036-21490-002-A-0204
12
Unitary Products Group
EER = Energy Efficiency Ratio at full load - the cooling capacity in
BTU’s per hour (Btuh) divided by the power input expressed in BTUH
per watt (Btuh/watt).
COP = Coefficient of Performance - the total heating capacity pro-
vided by the refrigeration system, including circulating fan heat, but
excluding supplementary resistance (Btu's per hour) divided by the
total electric input (watts) x 3.412.
IPLV = Integrated part load value. The EER of the unit operating on
first stage only.
TABLE 1: RATINGS
MODEL
COOLING CAPACITY
1
80//67-95º F
1. Certified in accordance with the Unitary Large Equipment Certi-
fication Program which is based on ARI Standard 340/360.
HEATING CAPACITY
1
ELECTRIC
HEAT
NOM.
CAPACITY
2
(KW)
2. Models with electric heat have single point power supply.
47º F
17º F
MBH
EER
IPLV
MBH COP MBH COP
KW
BP180
164
9.9
9.5
172
3.2
102
2.1
18,36,54,72
BP 240
226
10.3
10.2
218
3.4
129
2.1
18,36,54,72
HEAT PUMP WITH ELECTRIC HEAT
MODEL
MBH
EER
IPLV
BP180E18
164
9.9
9.5
BP180E36
164
9.9
9.5
BP180E54
162
9.8
9.4
BP180E72
160
9.8
9.4
BP240E18
226
10.3
10.2
BP240E36
226
10.3
10.2
BP240E54
223
10.2
10.1
BP240E72
220
10.2
10.1
TABLE 2: SOUND POWER RATING
1
UNIT
SIZE
CFM
ESP
BLOWER
SOUND POWER (db 10
-12
Watts)
Octave Band Centerline Frequency (Hz)
SWL
dB(A)
dB(A)
@
10Ft.
2
IWG
RPM
BHP
63
125
250
500
1,000
2,000
4,000
8,000
BP 180
6,000
1.00
1,080
4.60
99
99
89
82
84
77
72
67
89
56
BP 240
8,000
1.00
1,120
6.65
102
102
92
85
87
80
75
70
92
59
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee
requiring a dBA value or sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.