036-21490-002-A-0204

Unitary Products Group

27

 

NOTE: Units and ductwork are approved for zero clearance

to combustible materials when equipped with elec-
tric heaters.

NOTE: All entry holes should be field sealed to prevent rain

water entry into building.

    

TABLE 18: MINIMUM CLEARANCES

LOCATION

CLEARANCE

Front

36”

Back

24” (Less Economizer)

49” (With Economizer)

Left Side (Filter Access)

24” (Less Economizer)

36” (With Economizer)

Right Side (Cond. Coil)

36”

Below Unit

1

1. Units (applicable in U.S.A. only) may be installed on 

combustible floors made from wood or class A, B or C 
roof covering material.

0”

Above Unit

2

2. Units must be installed outdoors. Overhanging struc-

tures or shrubs should not obstruct outdoor air dis-
charge outlet.

72” With 36” Maximum

Horizontal Overhang (For

Condenser Air Discharge)

TABLE 19: UTILITIES ENTRY DATA

HOLE

OPENING SIZE (DIA.)

USED FOR

A

1-1/8” KO

Control Wiring

Front

3/4” NPS (Fem.)

Bottom

B

3-5/8” KO

Power Wiring

Front

3” NPS (Fem.)

Bottom

DUCT COVERS - Units are shipped with the bottom
duct openings covered. An accessory flange kit is avail-
able for connecting side ducts.

For bottom duct applications:

1. Remove the side panels from the supply and return
    air compartments to gain access to the bottom

    supply and return air duct covers.

2. Remove and discard the bottom duct covers. (Duct

    openings are closed with sheet metal covers except

    when the unit includes a power exhaust option. The

    covering consists of a heavy black paper composition.)

3. Replace the side supply and return air compartment
    panels.

For side duct applications;

1. Replace the side panels on the supply and return air
    compartments with the accessory flange kit panels.

2. Connect ductwork to the duct flanges on the rear of
    the unit.

OUTDOOR AIR PANEL SIZE

15 TON UNITS 23-3/4"  X 43-5/8"

FIGURE 8 -

DETAIL “X” ACCY. SIDE SUPPLY & RETURN AIR OPENINGS - 15 TON

SUPPLY
AIR

RETURN
AIR

OUTDOOR
AIR

5-1/8"

18-5/8"

27-3/4"

28-5/8"

40-1/2"

OUTDOOR AIR
COMPARTMENT
ACCESS

FILTER
ACCESS

1" NPT FEMALE
COND. DRAIN
CONNECTION

DOT PLUG
(For pressure
drop reading)

EVAPORATOR
SECTION

CONDENSER
SECTION

GAUGE LINE
ACCESS

40-3/8"

3-3/4"

COMPRESSOR
ACCESS

SUPPLY AIR
ACCESS

RETURN AIR
ACCESS

REAR

VIEW

Summary of Contents for BP 180

Page 1: ...ture decreases This helps to eliminate unnecessary and costly defrosts All units include Simplicity Control Board Powder Paint finish that meets ASTM B 117 750 hour salt spray standards Two stage cool...

Page 2: ...ENSIONS 15 20 TON 30 15 ROOF CURB BENEFITS 30 16 UNIT AND CURB APPLICATIONS 31 17 TYPICAL APPLICATIONS 15 TON 31 18 TYPICAL UNIT APPLICATIONS 20 TON 31 19 TYPICAL ROOF TOP INSTALLATION 15 TON SHOWN 32...

Page 3: ...c heat G Std Mtr Drive 4 Filters Single Input Econ R Options 3 4 H Std Mtr Drive 4 Filters Single Input Econ Power Exhaust S Option 5 L Std Mtr Drive BAS Ready Econ No BAS Controller w 2 Pleated Filte...

Page 4: ...oat Evap Cond Coils CP CPC Controller DFS APS Technicoat Evap Cond Coils Phase Monitor CQ CPC Controller DFS APS Technicoat Evap Cond Coils Coil Guard CR CPC Controller DFS APS Technicoat Evap Cond Co...

Page 5: ...ell Excel 10 Controller DFS APS Technicoat Cond Coil Phase Monitor Hinged Filter Door Tooless Access Panels GG Honeywell Excel 10 Controller DFS APS Technicoat Cond Coil Coil Guard Hinged Filter Door...

Page 6: ...chnicoat Evap Cond Coils NP Novar ETC 3 Controller DFS APS Technicoat Evap Cond Coils Phase Monitor NQ Novar ETC 3 Controller DFS APS Technicoat Evap Cond Coils Coil Guard NR Novar ETC 3 Controller DF...

Page 7: ...Condenser Coil Phase Monitor Dirty Filter Switch Hinged Filter Door Tooless Access Panels UG Technicoat Condenser Coil Coil Guard Dirty Filter Switch Hinged Filter Door Tooless Access Panels UH Techni...

Page 8: ...itional assis tance Optionally the control board can be pro grammed to lockout the compressors when the outdoor air temperature is low or when free cooling is available Anti Short Cycle Protection To...

Page 9: ...E OUTLET This 110 volt outlet can be powered by the unit with a stepdown transformer or you may order the unit with a non powered conve nience outlet that can be wired in the field DISCONNECT SWITCH F...

Page 10: ...o relieve internal building air pressure on units with an economizer without power exhaust This accessory includes a rain hood a bird screen and a fully assembled damper With bottom duct connections t...

Page 11: ...RMINAL BLOCK For Single Point Power Supply With Electirc Heat KNOCKOUT FOR SIDE CONTROL WIRING AND SIDE POWER WIRING ENTRY BOTTOM CONTROL WIRING ENTRY ELECTRIC HEATER LOCATION OPTION BELT DRIVE BLOWER...

Page 12: ...40 226 10 3 10 2 218 3 4 129 2 1 18 36 54 72 HEAT PUMP WITH ELECTRIC HEAT MODEL MBH EER IPLV BP180E18 164 9 9 9 5 BP180E36 164 9 9 9 5 BP180E54 162 9 8 9 4 BP180E72 160 9 8 9 4 BP240E18 226 10 3 10 2...

Page 13: ...65 0 13 12 165 0 165 0 165 0 144 1 123 3 102 4 81 5 57 169 1 11 99 169 1 169 1 169 1 148 2 127 3 106 5 85 6 163 8 13 25 163 8 163 8 163 8 142 9 122 1 101 2 80 3 AIR ON EVAPORATOR COIL TEMPERATURE OF A...

Page 14: ...154 2 128 3 217 17 7 216 8 216 8 216 8 190 9 165 0 139 0 113 1 57 228 0 16 2 228 0 228 0 228 0 202 1 176 2 150 2 124 3 215 17 5 214 7 214 7 214 7 188 7 162 8 136 9 110 9 AIR ON EVAPORATOR COIL TEMPER...

Page 15: ...3 100 9 77 6 N A N A 67 197 1 23 3 182 1 179 4 165 6 142 2 118 9 95 6 72 3 62 179 4 23 0 182 1 182 1 179 4 160 7 137 4 114 0 90 7 57 182 1 22 8 182 1 182 1 179 4 158 7 135 4 112 1 88 8 8350 72 221 3 2...

Page 16: ...00 55 MBH 46 67 89 110 132 153 175 196 KW 7 8 8 3 8 8 9 4 9 9 10 4 10 9 11 4 70 MBH 42 64 85 106 128 149 171 192 KW 9 8 10 3 10 9 11 4 11 9 12 4 12 9 13 4 80 MBH 43 65 86 108 129 150 172 193 KW 11 5 1...

Page 17: ...MBH 48 76 105 134 162 191 220 248 KW 10 4 11 0 11 5 12 1 12 6 13 2 13 7 14 3 70 MBH 43 72 101 129 158 187 215 244 KW 12 2 12 7 13 3 13 8 14 4 14 9 15 5 16 0 80 MBH 37 65 94 123 152 180 209 238 KW 13 6...

Page 18: ...208 VOLT AND HIGH SPEED DRIVE ACCESSORY 965 6 0 1 2 2 9 2 6 1 0 3 6 3 2 0 8 4 0 3 6 0 5 4 7 4 2 0 4 5 0 4 4 980 5 5 1 3 3 0 2 7 1 1 3 7 3 3 0 9 4 1 3 7 0 6 4 8 4 3 0 5 5 1 4 6 1025 4 5 1 5 3 2 2 9 1...

Page 19: ...6 6 9 5 8 0 1 7 3 6 1 1010 4 0 1 7 5 8 4 9 1 6 6 3 5 3 1 4 6 9 5 8 0 9 7 5 6 3 0 4 7 9 6 7 1020 3 5 1 8 6 1 5 1 1 7 6 5 5 5 1 5 7 1 6 0 1 0 7 8 6 6 0 5 8 3 7 0 1035 3 0 1 9 6 2 5 2 1 8 6 8 5 7 1 6 7 4...

Page 20: ...TANCES1 DESCRIPTION RESISTANCE IWG CFM 15 TON 20 TON 4500 6000 7200 6000 8000 9400 WET INDOOR COIL 0 1 0 1 0 1 0 1 0 1 0 1 ELECTRIC HEAT OPTIONS 18 KW 0 1 0 1 0 1 0 1 0 1 0 1 36 KW 0 1 0 2 0 3 0 1 0 2...

Page 21: ...p o s i t i o n 2 4 V o l t T r a n s f o r m e r T O R E M O T E S E N S O R 2 E T 0 4 7 0 1 3 2 4 I F U S E D O C C W 1 W 2 Y 1 G Y 2 X R S D C R E M O T E M I N P O S FIGURE 4 FIELD WIRING 24 VOLT...

Page 22: ...NNECT T E R M I N A L B L O C K T B 1 G R O U N D L U G T H R E E P H A S E P O W E R S U P P L Y F A C T O R Y O R F I E L D S U P P L I E D D I S C O N N E C T TABLE 12 VOLTAGE LIMITATIONS POWER SUP...

Page 23: ...3 126 1 150 E36 36 0 2 86 6 126 3 150 E54 54 0 2 129 9 147 9 175 E72 72 0 2 173 2 191 2 225 460 11 0 90 2 2 7 2 0 0 0 0 36 4 45 E18 18 0 1 21 7 63 4 70 E36 36 0 2 43 3 63 4 70 E54 54 0 2 65 0 74 0 90...

Page 24: ...136 2 150 E36 36 0 2 86 6 138 8 150 E54 54 0 2 129 9 160 4 175 E72 72 0 2 173 2 203 7 225 460 11 0 90 2 2 7 2 5 0 0 0 41 4 50 E18 18 0 1 21 7 68 4 70 E36 36 0 2 43 3 69 4 70 E54 54 0 2 65 0 80 2 90 E7...

Page 25: ...ach 30 30 FAN MOTOR HP Each 1 25 3 4 NOM CFM TOTAL Each 6500 5000 OUTDOOR COIL ROWS DEEP 3 2 FINS PER INCH 15 20 FACE AREA Sq Ft 36 0 63 8 COMPRESSOR Qty Per Unit SCROLL 2 2 AIR FILTERS QUANTITY PER U...

Page 26: ...15 TON RETURN AIR SUPPLY AIR OUTDOOR AIR OUTDOOR AIR Economizer All dimensions are in inches They are subject to change without notice Certified dimensions will be provided upon request FIGURE 7 UNIT...

Page 27: ...shipped with the bottom duct openings covered An accessory flange kit is avail able for connecting side ducts For bottom duct applications 1 Remove the side panels from the supply and return air compa...

Page 28: ...8 2 FIGURE 11 CENTER OF GRAVITY APPROXIMATE CENTER OF GRAVITY OUTDOOR COIL END OF UNIT BACK FRONT 92 125 15 TON 136 20 TON 45 15 TON 46 20 TON 60 15 TON 47 20 TON DUCT COVERS Units are shipped with t...

Page 29: ...IX POINT LOADS UNIT 4 POINT LOADS LBS TOTAL A B C D 180 2190 513 510 558 559 240 2840 495 925 925 495 NOTE These weights are with economizer and 72 kW electric heat A D C E B F A D B C UNIT 6 POINT LO...

Page 30: ...036 21490 002 A 0204 30 Unitary Products Group FIGURE 14 ROOF CURB DIMENSIONS 15 20 TON FIGURE 15 ROOF CURB BENEFITS...

Page 31: ...4 Unitary Products Group 31 FIGURE 16 UNIT AND CURB APPLICATIONS FIGURE 17 TYPICAL APPLICATIONS 15 TON FIGURE 18 TYPICAL UNIT APPLICATIONS 20 TON ROOF JACK INSTALLATION ROOF CURB INSTALLATION SLAB ON...

Page 32: ...CONTROL TERMINAL BLOCK TERMINALS ON A LIMITED NUMBER OF THERMOSTATS 3 1 2 4 3 1 2 4 Second stage heating not required on single stage heating units Second stage cooling not required on single stage c...

Page 33: ...s of 9 8 15 ton and 10 2 20 ton They shall have built in field convertible duct connections for down discharge supply return or horizontal discharge supply return and be available with factory install...

Page 34: ...y devices trip a LED light emitting diode indicator shall flash a diagnostic code that indicates which safety switch has tripped d Unit shall incorporate AUTO RESET compressor over temperature over cu...

Page 35: ...ust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation Whenever the indoor fan mo...

Page 36: ...o change without notice Printed in U S A 036 21490 002 A 0204 Copyright by Unitary Products Group 2004 All rights reserved Supersedes 036 21490 001 A 1202 Unitary 5005 Norman Products York OK Group Dr...

Reviews: