GUIDE SPECIFICATIONS

GENERAL

Units shall be manufactured by York International Unitary 
Products Group in an ISO 9001 certified facility.

York's Sunline 2000™ and Sunline Magnum™ units are con-
vertible single package units. All models have dual indepen-
dent refrigerant circuits for efficient part load operation and 
maximum comfort control. Although the units are primarily 
designed for curb mounting on a roof, they can also be slab-
mounted at ground level or set on steel beams above a fin-
ished roof. Cooling only, cooling with gas heat and cooling 
with electric heat models are available with a wide variety of 
factory-mounted options and field-installed accessories to 
make them suitable for almost every application. All units are 
self-contained and assembled on full perimeter base rails 
with holes in the four corners for overhead rigging. Every unit 
is completely piped, wired, charged and tested at the factory 
to simplify the field installation and to provide years of 
dependable operation. All models (including those with an 
economizer) are suitable for either bottom or horizontal duct 
connections. Models with power exhaust are suitable for bot-
tom duct connections only. For bottom duct, remove the 
sheet metal panels from the supply and return air openings 
through the base of the unit. For horizontal duct, replace the 
supply and return air panels on the rear of the unit with a side 
duct flange accessory. All supply air blowers are equipped 
with a belt drive that can be adjusted to meet the exact 
requirements of the job. 

Each unit shall have 2 condenser fan motors. A high speed 
drive accessory is available for applications with a higher 
CFM and/or static pressure requirement. All compressors 
include crankcase heat and internal pressure relief. Every 
refrigerant circuit includes an expansion valve, a liquid line fil-
ter-drier, a discharge line high pressure switch and a suction 
line with a freezestat and low pressure/loss of charge switch. 
The unit control circuit includes a 75 VA transformer, a 24-volt 
circuit breaker and a relay board with two compressor lockout 
circuits, a terminal strip for thermostat wiring, plus an addi-
tional set of pin connectors to simplify the interface of addi-
tional field controls. All units have long lasting powder paint 
cabinets with 750 hour salt spray test approval under ASTM-
B117 procedures. All models are CSA approved. All models 
include a 1-year limited warranty on the complete unit. Com-
pressors and electric heater elements carry an additional 4-
year warranty. Aluminized steel tubular heat exchangers 
carry an additional 9-year warranty.

DESCRIPTION

Units shall be factory-assembled, single packaged, BP180, 
240 Optional Electric Heat, designed for outdoor mounted 
installation. These units shall have minimum EER ratings of 
9.8 (15 ton) and 10.2 (20 ton).

They shall have built-in field convertible duct connections for 
down discharge supply/return or horizontal discharge supply/
return, and be available with factory installed options or field 
installed accessories. The units shall be factory wired, piped, 
charged with R-22 refrigerant and factory tested prior to ship-
ment. All unit wiring shall be both numbered and color coded. 
All units shall be manufactured in a facility certified to ISO 
9001 standards and the cooling performance shall be rated in 
accordance with DOE and ARI test procedures. Units shall be 
CGA listed, classified to ANSIZ21.47 standards, UL 1995/
CAN/CSA No. 236-M90 conditions. 

UNIT CABINET

Unit cabinet shall be constructed of G90 galvanized steel, 
with exterior surfaces coated with a non-chalking, powdered 
paint finish, certified at 750 hours salt spray test per ASTM-
B117 standards. Indoor blower section shall be insulated with 
a minimum 1/2" thick insulation, coated on the airside. Alumi-
num foil faced insulation shall be used in the furnace com-
partment and be fastened with ridged fasteners to prevent 
insulation from entering the air stream. Cabinet panels shall 
be "large" size, easily removable for servicing and mainte-
nance. Full perimeter base rails shall be provided to assure 
reliable transit of equipment, overhead rigging and proper 
sealing on roof curb applications. Disposable 2" filters shall 
be furnished and be accessible through a removable access 
door, sealed airtight. Units filter track shall be designed to 
accommodate either 2" or 4" filters. Fan performance mea-
suring ports shall be provided on the outside of the cabinet to 
allow accurate air measurements of evaporator fan perfor-
mance without removing panels or creating air by-pass of the 
coils. Condensate pan shall be internally sloped and conform 
to ASHRAE 62-89 self-draining standards. Condensate con-
nection shall be a minimum of 1" I.D. female and be a ridged 
mount connection. Unit shall incorporate a fixed outdoor air 
damper with an outdoor air intake opening covered with a 
bird screen and a rain hood painted to match the exterior of 
the unit. 

INDOOR (EVAPORATOR) FAN ASSEMBLY 

Fan shall be a belt drive assembly and include an adjustable- 
pitch motor pulley. Job site selected (B.H.P.) brake horse-
power shall not exceed the motors nameplate horsepower 
rating, plus the service factor. Units shall be designed not to 
operate above service factor. Fan wheel shall be double-inlet 
type with forward-curved blades, dynamically balanced to 
operate smoothly throughout the entire range of operation. 
Airflow design shall be constant air volume. Bearings shall be 
sealed and permanently lubricated for longer life and no 
maintenance. 

OUTDOOR (CONDENSER) FAN ASSEMBLY 

The outdoor fans shall be of the direct-driven propeller type, 
discharge air vertically, have aluminum blades riveted to cor-
rosion resistant steel spider brackets and shall be dynami-
cally balanced for smooth operation. The 2 outdoor fan 
motors (15 ton) and 4 outdoor fan motors (20 ton) shall be 

Summary of Contents for BP 180

Page 1: ...ture decreases This helps to eliminate unnecessary and costly defrosts All units include Simplicity Control Board Powder Paint finish that meets ASTM B 117 750 hour salt spray standards Two stage cool...

Page 2: ...ENSIONS 15 20 TON 30 15 ROOF CURB BENEFITS 30 16 UNIT AND CURB APPLICATIONS 31 17 TYPICAL APPLICATIONS 15 TON 31 18 TYPICAL UNIT APPLICATIONS 20 TON 31 19 TYPICAL ROOF TOP INSTALLATION 15 TON SHOWN 32...

Page 3: ...c heat G Std Mtr Drive 4 Filters Single Input Econ R Options 3 4 H Std Mtr Drive 4 Filters Single Input Econ Power Exhaust S Option 5 L Std Mtr Drive BAS Ready Econ No BAS Controller w 2 Pleated Filte...

Page 4: ...oat Evap Cond Coils CP CPC Controller DFS APS Technicoat Evap Cond Coils Phase Monitor CQ CPC Controller DFS APS Technicoat Evap Cond Coils Coil Guard CR CPC Controller DFS APS Technicoat Evap Cond Co...

Page 5: ...ell Excel 10 Controller DFS APS Technicoat Cond Coil Phase Monitor Hinged Filter Door Tooless Access Panels GG Honeywell Excel 10 Controller DFS APS Technicoat Cond Coil Coil Guard Hinged Filter Door...

Page 6: ...chnicoat Evap Cond Coils NP Novar ETC 3 Controller DFS APS Technicoat Evap Cond Coils Phase Monitor NQ Novar ETC 3 Controller DFS APS Technicoat Evap Cond Coils Coil Guard NR Novar ETC 3 Controller DF...

Page 7: ...Condenser Coil Phase Monitor Dirty Filter Switch Hinged Filter Door Tooless Access Panels UG Technicoat Condenser Coil Coil Guard Dirty Filter Switch Hinged Filter Door Tooless Access Panels UH Techni...

Page 8: ...itional assis tance Optionally the control board can be pro grammed to lockout the compressors when the outdoor air temperature is low or when free cooling is available Anti Short Cycle Protection To...

Page 9: ...E OUTLET This 110 volt outlet can be powered by the unit with a stepdown transformer or you may order the unit with a non powered conve nience outlet that can be wired in the field DISCONNECT SWITCH F...

Page 10: ...o relieve internal building air pressure on units with an economizer without power exhaust This accessory includes a rain hood a bird screen and a fully assembled damper With bottom duct connections t...

Page 11: ...RMINAL BLOCK For Single Point Power Supply With Electirc Heat KNOCKOUT FOR SIDE CONTROL WIRING AND SIDE POWER WIRING ENTRY BOTTOM CONTROL WIRING ENTRY ELECTRIC HEATER LOCATION OPTION BELT DRIVE BLOWER...

Page 12: ...40 226 10 3 10 2 218 3 4 129 2 1 18 36 54 72 HEAT PUMP WITH ELECTRIC HEAT MODEL MBH EER IPLV BP180E18 164 9 9 9 5 BP180E36 164 9 9 9 5 BP180E54 162 9 8 9 4 BP180E72 160 9 8 9 4 BP240E18 226 10 3 10 2...

Page 13: ...65 0 13 12 165 0 165 0 165 0 144 1 123 3 102 4 81 5 57 169 1 11 99 169 1 169 1 169 1 148 2 127 3 106 5 85 6 163 8 13 25 163 8 163 8 163 8 142 9 122 1 101 2 80 3 AIR ON EVAPORATOR COIL TEMPERATURE OF A...

Page 14: ...154 2 128 3 217 17 7 216 8 216 8 216 8 190 9 165 0 139 0 113 1 57 228 0 16 2 228 0 228 0 228 0 202 1 176 2 150 2 124 3 215 17 5 214 7 214 7 214 7 188 7 162 8 136 9 110 9 AIR ON EVAPORATOR COIL TEMPER...

Page 15: ...3 100 9 77 6 N A N A 67 197 1 23 3 182 1 179 4 165 6 142 2 118 9 95 6 72 3 62 179 4 23 0 182 1 182 1 179 4 160 7 137 4 114 0 90 7 57 182 1 22 8 182 1 182 1 179 4 158 7 135 4 112 1 88 8 8350 72 221 3 2...

Page 16: ...00 55 MBH 46 67 89 110 132 153 175 196 KW 7 8 8 3 8 8 9 4 9 9 10 4 10 9 11 4 70 MBH 42 64 85 106 128 149 171 192 KW 9 8 10 3 10 9 11 4 11 9 12 4 12 9 13 4 80 MBH 43 65 86 108 129 150 172 193 KW 11 5 1...

Page 17: ...MBH 48 76 105 134 162 191 220 248 KW 10 4 11 0 11 5 12 1 12 6 13 2 13 7 14 3 70 MBH 43 72 101 129 158 187 215 244 KW 12 2 12 7 13 3 13 8 14 4 14 9 15 5 16 0 80 MBH 37 65 94 123 152 180 209 238 KW 13 6...

Page 18: ...208 VOLT AND HIGH SPEED DRIVE ACCESSORY 965 6 0 1 2 2 9 2 6 1 0 3 6 3 2 0 8 4 0 3 6 0 5 4 7 4 2 0 4 5 0 4 4 980 5 5 1 3 3 0 2 7 1 1 3 7 3 3 0 9 4 1 3 7 0 6 4 8 4 3 0 5 5 1 4 6 1025 4 5 1 5 3 2 2 9 1...

Page 19: ...6 6 9 5 8 0 1 7 3 6 1 1010 4 0 1 7 5 8 4 9 1 6 6 3 5 3 1 4 6 9 5 8 0 9 7 5 6 3 0 4 7 9 6 7 1020 3 5 1 8 6 1 5 1 1 7 6 5 5 5 1 5 7 1 6 0 1 0 7 8 6 6 0 5 8 3 7 0 1035 3 0 1 9 6 2 5 2 1 8 6 8 5 7 1 6 7 4...

Page 20: ...TANCES1 DESCRIPTION RESISTANCE IWG CFM 15 TON 20 TON 4500 6000 7200 6000 8000 9400 WET INDOOR COIL 0 1 0 1 0 1 0 1 0 1 0 1 ELECTRIC HEAT OPTIONS 18 KW 0 1 0 1 0 1 0 1 0 1 0 1 36 KW 0 1 0 2 0 3 0 1 0 2...

Page 21: ...p o s i t i o n 2 4 V o l t T r a n s f o r m e r T O R E M O T E S E N S O R 2 E T 0 4 7 0 1 3 2 4 I F U S E D O C C W 1 W 2 Y 1 G Y 2 X R S D C R E M O T E M I N P O S FIGURE 4 FIELD WIRING 24 VOLT...

Page 22: ...NNECT T E R M I N A L B L O C K T B 1 G R O U N D L U G T H R E E P H A S E P O W E R S U P P L Y F A C T O R Y O R F I E L D S U P P L I E D D I S C O N N E C T TABLE 12 VOLTAGE LIMITATIONS POWER SUP...

Page 23: ...3 126 1 150 E36 36 0 2 86 6 126 3 150 E54 54 0 2 129 9 147 9 175 E72 72 0 2 173 2 191 2 225 460 11 0 90 2 2 7 2 0 0 0 0 36 4 45 E18 18 0 1 21 7 63 4 70 E36 36 0 2 43 3 63 4 70 E54 54 0 2 65 0 74 0 90...

Page 24: ...136 2 150 E36 36 0 2 86 6 138 8 150 E54 54 0 2 129 9 160 4 175 E72 72 0 2 173 2 203 7 225 460 11 0 90 2 2 7 2 5 0 0 0 41 4 50 E18 18 0 1 21 7 68 4 70 E36 36 0 2 43 3 69 4 70 E54 54 0 2 65 0 80 2 90 E7...

Page 25: ...ach 30 30 FAN MOTOR HP Each 1 25 3 4 NOM CFM TOTAL Each 6500 5000 OUTDOOR COIL ROWS DEEP 3 2 FINS PER INCH 15 20 FACE AREA Sq Ft 36 0 63 8 COMPRESSOR Qty Per Unit SCROLL 2 2 AIR FILTERS QUANTITY PER U...

Page 26: ...15 TON RETURN AIR SUPPLY AIR OUTDOOR AIR OUTDOOR AIR Economizer All dimensions are in inches They are subject to change without notice Certified dimensions will be provided upon request FIGURE 7 UNIT...

Page 27: ...shipped with the bottom duct openings covered An accessory flange kit is avail able for connecting side ducts For bottom duct applications 1 Remove the side panels from the supply and return air compa...

Page 28: ...8 2 FIGURE 11 CENTER OF GRAVITY APPROXIMATE CENTER OF GRAVITY OUTDOOR COIL END OF UNIT BACK FRONT 92 125 15 TON 136 20 TON 45 15 TON 46 20 TON 60 15 TON 47 20 TON DUCT COVERS Units are shipped with t...

Page 29: ...IX POINT LOADS UNIT 4 POINT LOADS LBS TOTAL A B C D 180 2190 513 510 558 559 240 2840 495 925 925 495 NOTE These weights are with economizer and 72 kW electric heat A D C E B F A D B C UNIT 6 POINT LO...

Page 30: ...036 21490 002 A 0204 30 Unitary Products Group FIGURE 14 ROOF CURB DIMENSIONS 15 20 TON FIGURE 15 ROOF CURB BENEFITS...

Page 31: ...4 Unitary Products Group 31 FIGURE 16 UNIT AND CURB APPLICATIONS FIGURE 17 TYPICAL APPLICATIONS 15 TON FIGURE 18 TYPICAL UNIT APPLICATIONS 20 TON ROOF JACK INSTALLATION ROOF CURB INSTALLATION SLAB ON...

Page 32: ...CONTROL TERMINAL BLOCK TERMINALS ON A LIMITED NUMBER OF THERMOSTATS 3 1 2 4 3 1 2 4 Second stage heating not required on single stage heating units Second stage cooling not required on single stage c...

Page 33: ...s of 9 8 15 ton and 10 2 20 ton They shall have built in field convertible duct connections for down discharge supply return or horizontal discharge supply return and be available with factory install...

Page 34: ...y devices trip a LED light emitting diode indicator shall flash a diagnostic code that indicates which safety switch has tripped d Unit shall incorporate AUTO RESET compressor over temperature over cu...

Page 35: ...ust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation Whenever the indoor fan mo...

Page 36: ...o change without notice Printed in U S A 036 21490 002 A 0204 Copyright by Unitary Products Group 2004 All rights reserved Supersedes 036 21490 001 A 1202 Unitary 5005 Norman Products York OK Group Dr...