![York BQ 048 Technical Manual Download Page 14](http://html1.mh-extra.com/html/york/bq-048/bq-048_technical-manual_913425014.webp)
254595-YTG-C-0308
14
Johnson Controls Unitary Products
TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (BQ060 BELT DRIVE) - SIDE DUCT APPLICATION
Air
Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard Drive Option
HIgh Static Drive Option
1200
680
0.47
781
0.52
874
0.58
960
0.65
1041
0.72
1115
0.80
1185
0.88
1251
0.96
1314
1.05
1375
1.14
1400
706
0.56
807
0.61
901
0.67
987
0.73
1067
0.80
1142
0.88
1212
0.96
1278
1.05
1341
1.13
1401
1.22
1600
737
0.67
839
0.72
932
0.77
1018
0.84
1098
0.91
1173
0.99
1243
1.07
1309
1.15
1372
1.24
1433
1.33
1800
774
0.80
875
0.85
968
0.90
1055
0.97
1135
1.04
1209
1.12
1279
1.20
1345
1.28
1408
1.37
1469
1.46
2000
815
0.95
916
1.00
1010
1.06
1096
1.12
1176
1.19
1251
1.27
1321
1.35
1387
1.44
1450
1.52
1510
1.61
2200
862
1.12
963
1.17
1056
1.23
1142
1.29
1223
1.36
1297
1.44
1367
1.52
1433
1.61
1496
1.70
1557
1.78
2400
913
1.31
1014
1.36
1107
1.42
1194
1.49
1274
1.56
1349
1.63
1419
1.72
1485
1.80
1548
1.89
1608
1.98
2600
969
1.52
1070
1.57
1163
1.63
1250
1.70
1330
1.77
1405
1.84
1475
1.93
1541
2.01
1603
2.10
1664
2.19
TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (BQ060 BELT DRIVE) - BOTTOM DUCT APPLICATION
Air
Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard Drive Option
HIgh Static Drive Option
1200
663
0.48
773
0.53
875
0.59
969
0.65
1056
0.72
1138
0.80
1214
0.88
1286
0.96
1354
1.04
1420
1.13
1400
692
0.57
802
0.61
904
0.67
998
0.73
1085
0.80
1167
0.88
1243
0.96
1315
1.04
1383
1.13
1449
1.21
1600
726
0.67
836
0.72
938
0.78
1032
0.84
1119
0.91
1201
0.98
1277
1.06
1349
1.15
1417
1.23
1483
1.32
1800
766
0.80
876
0.85
977
0.90
1072
0.97
1159
1.04
1240
1.11
1316
1.19
1388
1.27
1457
1.36
1523
1.45
2000
811
0.95
921
0.99
1023
1.05
1117
1.11
1204
1.18
1285
1.26
1362
1.34
1434
1.42
1502
1.51
1568
1.59
2200
861
1.11
971
1.16
1073
1.22
1167
1.28
1255
1.35
1336
1.43
1412
1.51
1484
1.59
1553
1.68
1619
1.76
2400
917
1.30
1027
1.35
1129
1.41
1223
1.47
1311
1.54
1392
1.62
1468
1.69
1540
1.78
1609
1.86
1675
1.95
2600
978
1.51
1088
1.56
1190
1.61
1284
1.68
1371
1.75
1453
1.82
1529
1.90
1601
1.98
1670
2.07
1736
2.15
Field Supplied Drive
TABLE 13: SUPPLY AIR BLOWER PERFORMANCE (BQ036, 048 & 060 DIRECT DRIVE) -
SIDE DUCT APPLICATION
UNIT
TONNAGE
MOTOR
1
SPEED
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
2
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
CFM
WA
T
T
S
CFM
WA
T
T
S
CFM
WA
T
T
S
CFM
WA
T
T
S
CFM
WA
T
T
S
CFM
WA
T
T
S
CFM
WA
T
T
S
CFM
WA
T
T
S
CFM
WA
T
T
S
3
3
HI
-
-
-
-
-
-
1720
825
1665
795
1600
765
1540
735
1490
700
1380
670
MED
1660
850
1630
820
1590
780
1550
750
1500
720
1450
690
1400
665
1360
650
1270
610
LOW
1470
750
1440
725
1410
700
1370
675
1330
650
1290
625
1250
610
1220
600
1130
560
4
3
HI
-
-
-
-
2000
1010
1950
975
1905
945
1840
910
1770
825
1660
825
1530
775
MED
1810
910
1780
880
1740
850
1700
825
1665
800
1620
775
1560
740
1480
700
1390
660
LOW
1635
810
1610
780
1580
760
1555
740
1540
730
1510
715
1460
690
1400
660
1300
615
5
3
HI
-
-
-
-
2500
1400
2420
1350
2340
1300
2260
1250
2160
1190
2060
1135
1925
1065
MED
2390
1350
2350
1300
2300
1255
2245
1210
2190
1165
2130
1120
2065
1075
1990
1030
1900
970
LOW
2270
1320
2230
1270
2190
1220
2145
1170
2090
1110
2030
1070
1960
1020
1890
970
1810
920
1. Factory set on medium speed tap.
2. Includes allowances for a wet evaporator coil, 1” filters. Refer to STATIC RESISTANCES Table for resistance values.
3. Side Flow application (230/460/575 Volts)