GUIDE SPECIFICATIONS

GENERAL

Units shall be manufactured by York International Unitary 
Products Group in an ISO 9001 certified facility.

York's Sunline Ultra

®

 units are convertible single package 

units. Although the units are primarily designed for curb 
mounting on a roof, they can also be slab-mounted at ground 
level or set on steel beams above a finished roof. Cooling 
only, cooling with gas heat and cooling with electric heat 
models are available with a wide variety of factory-mounted 
options and field-installed accessories to make them suitable 
for almost every application. All units are self-contained and 
assembled on full perimeter base rails with holes in the four 
corners for overhead rigging. Every unit is completely piped, 
wired, charged and tested at the factory to simplify the field 
installation and to provide years of dependable operation. All 
models (including those with an economizer) are suitable for 
either bottom or horizontal duct connections. Models with 
power exhaust are suitable for bottom duct connections only. 
For bottom duct, remove the sheet metal panels from the 
supply and return air openings through the base of the unit. 
For horizontal duct, remove the supply and return air panels 
on the rear of the unit. 

All non-Scroll compressors include crankcase heaters and all 
compressors have internal pressure relief. Every refrigerant 
circuit includes a liquid line filter-drier, a discharge line high 
pressure switch and a suction line with a freezestat and low 
pressure/loss of charge switch.The unit control circuit 
includes a 75 VA transformer, a 24-volt circuit breaker and a 
relay board with a compressor lockout circuit, a terminal strip 
for thermostat wiring, plus an additional set of pin connectors 
to simplify the interface of additional field controls. All units 
have long lasting powder paint cabinets with 1000 hour salt 
spray test approval under ASTMB117 procedures. All models 
are CSA listed. All models include a 1-year limited warranty 
on the complete unit. Compressors and electric heater ele-
ments carry a 5-year warranty. Aluminized steel and Stainless 
steel tubular heat exchangers carry a 10-year warranty.

DESCRIPTION

Units shall be factory-assembled, single packaged, Electric 
Cooling/Gas Heat,  Electric Cooling/Optional Electric Heat 
and designed for outdoor mounted installation.

The 3 ton, 4 ton and 5 ton units shall have minimum SEER 
ratings of 12.2, 13.2 and 12.2 respectively. They shall have 
built-in field convertible duct connections for down discharge 
supply/return or horizontal discharge supply/return, and be 
available with factory installed options or field installed acces-
sories. The units shall be factory wired, piped, charged with 
R-22 refrigerant and factory tested prior to shipment. All unit 
wiring shall be both numbered and color coded. All units the 
cooling performance shall be rated in accordance with DOE 
and ARI test procedures. Units shall be CSA listed, classified 
to ANSI Z21.47, UL 1995/CSA No. 236 standards.

UNIT CABINET

Unit cabinet shall be constructed of G90 galvanized steel,
with exterior surfaces coated with a non-chalking, powdered 
paint finish, certified at 1000 hours salt spray test per 
ASTMB117 standards. Indoor blower section shall be insu-
lated with a minimum 1/2” thick insulation, coated on the air-
side. Aluminum foil faced insulation shall be used in the 
furnace compartment and be fastened with ridged fasteners 
to prevent insulation from entering the air stream. Cabinet 
panels shall be “large” size, easily removable for servicing 
and maintenance. Full perimeter base rails shall be provided 
to assure reliable transit of equipment, overhead rigging and 
proper sealing on roof curb applications. Disposable 1" filters 
shall be furnished and be accessible through a removable 
access door, sealed airtight. Units filter track shall be 
designed to accommodate either 1" or 2" filters. Fan perfor-
mance measuring ports shall be provided on the outside of 
the cabinet to allow accurate air measurements of evaporator 
fan performance without removing panels or creating air by-
pass of the coils. Condensate pan shall be internally sloped 
and conform to ASHRAE 62-89 self-draining standards. Con-
densate connection shall be a minimum of 3/4” I.D. female 
and be a ridged mount connection.

INDOOR (EVAPORATOR) FAN ASSEMBLY

The indoor fan shall be a factory installed with either direct 
drive or belt drive assembly that includes an adjustable pitch 
motor pulley. Job site selected brake horsepower (B.H.P.) 
shall not exceed the motors nameplate horsepower rating, 
plus the service factor. Units shall be designed not to operate 
above service factor. Fan wheel shall be double-inlet type 
with forward-curved blades, dynamically balanced to operate 
smoothly throughout the entire range of operation. Airflow 
design shall be constant air volume. Bearings shall be sealed 
and permanently lubricated for longer life and no mainte-
nance.

OUTDOOR (CONDENSER) FAN ASSEMBLY

The outdoor fan shall be of the direct-driven propeller type, 
discharge air vertically, have aluminum blades riveted to a 
corrosion resistant steel spider bracket and shall be dynami-
cally balanced for smooth operation. The outdoor fan motor 
shall be totally enclosed with permanently lubricated bear-
ings, internally protected against overload conditions and 
staged independently.

REFRIGERANT COMPONENTS

Compressor:

a.

Shall be  internally protected with internal high-pres-
sure relief and over temperature protection.

b.

Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be exter-
nally isolated on a dedicated, independent 
mounting.

Summary of Contents for CSA 48

Page 1: ...or frame All units include Powder Paint finish that meets ASTM B 117 1000 hour salt spray standards Permanently lubricated motors Bottom or side air discharge configuration capability field convertibl...

Page 2: ...6 DH048 COOLING CAPACITIES 4 TON 10 7 DH060 COOLING CAPACITIES 5 TON 11 8 SUPPLY AIR BLOWER PERFORMANCE 3 TON BELT DRIVE SIDE DUCT APPLICATION 12 9 SUPPLY AIR BLOWER PERFORMANCE 4 TON BELT DRIVE SIDE...

Page 3: ...1 4 5 W Options 1 3 4 5 X Options 3 5 Y Options 4 5 Z Options 3 4 5 1 Disconnect 2 Non Pwr d Conv Outlet 3 Smoke Detector S A 4 Smoke Detector R A 5 Pwr d Conv Outlet Options SS Drain Pan Configurati...

Page 4: ...n their configuration of cooling and heat Safety Monitoring The control board monitors the high and low pressure switches the freezestats the gas valve if applicable and the temperature limit switch o...

Page 5: ...LIC COATED EVAPORATOR AND CON DENSER COILS Special coating process that utilizes Technicoat 10 1TM processes Coating is applied by total immersion of the complete coil for maximum protection ELECTRIC...

Page 6: ...C BAS CONTROL The Computer Process Controls Model 810 3060 ARTC Advanced Rooftop building auto mation system controller is factory installed Includes supply air sensor return air sensor dirty filter i...

Page 7: ...propane HIGH ALTITUDE PROPANE Burner orifices and pilot orifices are provided for proper furnace operation at alti tudes up to 6 000 feet This accessory supplements the basic propane conversion kit LO...

Page 8: ...2 CAPACITY RATINGS ARI 210 240 1 1 80 67 F Indoor and 95 F outdoor MODEL MBH EER2 2 EER Energy Efficiency Ratio at full load the cooling capacity in Btu s per hour Btuh divided by the power input in...

Page 9: ...9 5 34 9 3 73 34 9 34 9 34 9 30 5 26 0 21 5 17 0 72 46 5 3 62 29 7 25 8 21 8 17 8 13 8 42 9 3 83 28 0 24 0 20 0 16 0 12 0 67 41 6 3 53 36 0 32 0 28 0 24 0 20 1 16 1 12 1 38 6 3 74 34 8 30 8 26 8 22 8...

Page 10: ...34 29 24 19 62 39 3 6 39 39 40 35 30 25 20 35 3 9 35 35 37 32 27 22 57 38 3 6 38 38 38 33 28 23 18 34 3 8 34 34 34 29 24 19 72 49 3 8 35 31 26 21 17 45 4 1 33 29 24 20 15 67 44 3 7 43 39 34 30 25 20 1...

Page 11: ...1 53 50 44 38 32 26 20 62 55 4 7 55 55 54 48 42 36 30 49 5 0 49 49 49 43 37 31 25 57 54 4 7 54 54 53 47 41 35 29 49 5 0 49 49 49 43 37 31 25 72 65 4 9 44 39 33 28 23 60 5 2 42 36 31 26 20 67 57 4 8 5...

Page 12: ...TIC RESISTANCE Table for resistance values on applications other than gas electric units with side duct airflows TABLE 9 SUPPLY AIR BLOWER PERFORMANCE 4 TON BELT DRIVE SIDE DUCT APPLICATION RPM WATTS...

Page 13: ...t 230 460 Volts with side duct connections 2 Includes allowances for a wet evaporator coil 1 filters and the heat exchangers Refer to STATIC RESISTANCE Table for resistance values on applications othe...

Page 14: ...06 0 07 0 08 0 09 0 11 0 13 0 15 0 17 0 20 0 23 0 26 0 06 0 07 0 08 0 09 0 10 0 11 0 12 0 14 0 16 0 19 0 22 0 08 0 10 0 12 0 14 0 16 0 18 0 20 0 23 0 26 0 29 0 32 COOLING ONLY2 RESISTANCE IWG CFM DES...

Page 15: ...3 40 2CE045107252 5 6 15 5 32 7 40 2CE04511025 8 0 22 2 41 0 45 2CE04511525 11 9 33 0 54 5 60 2CE04512025 15 9 44 1 68 4 70 230 3 60 13 1 110 0 2 3 10 6 0 0 None 29 3 40 2CE045105252 5 3 12 7 29 3 40...

Page 16: ...6 25 5 38 4 40 2CE04511525 15 9 38 2 54 3 60 2CE04512025 21 2 51 0 70 2 80 460 3 60 6 7 54 0 1 3 2 6 0 0 None 12 3 15 2CE045107462 6 8 8 2 13 5 15 2CE045110462 10 1 12 1 18 4 20 2CE045115462 13 6 16 4...

Page 17: ...50 2CE045107252 5 6 15 5 45 2 50 2CE04511025 8 0 22 2 53 5 60 2CE04511525 11 9 33 0 67 0 70 2CE04512025 15 9 44 1 80 9 90 230 3 60 13 1 110 0 2 3 10 6 10 0 None 39 3 50 2CE045105252 5 3 12 7 41 7 50...

Page 18: ...25 5 50 9 60 2CE04511525 15 9 38 2 66 8 70 2CE04512025 21 2 51 0 82 7 90 460 3 60 6 7 54 0 1 3 2 6 5 0 None 17 3 20 2CE045107462 6 8 8 2 19 7 20 2CE045110462 10 1 12 1 24 7 25 2CE045115462 13 6 16 4 2...

Page 19: ...CONDENSER COILS Rows Deep 2 2 2 Fins Per Inch 18 18 18 Face Area Sq Ft 17 1 17 1 17 1 COMPRESSOR Qty Per Unit Recip Type 1 1 1 AIR FILTERS Quantity Per Unit 15 X 20 X 1 or 2 2 2 2 Quantity Per Unit 1...

Page 20: ...BACK POSITION COOLING HEATING ELECTRONIC THERMOSTAT MULTI STAGE RH RC Y W G R Y1 W1 C G ADD JUMPER THERMOSTAT1 TERMINALS UNIT TERMINAL STRIP TB1 24 VOLT TRANSFORMER 1ELECTRONIC PROGRAMMABLE THERMOSTA...

Page 21: ...254597 YTG B 0507 Unitary Products Group 21 FIGURE 3 UNIT DIMENSIONS 3 5 TON COOLING ONLY ELECTRIC HEAT FRONT VIEW FIGURE 4 UNIT DIMENSIONS 3 5 TON COOLING GAS HEAT FRONT VIEW...

Page 22: ...254597 YTG B 0507 22 Unitary Products Group FIGURE 5 UNIT WITH ECONOMIZER RAINHOOD FIGURE 6 UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD DETAIL A DETAIL B...

Page 23: ...RY See Detail B MOUNTING BRACKET FOR DICONNECT SWITCH Shipped attached to the blower housing inside the blower compartment FIELD SUPPLIED DISCONNECT SWITCH LOCATION BLOWER MOTOR ACCESS FILTER ACCESS D...

Page 24: ...254597 YTG B 0507 24 Unitary Products Group FIGURE 9 TYPICAL APPLICATIONS...

Page 25: ...82 104 105 107 DH036N04 605 134 132 168 171 90 89 88 112 113 114 DH036D06 615 137 134 171 174 91 90 89 113 115 116 DH036N08 625 139 136 173 177 93 92 91 115 117 118 DH036D10 635 141 138 176 179 94 93...

Page 26: ...DH Cooling Only 565 610 645 DH Gas Electric N04 605 N06 660 N08 625 705 N10 680 715 D06 615 660 695 D10 635 680 715 OPTIONS Economizer 50 26 18 23 28 92 10 5 Motorized Damper Electric Heater 5 7 kW 10...

Page 27: ...ped charged with R 22 refrigerant and factory tested prior to shipment All unit wiring shall be both numbered and color coded All units the cooling performance shall be rated in accordance with DOE an...

Page 28: ...ge logic energy saving direct spark ignition and redun dant main gas valve Venter wheel shall be constructed of stainless steel for corrosion resistance The heat exchanger shall be of the tubular type...

Page 29: ...5 IWG A unit mounted potentiome ter shall be provided to adjust the outdoor damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space duri...

Page 30: ...HASE MONITOR COIL GUARD POWERED GFI CONVENIENCE OUTLET NON POWERED GFI CONVENIENCE OUTLET BAS CONTROLS Simplicity INTELLI Comfort CPC JOHNSON HONEYWELL NOVAR BAS READY ECONOMIZER 2 10 V D C ACTUATOR W...

Page 31: ...254597 YTG B 0507 Unitary Products Group 31...

Page 32: ...t to change without notice Printed in U S A 254597 YTG B 0507 Copyright 2007 by Unitary Products Group All rights reserved Supersedes 254597 YTG A 0306 Unitary 5005 Norman Products York OK Group Drive...

Reviews: