS ARI 210 240 1 1 80 67 F Indoor and 95 F outdoor MODEL MBH EER2 2 EER Energy Efficiency Ratio at full load the cooling capacity in Btu s per hour Btuh divided by the power input in...

Page 9: ...9 5 34 9 3 73 34 9 34 9 34 9 30 5 26 0 21 5 17 0 72 46 5 3 62 29 7 25 8 21 8 17 8 13 8 42 9 3 83 28 0 24 0 20 0 16 0 12 0 67 41 6 3 53 36 0 32 0 28 0 24 0 20 1 16 1 12 1 38 6 3 74 34 8 30 8 26 8 22 8...

Page 10: ...34 29 24 19 62 39 3 6 39 39 40 35 30 25 20 35 3 9 35 35 37 32 27 22 57 38 3 6 38 38 38 33 28 23 18 34 3 8 34 34 34 29 24 19 72 49 3 8 35 31 26 21 17 45 4 1 33 29 24 20 15 67 44 3 7 43 39 34 30 25 20 1...

Page 11: ...1 53 50 44 38 32 26 20 62 55 4 7 55 55 54 48 42 36 30 49 5 0 49 49 49 43 37 31 25 57 54 4 7 54 54 53 47 41 35 29 49 5 0 49 49 49 43 37 31 25 72 65 4 9 44 39 33 28 23 60 5 2 42 36 31 26 20 67 57 4 8 5...

Page 12: ...TIC RESISTANCE Table for resistance values on applications other than gas electric units with side duct airflows TABLE 9 SUPPLY AIR BLOWER PERFORMANCE 4 TON BELT DRIVE SIDE DUCT APPLICATION RPM WATTS...

Page 13: ...t 230 460 Volts with side duct connections 2 Includes allowances for a wet evaporator coil 1 filters and the heat exchangers Refer to STATIC RESISTANCE Table for resistance values on applications othe...

Page 14: ...06 0 07 0 08 0 09 0 11 0 13 0 15 0 17 0 20 0 23 0 26 0 06 0 07 0 08 0 09 0 10 0 11 0 12 0 14 0 16 0 19 0 22 0 08 0 10 0 12 0 14 0 16 0 18 0 20 0 23 0 26 0 29 0 32 COOLING ONLY2 RESISTANCE IWG CFM DES...

Page 15: ...3 40 2CE045107252 5 6 15 5 32 7 40 2CE04511025 8 0 22 2 41 0 45 2CE04511525 11 9 33 0 54 5 60 2CE04512025 15 9 44 1 68 4 70 230 3 60 13 1 110 0 2 3 10 6 0 0 None 29 3 40 2CE045105252 5 3 12 7 29 3 40...

Page 16: ...6 25 5 38 4 40 2CE04511525 15 9 38 2 54 3 60 2CE04512025 21 2 51 0 70 2 80 460 3 60 6 7 54 0 1 3 2 6 0 0 None 12 3 15 2CE045107462 6 8 8 2 13 5 15 2CE045110462 10 1 12 1 18 4 20 2CE045115462 13 6 16 4...

Page 17: ...50 2CE045107252 5 6 15 5 45 2 50 2CE04511025 8 0 22 2 53 5 60 2CE04511525 11 9 33 0 67 0 70 2CE04512025 15 9 44 1 80 9 90 230 3 60 13 1 110 0 2 3 10 6 10 0 None 39 3 50 2CE045105252 5 3 12 7 41 7 50...

Page 18: ...25 5 50 9 60 2CE04511525 15 9 38 2 66 8 70 2CE04512025 21 2 51 0 82 7 90 460 3 60 6 7 54 0 1 3 2 6 5 0 None 17 3 20 2CE045107462 6 8 8 2 19 7 20 2CE045110462 10 1 12 1 24 7 25 2CE045115462 13 6 16 4 2...

Page 19: ...CONDENSER COILS Rows Deep 2 2 2 Fins Per Inch 18 18 18 Face Area Sq Ft 17 1 17 1 17 1 COMPRESSOR Qty Per Unit Recip Type 1 1 1 AIR FILTERS Quantity Per Unit 15 X 20 X 1 or 2 2 2 2 Quantity Per Unit 1...

Page 20: ...BACK POSITION COOLING HEATING ELECTRONIC THERMOSTAT MULTI STAGE RH RC Y W G R Y1 W1 C G ADD JUMPER THERMOSTAT1 TERMINALS UNIT TERMINAL STRIP TB1 24 VOLT TRANSFORMER 1ELECTRONIC PROGRAMMABLE THERMOSTA...

Page 21: ...254597 YTG B 0507 Unitary Products Group 21 FIGURE 3 UNIT DIMENSIONS 3 5 TON COOLING ONLY ELECTRIC HEAT FRONT VIEW FIGURE 4 UNIT DIMENSIONS 3 5 TON COOLING GAS HEAT FRONT VIEW...

Page 22: ...254597 YTG B 0507 22 Unitary Products Group FIGURE 5 UNIT WITH ECONOMIZER RAINHOOD FIGURE 6 UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD DETAIL A DETAIL B...

Page 23: ...RY See Detail B MOUNTING BRACKET FOR DICONNECT SWITCH Shipped attached to the blower housing inside the blower compartment FIELD SUPPLIED DISCONNECT SWITCH LOCATION BLOWER MOTOR ACCESS FILTER ACCESS D...

Page 24: ...254597 YTG B 0507 24 Unitary Products Group FIGURE 9 TYPICAL APPLICATIONS...

Page 25: ...82 104 105 107 DH036N04 605 134 132 168 171 90 89 88 112 113 114 DH036D06 615 137 134 171 174 91 90 89 113 115 116 DH036N08 625 139 136 173 177 93 92 91 115 117 118 DH036D10 635 141 138 176 179 94 93...

Page 26: ...DH Cooling Only 565 610 645 DH Gas Electric N04 605 N06 660 N08 625 705 N10 680 715 D06 615 660 695 D10 635 680 715 OPTIONS Economizer 50 26 18 23 28 92 10 5 Motorized Damper Electric Heater 5 7 kW 10...

Page 27: ...ped charged with R 22 refrigerant and factory tested prior to shipment All unit wiring shall be both numbered and color coded All units the cooling performance shall be rated in accordance with DOE an...

Page 28: ...ge logic energy saving direct spark ignition and redun dant main gas valve Venter wheel shall be constructed of stainless steel for corrosion resistance The heat exchanger shall be of the tubular type...

Page 29: ...5 IWG A unit mounted potentiome ter shall be provided to adjust the outdoor damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space duri...

Page 30: ...HASE MONITOR COIL GUARD POWERED GFI CONVENIENCE OUTLET NON POWERED GFI CONVENIENCE OUTLET BAS CONTROLS Simplicity INTELLI Comfort CPC JOHNSON HONEYWELL NOVAR BAS READY ECONOMIZER 2 10 V D C ACTUATOR W...

Page 31: ...254597 YTG B 0507 Unitary Products Group 31...

Page 32: ...t to change without notice Printed in U S A 254597 YTG B 0507 Copyright 2007 by Unitary Products Group All rights reserved Supersedes 254597 YTG A 0306 Unitary 5005 Norman Products York OK Group Drive...

Reviews: