254597-YTG-B-0507

28

Unitary Products Group

Coils:

a.

Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless 
internally enhanced copper tubes with all joints 
brazed. Special Phenolic coating shall be available 
as a factory option.

b.

Evaporator and Condenser coils shall be of the 
direct expansion, draw-thru, design.  

Refrigerant Circuit and Refrigerant Safety Components shall 
include:

a.

Thermal expansion devices (TXV’s).

b.

Filter drier/strainer to eliminate any moisture or for-
eign matter.

c.

Accessible service gage connections on both suc-
tion and liquid lines to charge, evacuate, and mea-
sure refrigerant pressure during any necessary 
servicing or troubleshooting, without losing charge.

d.

The refrigeration system shall provide at least 15°F 
of sub-cooling at design conditions.

UNIT CONTROLS

a.

Unit shall be complete with self-contained low-volt-
age control circuit protected by a resetable circuit 
breaker on the 24-volt transformer side.

b.

Unit shall incorporate a lockout circuit which pro-
vides reset capability at the space thermostat or 
base unit, should any of the following standard 
safety devices trip and shut off compressor.

c.

Loss-of-charge/Low-pressure switch.

d.

High-pressure switch.

e.

Freeze-protection thermostat, evaporator coil. 

f.

If any of the above safety devices trip, a LED (light-
emitting diode) indicator shall flash a diagnostic 
code that indicates which safety switch has tripped.

g.

Unit shall incorporate “AUTO RESET” compressor 
over temperature, over current protection.

h.

Unit shall operate with conventional thermostat 
designs and have a low voltage terminal strip for 
easy hook-up.

i.

Unit control board shall have on-board diagnostics 
and fault code display.

j.

Standard controls shall include anti-short cycle and 
low voltage protection, and permit cooling operation 
down to 0°F.

k.

Control board shall monitor each refrigerant safety 
switch independently.

l.

Control board shall retain last 5 fault codes in non 
volatile memory which will not be lost in the event of 
a power loss.

GAS HEATING SECTION (SINGLE OR 2 STAGE)

Shall be designed with induced draft combustion with post 
purge logic, energy saving direct spark ignition, and redun-
dant main gas valve. Venter wheel shall be constructed of 
stainless steel for corrosion resistance. The heat exchanger 
shall be of the tubular type, constructed of T1-40 aluminized 
steel for corrosion resistance and allowing minimum mixed 
air entering temperature of 25°F. Burners shall be of the 
inshot type, constructed of aluminum coated steel and con-
tain air mixture adjustments. All gas piping shall enter the unit 
cabinet at a single location through either the side or curb 
without any field modifications. Integrated control boards 
shall provide timed control of evaporator fan functioning and 
burner ignition. Heating section shall be provided with the fol-
lowing minimum protection:

a.

Primary and auxiliary high-temperature limit 
switches.

b.

Induced draft motor speed sensor.

c.

Flame roll out switch.

d.

Flame proving controls. 

e.

If any of the above safety devices trip, a LED (light-
emitting diode) indicator shall flash a diagnostic 
code that indicates which safety switch has tripped.

ELECTRIC HEATING SECTION

An electric heating section, with nickel chromium elements, 
shall be provided in a range of 5 thru 30 KW, offering two 
stages of capacity - 16 KW and above on 208/230 volt heaters 
and 20 KW and above on 460 and 575 volt heaters. The heat-
ing section shall have a primary limit control(s) and automatic 
reset to prevent the heating element system from operating at 
an excessive temperature. The heating section assembly 
shall slide out of the unit for easy maintenance and service. 
Units with Electric Heating shall be wired for a single point 
power supply with branch circuit fusing (where required).

UNIT OPERATING CHARACTERISTICS

a.

Unit shall be capable of starting and running at 125°F 
outdoor temperature, exceeding maximum load crite-
ria of ARI Standard 210/240. The compressor, with 
standard controls, shall be capable of operation 
down to 0°F outdoor temperature. Unit shall be pro-
vided with fan time delay to prevent cold air delivery 
before heat exchanger warms up (Gas heat only).

ELECTRICAL REQUIREMENTS

All unit power wiring shall enter unit cabinet at a single factory 
provided location and be capable of side or bottom entry, to 
minimize roof penetrations and avoid unit field modifications. 
Separate side and bottom openings shall be provided for the 
control wiring.

Summary of Contents for CSA 48

Page 1: ...or frame All units include Powder Paint finish that meets ASTM B 117 1000 hour salt spray standards Permanently lubricated motors Bottom or side air discharge configuration capability field convertibl...

Page 2: ...6 DH048 COOLING CAPACITIES 4 TON 10 7 DH060 COOLING CAPACITIES 5 TON 11 8 SUPPLY AIR BLOWER PERFORMANCE 3 TON BELT DRIVE SIDE DUCT APPLICATION 12 9 SUPPLY AIR BLOWER PERFORMANCE 4 TON BELT DRIVE SIDE...

Page 3: ...1 4 5 W Options 1 3 4 5 X Options 3 5 Y Options 4 5 Z Options 3 4 5 1 Disconnect 2 Non Pwr d Conv Outlet 3 Smoke Detector S A 4 Smoke Detector R A 5 Pwr d Conv Outlet Options SS Drain Pan Configurati...

Page 4: ...n their configuration of cooling and heat Safety Monitoring The control board monitors the high and low pressure switches the freezestats the gas valve if applicable and the temperature limit switch o...

Page 5: ...LIC COATED EVAPORATOR AND CON DENSER COILS Special coating process that utilizes Technicoat 10 1TM processes Coating is applied by total immersion of the complete coil for maximum protection ELECTRIC...

Page 6: ...C BAS CONTROL The Computer Process Controls Model 810 3060 ARTC Advanced Rooftop building auto mation system controller is factory installed Includes supply air sensor return air sensor dirty filter i...

Page 7: ...propane HIGH ALTITUDE PROPANE Burner orifices and pilot orifices are provided for proper furnace operation at alti tudes up to 6 000 feet This accessory supplements the basic propane conversion kit LO...

Page 8: ...2 CAPACITY RATINGS ARI 210 240 1 1 80 67 F Indoor and 95 F outdoor MODEL MBH EER2 2 EER Energy Efficiency Ratio at full load the cooling capacity in Btu s per hour Btuh divided by the power input in...

Page 9: ...9 5 34 9 3 73 34 9 34 9 34 9 30 5 26 0 21 5 17 0 72 46 5 3 62 29 7 25 8 21 8 17 8 13 8 42 9 3 83 28 0 24 0 20 0 16 0 12 0 67 41 6 3 53 36 0 32 0 28 0 24 0 20 1 16 1 12 1 38 6 3 74 34 8 30 8 26 8 22 8...

Page 10: ...34 29 24 19 62 39 3 6 39 39 40 35 30 25 20 35 3 9 35 35 37 32 27 22 57 38 3 6 38 38 38 33 28 23 18 34 3 8 34 34 34 29 24 19 72 49 3 8 35 31 26 21 17 45 4 1 33 29 24 20 15 67 44 3 7 43 39 34 30 25 20 1...

Page 11: ...1 53 50 44 38 32 26 20 62 55 4 7 55 55 54 48 42 36 30 49 5 0 49 49 49 43 37 31 25 57 54 4 7 54 54 53 47 41 35 29 49 5 0 49 49 49 43 37 31 25 72 65 4 9 44 39 33 28 23 60 5 2 42 36 31 26 20 67 57 4 8 5...

Page 12: ...TIC RESISTANCE Table for resistance values on applications other than gas electric units with side duct airflows TABLE 9 SUPPLY AIR BLOWER PERFORMANCE 4 TON BELT DRIVE SIDE DUCT APPLICATION RPM WATTS...

Page 13: ...t 230 460 Volts with side duct connections 2 Includes allowances for a wet evaporator coil 1 filters and the heat exchangers Refer to STATIC RESISTANCE Table for resistance values on applications othe...

Page 14: ...06 0 07 0 08 0 09 0 11 0 13 0 15 0 17 0 20 0 23 0 26 0 06 0 07 0 08 0 09 0 10 0 11 0 12 0 14 0 16 0 19 0 22 0 08 0 10 0 12 0 14 0 16 0 18 0 20 0 23 0 26 0 29 0 32 COOLING ONLY2 RESISTANCE IWG CFM DES...

Page 15: ...3 40 2CE045107252 5 6 15 5 32 7 40 2CE04511025 8 0 22 2 41 0 45 2CE04511525 11 9 33 0 54 5 60 2CE04512025 15 9 44 1 68 4 70 230 3 60 13 1 110 0 2 3 10 6 0 0 None 29 3 40 2CE045105252 5 3 12 7 29 3 40...

Page 16: ...6 25 5 38 4 40 2CE04511525 15 9 38 2 54 3 60 2CE04512025 21 2 51 0 70 2 80 460 3 60 6 7 54 0 1 3 2 6 0 0 None 12 3 15 2CE045107462 6 8 8 2 13 5 15 2CE045110462 10 1 12 1 18 4 20 2CE045115462 13 6 16 4...

Page 17: ...50 2CE045107252 5 6 15 5 45 2 50 2CE04511025 8 0 22 2 53 5 60 2CE04511525 11 9 33 0 67 0 70 2CE04512025 15 9 44 1 80 9 90 230 3 60 13 1 110 0 2 3 10 6 10 0 None 39 3 50 2CE045105252 5 3 12 7 41 7 50...

Page 18: ...25 5 50 9 60 2CE04511525 15 9 38 2 66 8 70 2CE04512025 21 2 51 0 82 7 90 460 3 60 6 7 54 0 1 3 2 6 5 0 None 17 3 20 2CE045107462 6 8 8 2 19 7 20 2CE045110462 10 1 12 1 24 7 25 2CE045115462 13 6 16 4 2...

Page 19: ...CONDENSER COILS Rows Deep 2 2 2 Fins Per Inch 18 18 18 Face Area Sq Ft 17 1 17 1 17 1 COMPRESSOR Qty Per Unit Recip Type 1 1 1 AIR FILTERS Quantity Per Unit 15 X 20 X 1 or 2 2 2 2 Quantity Per Unit 1...

Page 20: ...BACK POSITION COOLING HEATING ELECTRONIC THERMOSTAT MULTI STAGE RH RC Y W G R Y1 W1 C G ADD JUMPER THERMOSTAT1 TERMINALS UNIT TERMINAL STRIP TB1 24 VOLT TRANSFORMER 1ELECTRONIC PROGRAMMABLE THERMOSTA...

Page 21: ...254597 YTG B 0507 Unitary Products Group 21 FIGURE 3 UNIT DIMENSIONS 3 5 TON COOLING ONLY ELECTRIC HEAT FRONT VIEW FIGURE 4 UNIT DIMENSIONS 3 5 TON COOLING GAS HEAT FRONT VIEW...

Page 22: ...254597 YTG B 0507 22 Unitary Products Group FIGURE 5 UNIT WITH ECONOMIZER RAINHOOD FIGURE 6 UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD DETAIL A DETAIL B...

Page 23: ...RY See Detail B MOUNTING BRACKET FOR DICONNECT SWITCH Shipped attached to the blower housing inside the blower compartment FIELD SUPPLIED DISCONNECT SWITCH LOCATION BLOWER MOTOR ACCESS FILTER ACCESS D...

Page 24: ...254597 YTG B 0507 24 Unitary Products Group FIGURE 9 TYPICAL APPLICATIONS...

Page 25: ...82 104 105 107 DH036N04 605 134 132 168 171 90 89 88 112 113 114 DH036D06 615 137 134 171 174 91 90 89 113 115 116 DH036N08 625 139 136 173 177 93 92 91 115 117 118 DH036D10 635 141 138 176 179 94 93...

Page 26: ...DH Cooling Only 565 610 645 DH Gas Electric N04 605 N06 660 N08 625 705 N10 680 715 D06 615 660 695 D10 635 680 715 OPTIONS Economizer 50 26 18 23 28 92 10 5 Motorized Damper Electric Heater 5 7 kW 10...

Page 27: ...ped charged with R 22 refrigerant and factory tested prior to shipment All unit wiring shall be both numbered and color coded All units the cooling performance shall be rated in accordance with DOE an...

Page 28: ...ge logic energy saving direct spark ignition and redun dant main gas valve Venter wheel shall be constructed of stainless steel for corrosion resistance The heat exchanger shall be of the tubular type...

Page 29: ...5 IWG A unit mounted potentiome ter shall be provided to adjust the outdoor damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space duri...

Page 30: ...HASE MONITOR COIL GUARD POWERED GFI CONVENIENCE OUTLET NON POWERED GFI CONVENIENCE OUTLET BAS CONTROLS Simplicity INTELLI Comfort CPC JOHNSON HONEYWELL NOVAR BAS READY ECONOMIZER 2 10 V D C ACTUATOR W...

Page 31: ...254597 YTG B 0507 Unitary Products Group 31...

Page 32: ...t to change without notice Printed in U S A 254597 YTG B 0507 Copyright 2007 by Unitary Products Group All rights reserved Supersedes 254597 YTG A 0306 Unitary 5005 Norman Products York OK Group Drive...

Reviews: