254595-YTG-C-0308

Johnson Controls Unitary Products

33

service. Units with Electric Heating shall be wired for a single 
point power supply with branch circuit fusing (where 
required).

UNIT OPERATING CHARACTERISTICS

a.

Unit shall be capable of starting and running at 
125°F outdoor temperature, exceeding maximum 
load criteria of ARI Standard 210/240. The compres-
sor, with standard controls, shall be capable of oper-
ation down to 0°F outdoor temperature. Unit shall be 
provided with fan time delay to prevent cold air 
delivery before heat exchanger warms up (Gas heat 
only).

ELECTRICAL REQUIREMENTS

All unit power wiring shall enter unit cabinet at a single factory 
provided location and be capable of side or bottom entry, to 
minimize roof penetrations and avoid unit field modifications. 
Separate side and bottom openings shall be provided for the 
control wiring.

STANDARD LIMITED WARRANTIES

Compressor 5 Years

Electric Heat Element 5 Years

Other Parts 1 Year

OPTIONAL OUTDOOR AIR 

(Shall be made available by 

either/or):

ELECTRONIC ENTHALPY AUTOMATIC ECONO-
MIZER

- Outdoor and return air dampers that are inter-

locked and positioned by a fully-modulating, spring 
return damper actuator. The maximum leakage rate for 
the outdoor air intake dampers shall not exceed 2% 
when dampers are fully closed and operating against a 
pressure differential of 0.5 IWG. A unit-mounted potenti-
ometer shall be provided to adjust the outdoor and return 
air damper assembly to take in CFM of outdoor air to 
meet the minimum ventilation requirement of the condi-
tioned space during normal operation. During econo-
mizer operation, a mixed-air temperature control shall 
modulate the outdoor and return air damper assembly to 
prevent the supply air temperature from dropping below 
55°F. Changeover from compressor to economizer oper-
ation shall be provided by an integral electronic enthalpy 
control that feeds input into the basic module. The out-
door intake opening shall be covered with a rain hood 
that matches the exterior of the unit. Water eliminator/fil-
ters shall be provided. Simultaneous economizer/com-
pressor operation is also possible. Dampers shall fully 
close on power loss.

MOTORIZED OUTDOOR AIR DAMPERS

 - Outdoor air 

dampers are positioned by a 2-position, spring-return 
damper actuator. The maximum leakage rate for the out-
door air intake dampers shall not exceed 2% when 
dampers are fully closed and operating against a pres-
sure differential of 0.5 IWG. A unit-mounted potentiome-
ter shall be provided to adjust the outdoor damper 
assembly to take in the design CFM of outdoor air to 
meet the ventilation requirements of the conditioned 
space during normal operation. Whenever the indoor fan 
motor is energized, the dampers open up to one of two 
pre-selected positions - regardless of the outdoor air 
enthalpy. Dampers return to the fully closed position 
when the indoor fan motor is de-energized. Dampers 
shall fully close on power loss.

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE

ROOF CURB

 - 14" and 8”  high, full perimeter curb with 

wood nailer (shipped knocked-down).

BAROMETRIC RELIEF DAMPER

 - Contains a rain 

hood, air inlet screen, exhaust damper and mounting 
hardware. Used to relieve internal air pressure through 
the unit.

POWER EXHAUST OPTION

 - To work in conjunction 

with economizers.

ELECTRIC HEATERS

ECONOMIZER/MOTORIZED DAMPER RAIN HOOD

 -

Contains all hood panels and the hardware for assem-
bling.

MANUAL OUTDOOR AIR DAMPER

COIL GUARD KIT

 - Guard for cooling coil.

HAIL GUARD

OTHER FACTORY INSTALLED OPTIONS

POWER EXHAUST OPTION

 - To work in conjunction 

with economizers.

TECHNICOAT PHENOLIC COATED CONDENSER 
AND EVAPORATOR COIL

ELECTRONIC SINGLE ENTHALPY ECONOMIZER

DIRTY FILTER SWITCH

PHASE MONITOR

COIL GUARD

POWERED GFI CONVENIENCE OUTLET

NON-POWERED GFI CONVENIENCE OUTLET

Summary of Contents for BQ 048

Page 1: ...r Paint finish that meets ASTM B 117 750 hour salt spray standards Permanently lubricated motors Direct Drive or Belt Drive Blower with high static drive option Bottom or side air discharge configurat...

Page 2: ...BQ048 BELT DRIVE BOTTOM DUCT APPLICATION 13 11 SUPPLY AIR BLOWER PERFORMANCE BQ060 BELT DRIVE SIDE DUCT APPLICATION 14 12 SUPPLY AIR BLOWER PERFORMANCE BQ060 BELT DRIVE BOTTOM DUCT APPLICATION 14 13...

Page 3: ...uested or an order placed CPC Controller DFS APS Johnson Controller DFS APS Honeywell Controller DFS APS Novar Controller DFS APS Simplicity IntelliComfort Controller Simplicity IntelliComfort Control...

Page 4: ...e minimum run times For testing the anti short cycle delay can be temporarily overridden with the push of a button Fan Delays Fan on and fan off delays are fully pro grammable and are independent of o...

Page 5: ...ation at excessive temperatures FILTER OPTIONS Standard units are shipped with 1 throw away filters installed 2 pleated filters are offered as a factory installed option CONVENIENCE OUTLET This 110 vo...

Page 6: ...C Advanced Rooftop building auto mation system controller is factory installed Includes supply air sensor return air sensor dirty filter indicator switch and air proving switch HONEYWELL BAS CONTROL T...

Page 7: ...tion NRCA and are shipped knocked down for field assem bly Roof curbs are designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports POWER EXHAUST...

Page 8: ...84 74 67 69 62 57 52 74 41 048 1 600 0 55 HIGH 0 80 85 85 75 68 70 63 58 53 75 42 060 2 000 0 45 HIGH 1 00 86 86 76 69 71 64 59 54 76 43 1 These values have been accessed using a model of sound propag...

Page 9: ...30 28 25 22 18 15 11 62 34 3 9 34 34 33 30 26 23 19 33 4 1 33 33 32 29 25 22 19 57 34 3 9 34 34 34 31 28 24 20 32 4 1 32 32 32 29 26 22 19 72 42 4 0 28 25 21 17 14 39 4 2 26 23 19 16 13 67 37 4 0 32 3...

Page 10: ...62 42 4 6 42 42 41 37 32 27 22 39 4 8 39 39 37 34 29 24 19 57 42 4 5 42 42 42 37 33 27 23 38 4 7 38 38 38 33 30 25 20 72 49 4 8 35 31 26 22 46 5 1 34 29 25 20 67 44 4 6 40 40 35 31 26 22 39 4 9 36 36...

Page 11: ...62 53 5 8 53 53 52 46 40 34 28 49 6 5 49 49 47 42 36 30 24 57 53 5 8 53 53 52 46 41 35 27 49 6 4 49 49 48 43 37 31 25 72 62 5 9 45 39 34 28 59 6 8 44 38 33 27 67 57 5 9 51 49 44 38 33 27 53 6 5 45 45...

Page 12: ...19 9 24 9 32 1 39 4 47 6 54 5 KW 3 6 3 7 4 4 4 1 4 4 5 5 7 MBH 12 1 17 22 27 7 34 5 42 3 51 2 58 6 KW 3 3 3 4 3 5 3 6 3 6 3 8 4 4 5 MBH 11 6 16 3 21 2 26 6 33 2 40 7 49 2 56 3 KW 3 4 3 5 3 6 3 7 3 8...

Page 13: ...7 1489 1 37 Field Supplied Drive TABLE 9 SUPPLY AIR BLOWER PERFORMANCE BQ048 BELT DRIVE SIDE DUCT APPLICATION Air Flow CFM Available External Static Pressure IWG1 1 Blower performance includes 1 filte...

Page 14: ...upplied Drive Standard Drive Option HIgh Static Drive Option 1200 663 0 48 773 0 53 875 0 59 969 0 65 1056 0 72 1138 0 80 1214 0 88 1286 0 96 1354 1 04 1420 1 13 1400 692 0 57 802 0 61 904 0 67 998 0...

Page 15: ...Fully Closed 036 3 1 5 1 73 1VL44 AK64 805 865 920 980 1035 1095 1 5 1 73 1VP56 AK66 1115 1170 1225 1280 1335 1390 048 4 1 5 1 73 1VL44 AK56 930 995 1060 1130 1195 1260 1 5 1 73 1VP56 AK61 1210 1270...

Page 16: ...HP motor is required 6 1150 RPM is within the range of the 30 40 HP drives but step 5 requires the 40 HP motor 7 Using the 40 HP motor and drive 5 5 turns open will achieve 1150 RPM Example Supply Air...

Page 17: ...48 0 817 0 787 0 758 0 730 0 703 0 676 0 651 0 600 0 650 0 700 0 750 0 800 0 850 0 900 0 950 1 000 1 050 1 100 40 50 60 70 80 90 100 Air Temperature F Correction Factor Sea Level 1000 ft 2000 ft 3000...

Page 18: ...35 E05 4 0 1 11 1 39 6 50 E07 5 6 1 15 5 45 1 50 E10 8 0 1 22 2 53 4 60 E15 11 9 2 33 0 67 0 70 E20 15 9 2 44 1 80 8 90 230 3 60 14 7 130 0 23 0 2 3 5 0 0 0 None 25 7 35 E05 5 3 1 13 3 41 6 50 E07 7...

Page 19: ...35 E05 4 0 1 11 1 39 8 50 E07 5 6 1 15 5 45 3 50 E10 8 0 1 22 2 53 6 60 E15 11 9 2 33 0 67 2 70 E20 15 9 2 44 1 81 0 90 230 3 60 14 7 130 0 23 0 2 3 5 2 0 0 None 25 9 35 E05 5 3 1 13 3 41 8 50 E07 7 5...

Page 20: ...25 9 35 E05 4 0 1 11 1 39 8 50 E07 5 6 1 15 5 45 3 50 E10 8 0 1 22 2 53 6 60 E15 11 9 2 33 0 67 2 70 E20 15 9 2 44 1 81 0 90 230 3 60 14 7 130 0 23 0 2 3 5 2 0 0 None 25 9 35 E05 5 3 1 13 3 41 8 50 E...

Page 21: ...5 E05 4 0 1 11 1 49 6 60 E07 5 6 1 15 5 55 1 60 E10 8 0 1 22 2 63 4 70 E15 11 9 2 33 0 77 0 80 E20 15 9 2 44 1 90 8 100 230 3 60 14 7 130 0 23 0 2 3 5 0 10 0 None 35 7 45 E05 5 3 1 13 3 51 6 60 E07 7...

Page 22: ...E05 4 0 1 11 1 49 8 60 E07 5 6 1 15 5 55 3 60 E10 8 0 1 22 2 63 6 70 E15 11 9 2 33 0 77 2 80 E20 15 9 2 44 1 91 0 100 230 3 60 14 7 130 0 23 0 2 3 5 2 10 0 None 35 9 50 E05 5 3 1 13 3 51 8 60 E07 7 5...

Page 23: ...5 9 50 E05 4 0 1 11 1 49 8 60 E07 5 6 1 15 5 55 3 60 E10 8 0 1 22 2 63 6 70 E15 11 9 2 33 0 77 2 80 E20 15 9 2 44 1 91 0 100 230 3 60 14 7 130 0 23 0 2 3 5 2 10 0 None 35 9 50 E05 5 3 1 13 3 51 8 60 E...

Page 24: ...2 1 2 Nom CFM 4300 4200 4500 CONDENSER COILS Rows Deep 1 1 1 Fins Per Inch 20 20 20 Face Area Sq Ft 17 1 17 1 17 1 COMPRESSOR Qty Per Unit Reciprocating Type 1 1 1 AIR FILTERS Quantity Per Unit 15 X...

Page 25: ...FORMER TO REMOTE SENSOR 2TH040702224 IF USED NOT USED ADD JUMPER ADD JUMPER 4 4 3 2 1 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 INCLUDES SUBBASE 2 SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LE...

Page 26: ...254595 YTG C 0308 26 Johnson Controls Unitary Products FIGURE 3 UNIT DIMENSIONS 3 5 TON HEAT PUMP FRONT VIEW FIGURE 4 UNIT WITH ECONOMIZER RAINHOOD DETAIL A...

Page 27: ...254595 YTG C 0308 Johnson Controls Unitary Products 27 FIGURE 5 UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD DETAIL B FIGURE 6 UNIT DIMENSIONS REAR VIEW...

Page 28: ...5 8 KO Gas Piping Front D 1 1 2 KO Gas Piping Bottom 1 Opening in the bottom to the unit can be located by the side in the insulation 2 Do not remove the 2 knockout ring TABLE 29 MINIMUM CLEARANCES LO...

Page 29: ...254595 YTG C 0308 Johnson Controls Unitary Products 29 FIGURE 8 TYPICAL APPLICATIONS...

Page 30: ...TAL A B C D BQ036 628 139 137 174 177 BQ048 668 148 146 185 189 BQ060 693 154 151 192 196 TABLE 31 BQ 6 POINT LOADS WEIGHT DISTRIBUTION UNIT TOTAL A B C D E F BQ036 628 93 92 91 116 117 119 BQ048 668...

Page 31: ...ure loss of charge switch The unit control circuit includes a 75 VA transformer a 24 volt circuit breaker and a relay board with a compressor lockout circuit a terminal strip for thermostat wiring plu...

Page 32: ...ent mounting Coils a Evaporator and condenser coils shall have alumi num plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed Special Phenolic coating sha...

Page 33: ...ssor to economizer oper ation shall be provided by an integral electronic enthalpy control that feeds input into the basic module The out door intake opening shall be covered with a rain hood that mat...

Page 34: ...0 V D C ACTUATOR WITHOUT A CONTROLLER HINGED FILTER DOOR ACCESS AND TOOLESS ACCESS PANELS STAINLESS STEEL DRAIN PAN BOTTOM DRAIN CONNECTION 2 PLEATED FILTERS DISCONNECT SWITCH SUPPLY AIR SMOKE DETECTO...

Page 35: ...254595 YTG C 0308 Johnson Controls Unitary Products 35...

Page 36: ...change without notice Printed in U S A 254595 YTG C 0308 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes 254595 YTG B 0507 Johnson Controls Unitary Products 5005 York Drive Norma...

Reviews: