TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (BQ060 BELT DRIVE) - SIDE DUCT APPLICATION

Air

Flow

(CFM)

Available External Static Pressure - IWG

1

1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive

Standard Drive Option

HIgh Static Drive Option

1200

680

0.47

781

0.52

874

0.58

960

0.65

1041

0.72

1115

0.80

1185

0.88

1251

0.96

1314

1.05

1375

1.14

1400

706

0.56

807

0.61

901

0.67

987

0.73

1067

0.80

1142

0.88

1212

0.96

1278

1.05

1341

1.13

1401

1.22

1600

737

0.67

839

0.72

932

0.77

1018

0.84

1098

0.91

1173

0.99

1243

1.07

1309

1.15

1372

1.24

1433

1.33

1800

774

0.80

875

0.85

968

0.90

1055

0.97

1135

1.04

1209

1.12

1279

1.20

1345

1.28

1408

1.37

1469

1.46

2000

815

0.95

916

1.00

1010

1.06

1096

1.12

1176

1.19

1251

1.27

1321

1.35

1387

1.44

1450

1.52

1510

1.61

2200

862

1.12

963

1.17

1056

1.23

1142

1.29

1223

1.36

1297

1.44

1367

1.52

1433

1.61

1496

1.70

1557

1.78

2400

913

1.31

1014

1.36

1107

1.42

1194

1.49

1274

1.56

1349

1.63

1419

1.72

1485

1.80

1548

1.89

1608

1.98

2600

969

1.52

1070

1.57

1163

1.63

1250

1.70

1330

1.77

1405

1.84

1475

1.93

1541

2.01

1603

2.10

1664

2.19

TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (BQ060 BELT DRIVE) - BOTTOM DUCT APPLICATION

Air

Flow

(CFM)

Available External Static Pressure - IWG

1

1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Field Supplied Drive

Standard Drive Option

HIgh Static Drive Option

1200

663

0.48

773

0.53

875

0.59

969

0.65

1056

0.72

1138

0.80

1214

0.88

1286

0.96

1354

1.04

1420

1.13

1400

692

0.57

802

0.61

904

0.67

998

0.73

1085

0.80

1167

0.88

1243

0.96

1315

1.04

1383

1.13

1449

1.21

1600

726

0.67

836

0.72

938

0.78

1032

0.84

1119

0.91

1201

0.98

1277

1.06

1349

1.15

1417

1.23

1483

1.32

1800

766

0.80

876

0.85

977

0.90

1072

0.97

1159

1.04

1240

1.11

1316

1.19

1388

1.27

1457

1.36

1523

1.45

2000

811

0.95

921

0.99

1023

1.05

1117

1.11

1204

1.18

1285

1.26

1362

1.34

1434

1.42

1502

1.51

1568

1.59

2200

861

1.11

971

1.16

1073

1.22

1167

1.28

1255

1.35

1336

1.43

1412

1.51

1484

1.59

1553

1.68

1619

1.76

2400

917

1.30

1027

1.35

1129

1.41

1223

1.47

1311

1.54

1392

1.62

1468

1.69

1540

1.78

1609

1.86

1675

1.95

2600

978

1.51

1088

1.56

1190

1.61

1284

1.68

1371

1.75

1453

1.82

1529

1.90

1601

1.98

1670

2.07

1736

2.15

Field Supplied Drive

TABLE 13: SUPPLY AIR BLOWER PERFORMANCE (BQ036, 048 & 060 DIRECT DRIVE) -

SIDE DUCT APPLICATION

UNIT

TONNAGE

MOTOR

1

SPEED

AVAILABLE EXTERNAL STATIC PRESSURE - IWG

2

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

CFM

 WA

T

T

S

CFM

 WA

T

T

S

CFM

 WA

T

T

S

CFM

 WA

T

T

S

CFM

 WA

T

T

S

CFM

 WA

T

T

S

CFM

 WA

T

T

S

CFM

 WA

T

T

S

CFM

 WA

T

T

S

3

3

HI

-

-

-

-

-

-

1720

825

1665

795

1600

765

1540

735

1490

700

1380

670

MED

1660

850

1630

820

1590

780

1550

750

1500

720

1450

690

1400

665

1360

650

1270

610

LOW

1470

750

1440

725

1410

700

1370

675

1330

650

1290

625

1250

610

1220

600

1130

560

4

3

HI

-

-

-

-

2000

1010

1950

975

1905

945

1840

910

1770

825

1660

825

1530

775

MED

1810

910

1780

880

1740

850

1700

825

1665

800

1620

775

1560

740

1480

700

1390

660

LOW

1635

810

1610

780

1580

760

1555

740

1540

730

1510

715

1460

690

1400

660

1300

615

5

3

HI

-

-

-

-

2500

1400

2420

1350

2340

1300

2260

1250

2160

1190

2060

1135

1925

1065

MED

2390

1350

2350

1300

2300

1255

2245

1210

2190

1165

2130

1120

2065

1075

1990

1030

1900

970

LOW

2270

1320

2230

1270

2190

1220

2145

1170

2090

1110

2030

1070

1960

1020

1890

970

1810

920

1. Factory set on medium speed tap.
2. Includes allowances for a wet evaporator coil, 1” filters. Refer to STATIC RESISTANCES Table for resistance values.
3. Side Flow application (230/460/575 Volts)

Summary of Contents for BQ 048

Page 1: ...r Paint finish that meets ASTM B 117 750 hour salt spray standards Permanently lubricated motors Direct Drive or Belt Drive Blower with high static drive option Bottom or side air discharge configurat...

Page 2: ...BQ048 BELT DRIVE BOTTOM DUCT APPLICATION 13 11 SUPPLY AIR BLOWER PERFORMANCE BQ060 BELT DRIVE SIDE DUCT APPLICATION 14 12 SUPPLY AIR BLOWER PERFORMANCE BQ060 BELT DRIVE BOTTOM DUCT APPLICATION 14 13...

Page 3: ...uested or an order placed CPC Controller DFS APS Johnson Controller DFS APS Honeywell Controller DFS APS Novar Controller DFS APS Simplicity IntelliComfort Controller Simplicity IntelliComfort Control...

Page 4: ...e minimum run times For testing the anti short cycle delay can be temporarily overridden with the push of a button Fan Delays Fan on and fan off delays are fully pro grammable and are independent of o...

Page 5: ...ation at excessive temperatures FILTER OPTIONS Standard units are shipped with 1 throw away filters installed 2 pleated filters are offered as a factory installed option CONVENIENCE OUTLET This 110 vo...

Page 6: ...C Advanced Rooftop building auto mation system controller is factory installed Includes supply air sensor return air sensor dirty filter indicator switch and air proving switch HONEYWELL BAS CONTROL T...

Page 7: ...tion NRCA and are shipped knocked down for field assem bly Roof curbs are designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports POWER EXHAUST...

Page 8: ...84 74 67 69 62 57 52 74 41 048 1 600 0 55 HIGH 0 80 85 85 75 68 70 63 58 53 75 42 060 2 000 0 45 HIGH 1 00 86 86 76 69 71 64 59 54 76 43 1 These values have been accessed using a model of sound propag...

Page 9: ...30 28 25 22 18 15 11 62 34 3 9 34 34 33 30 26 23 19 33 4 1 33 33 32 29 25 22 19 57 34 3 9 34 34 34 31 28 24 20 32 4 1 32 32 32 29 26 22 19 72 42 4 0 28 25 21 17 14 39 4 2 26 23 19 16 13 67 37 4 0 32 3...

Page 10: ...62 42 4 6 42 42 41 37 32 27 22 39 4 8 39 39 37 34 29 24 19 57 42 4 5 42 42 42 37 33 27 23 38 4 7 38 38 38 33 30 25 20 72 49 4 8 35 31 26 22 46 5 1 34 29 25 20 67 44 4 6 40 40 35 31 26 22 39 4 9 36 36...

Page 11: ...62 53 5 8 53 53 52 46 40 34 28 49 6 5 49 49 47 42 36 30 24 57 53 5 8 53 53 52 46 41 35 27 49 6 4 49 49 48 43 37 31 25 72 62 5 9 45 39 34 28 59 6 8 44 38 33 27 67 57 5 9 51 49 44 38 33 27 53 6 5 45 45...

Page 12: ...19 9 24 9 32 1 39 4 47 6 54 5 KW 3 6 3 7 4 4 4 1 4 4 5 5 7 MBH 12 1 17 22 27 7 34 5 42 3 51 2 58 6 KW 3 3 3 4 3 5 3 6 3 6 3 8 4 4 5 MBH 11 6 16 3 21 2 26 6 33 2 40 7 49 2 56 3 KW 3 4 3 5 3 6 3 7 3 8...

Page 13: ...7 1489 1 37 Field Supplied Drive TABLE 9 SUPPLY AIR BLOWER PERFORMANCE BQ048 BELT DRIVE SIDE DUCT APPLICATION Air Flow CFM Available External Static Pressure IWG1 1 Blower performance includes 1 filte...

Page 14: ...upplied Drive Standard Drive Option HIgh Static Drive Option 1200 663 0 48 773 0 53 875 0 59 969 0 65 1056 0 72 1138 0 80 1214 0 88 1286 0 96 1354 1 04 1420 1 13 1400 692 0 57 802 0 61 904 0 67 998 0...

Page 15: ...Fully Closed 036 3 1 5 1 73 1VL44 AK64 805 865 920 980 1035 1095 1 5 1 73 1VP56 AK66 1115 1170 1225 1280 1335 1390 048 4 1 5 1 73 1VL44 AK56 930 995 1060 1130 1195 1260 1 5 1 73 1VP56 AK61 1210 1270...

Page 16: ...HP motor is required 6 1150 RPM is within the range of the 30 40 HP drives but step 5 requires the 40 HP motor 7 Using the 40 HP motor and drive 5 5 turns open will achieve 1150 RPM Example Supply Air...

Page 17: ...48 0 817 0 787 0 758 0 730 0 703 0 676 0 651 0 600 0 650 0 700 0 750 0 800 0 850 0 900 0 950 1 000 1 050 1 100 40 50 60 70 80 90 100 Air Temperature F Correction Factor Sea Level 1000 ft 2000 ft 3000...

Page 18: ...35 E05 4 0 1 11 1 39 6 50 E07 5 6 1 15 5 45 1 50 E10 8 0 1 22 2 53 4 60 E15 11 9 2 33 0 67 0 70 E20 15 9 2 44 1 80 8 90 230 3 60 14 7 130 0 23 0 2 3 5 0 0 0 None 25 7 35 E05 5 3 1 13 3 41 6 50 E07 7...

Page 19: ...35 E05 4 0 1 11 1 39 8 50 E07 5 6 1 15 5 45 3 50 E10 8 0 1 22 2 53 6 60 E15 11 9 2 33 0 67 2 70 E20 15 9 2 44 1 81 0 90 230 3 60 14 7 130 0 23 0 2 3 5 2 0 0 None 25 9 35 E05 5 3 1 13 3 41 8 50 E07 7 5...

Page 20: ...25 9 35 E05 4 0 1 11 1 39 8 50 E07 5 6 1 15 5 45 3 50 E10 8 0 1 22 2 53 6 60 E15 11 9 2 33 0 67 2 70 E20 15 9 2 44 1 81 0 90 230 3 60 14 7 130 0 23 0 2 3 5 2 0 0 None 25 9 35 E05 5 3 1 13 3 41 8 50 E...

Page 21: ...5 E05 4 0 1 11 1 49 6 60 E07 5 6 1 15 5 55 1 60 E10 8 0 1 22 2 63 4 70 E15 11 9 2 33 0 77 0 80 E20 15 9 2 44 1 90 8 100 230 3 60 14 7 130 0 23 0 2 3 5 0 10 0 None 35 7 45 E05 5 3 1 13 3 51 6 60 E07 7...

Page 22: ...E05 4 0 1 11 1 49 8 60 E07 5 6 1 15 5 55 3 60 E10 8 0 1 22 2 63 6 70 E15 11 9 2 33 0 77 2 80 E20 15 9 2 44 1 91 0 100 230 3 60 14 7 130 0 23 0 2 3 5 2 10 0 None 35 9 50 E05 5 3 1 13 3 51 8 60 E07 7 5...

Page 23: ...5 9 50 E05 4 0 1 11 1 49 8 60 E07 5 6 1 15 5 55 3 60 E10 8 0 1 22 2 63 6 70 E15 11 9 2 33 0 77 2 80 E20 15 9 2 44 1 91 0 100 230 3 60 14 7 130 0 23 0 2 3 5 2 10 0 None 35 9 50 E05 5 3 1 13 3 51 8 60 E...

Page 24: ...2 1 2 Nom CFM 4300 4200 4500 CONDENSER COILS Rows Deep 1 1 1 Fins Per Inch 20 20 20 Face Area Sq Ft 17 1 17 1 17 1 COMPRESSOR Qty Per Unit Reciprocating Type 1 1 1 AIR FILTERS Quantity Per Unit 15 X...

Page 25: ...FORMER TO REMOTE SENSOR 2TH040702224 IF USED NOT USED ADD JUMPER ADD JUMPER 4 4 3 2 1 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 INCLUDES SUBBASE 2 SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LE...

Page 26: ...254595 YTG C 0308 26 Johnson Controls Unitary Products FIGURE 3 UNIT DIMENSIONS 3 5 TON HEAT PUMP FRONT VIEW FIGURE 4 UNIT WITH ECONOMIZER RAINHOOD DETAIL A...

Page 27: ...254595 YTG C 0308 Johnson Controls Unitary Products 27 FIGURE 5 UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD DETAIL B FIGURE 6 UNIT DIMENSIONS REAR VIEW...

Page 28: ...5 8 KO Gas Piping Front D 1 1 2 KO Gas Piping Bottom 1 Opening in the bottom to the unit can be located by the side in the insulation 2 Do not remove the 2 knockout ring TABLE 29 MINIMUM CLEARANCES LO...

Page 29: ...254595 YTG C 0308 Johnson Controls Unitary Products 29 FIGURE 8 TYPICAL APPLICATIONS...

Page 30: ...TAL A B C D BQ036 628 139 137 174 177 BQ048 668 148 146 185 189 BQ060 693 154 151 192 196 TABLE 31 BQ 6 POINT LOADS WEIGHT DISTRIBUTION UNIT TOTAL A B C D E F BQ036 628 93 92 91 116 117 119 BQ048 668...

Page 31: ...ure loss of charge switch The unit control circuit includes a 75 VA transformer a 24 volt circuit breaker and a relay board with a compressor lockout circuit a terminal strip for thermostat wiring plu...

Page 32: ...ent mounting Coils a Evaporator and condenser coils shall have alumi num plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed Special Phenolic coating sha...

Page 33: ...ssor to economizer oper ation shall be provided by an integral electronic enthalpy control that feeds input into the basic module The out door intake opening shall be covered with a rain hood that mat...

Page 34: ...0 V D C ACTUATOR WITHOUT A CONTROLLER HINGED FILTER DOOR ACCESS AND TOOLESS ACCESS PANELS STAINLESS STEEL DRAIN PAN BOTTOM DRAIN CONNECTION 2 PLEATED FILTERS DISCONNECT SWITCH SUPPLY AIR SMOKE DETECTO...

Page 35: ...254595 YTG C 0308 Johnson Controls Unitary Products 35...

Page 36: ...change without notice Printed in U S A 254595 YTG C 0308 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes 254595 YTG B 0507 Johnson Controls Unitary Products 5005 York Drive Norma...

Reviews: