background image

CLEARANCES

All units require certain clearances for proper operation and
service. Refer to Figure 3 for the clearances required for com-
bustion, construction, servicing and proper unit operation.

WARNING: Do not permit overhanging structures or shrubs to

obstruct the condenser air discharge outlet.

DUCT WORK

These units are adaptable to downflow use as well as rear
supply and return air duct openings. To convert to downflow,
use the following steps:

1. Remove the duct covers found in the bottom return and

supply air duct openings. There are four (4) screws secur-
ing each duct cover (save these screws to use later).

2. Install the duct covers, removed in step one, to the rear sup-

ply and return air duct openings. Secure with the four (4)
screws used in step one.

3. Seal duct covers with silicone caulk.

Downflow units must have an “L”-shaped supply duct without
any outlets or registers located below the outlet of the unit.

Duct work should be designed and sized according to the
methods of the Air Conditioning Contractors of America
(ACCA), as set forth in their Manual D.

A closed return duct system shall be used. This shall not pre-
clude use of economizers or ventilation air intake. Flexible
joints may be used in the supply and return duct work to mini-
mize the transmission of noise.

CAUTION: When fastening duct work to the side duct flanges on

the unit, insert the screws through the duct flanges only.
DO NOT insert the screws through the casing. Outdoor
duct work must be insulated and waterproofed.

NOTE: Be sure to note supply and return openings.

Refer to Figure 4 for information concerning rear and bottom
supply and return air duct openings.

FILTERS

Single phase units are shipped without a filter and is the re-
sponsibility of the installer to secure a filter in the return air
ductwork or install a Filter/Frame Kit 
(1FF0114).

A filter rack and a high velocity filters are standard on three
phase units.

Filters must always be used and must be kept clean. When
filters become dirt laden, insufficient air is delivered by the
blower, decreasing your unit's efficiency and increasing oper-
ating costs and wear-and-tear on the unit and controls.

Filters should be checked monthly especially since this unit is
used for both heating and cooling.

CONDENSATE DRAIN

A condensate trap is required to be installed in the conden-
sate drain. The plumbing must conform to local codes. Use a
sealing compound on male pipe threads. Install the conden-
sate drain line (

!

"

" NPTF) to spill into an open drain.

SERVICE ACCESS

Access to all serviceable components is provided by the follow-
ing removable panels:

Blower service access

Electrical/Filter access

Compressor service access

Refer to Figure 3 for location of these access panels and mini-
mum clearances.

THERMOSTAT

The room thermostat should be located on an inside wall ap-
proximately 56" above the floor where it will not be subject to
drafts, sun exposure or heat from electrical fixtures or appli-
ances. Follow manufacturer's instructions enclosed with the
thermostat for general installation procedure. Six color coded
insulated wires (minimum #18 AWG) should be used to con-
nect thermostat to unit. See Figure 2.

POWER AND CONTROL WIRING

Field wiring to the unit must conform to provisions of the cur-
rent N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordi-
nances. The unit must be electrically grounded in
accordance with local codes or, in their absence, with the
N.E.C./C.E.C. Voltage tolerances which must be maintained
at the compressor terminals during starting and running con-
ditions are indicated on the unit Rating Plate and Table 3.

The wiring entering the cabinet must be provided with me-
chanical strain relief.

A fused disconnect switch should be field provided for the unit. If
any of the wire supplied with the unit must be replaced, replace-
ment wire must be of the type shown on the wiring diagram.

Electrical line must be sized properly to carry the load. Each
unit must be wired with a separate branch circuit fed directly
from the meter panel and properly fused.

Refer to Figure 2 for typical field wiring and to the appropriate unit
wiring diagram for control circuit and power wiring information.

COMPRESSORS

Units are shipped with compressor mountings factory-
adjusted and ready for operation.

CAUTION: Do Not loosen compressor mounting bolts.

66297-YIM-C-0205

Unitary Products Group

3

Summary of Contents for B1HH018

Page 1: ...in the following refer ence forms 55 70 N1 General Installation 55 70 N2 Pre start Post start Check List 511 26 N1 1V Electric Heater Accessory REPLACEMENT PARTS Refer to Replacement Parts Manual for...

Page 2: ...with slings placed under the unit Spreader bars of sufficient length should be used across the top of the unit BEFORE LIFTING A UNIT MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO T...

Page 3: ...reasing oper ating costs and wear and tear on the unit and controls Filters should be checked monthly especially since this unit is used for both heating and cooling CONDENSATE DRAIN A condensate trap...

Page 4: ...AREA Sq Ft Qty Size 4 28 2 14 x 22 COMPRESSOR HERMETIC Type Qty 1 Reciprocating Reciprocating Scroll Scroll Scroll Scroll Scroll FIG 2 TYPICAL FIELD WIRING DIAGRAM POWER WIRING REFER TO ELECTRICAL DA...

Page 5: ...7 32 0 0 4 1 5 7 8 15 15 0 96 75 042 208 230 1 60 187 253 20 0 104 0 1 1 3 5 29 6 40 40 0 96 40 208 230 3 60 187 253 13 9 88 0 1 1 3 5 22 0 30 30 0 96 75 460 3 60 414 504 6 4 44 0 0 6 1 8 10 4 15 15...

Page 6: ...0 1 5 5 6 2NP04501006 2NP04501506 2NH04502006 2NP04502506 7 5 10 0 11 3 15 0 15 0 20 0 18 8 25 0 36 1 41 7 54 2 62 5 72 2 83 3 90 3 104 2 88 2 95 2 110 8 121 2 133 4 147 3 155 9 173 3 100 110 125 125...

Page 7: ...30 25 30 048 575 3 60 5 1 37 2 0 6 1 6 2NH04501058 2NH04501558 2NH04502058 2NH04502558 10 0 15 0 20 0 25 0 9 6 14 4 19 2 24 1 20 6 26 7 32 7 38 7 25 30 35 40 25 30 35 40 060 575 3 60 7 0 50 0 0 6 2 8...

Page 8: ...4 6 27 7 90 5 9 7 2 8 7 10 1 11 5 15 3 19 1 22 9 26 7 95 5 1 6 4 7 7 12 2 16 7 21 1 25 6 100 5 3 6 2 10 0 13 9 17 7 21 5 105 7 9 11 1 14 2 17 4 110 5 8 8 3 10 8 13 3 115 5 5 7 3 9 2 INDOOR DB TEMPERAT...

Page 9: ...9 0 23 8 95 7 2 12 1 17 1 22 0 100 5 9 9 9 14 0 18 0 105 7 7 10 9 14 0 110 5 5 7 8 10 1 115 6 1 TABLE 10 COOLING SUPERHEAT AT COMPRESSOR SUCTION AIRFLOW 1 000 CFM B1HH030 TABLE 11 HEATING SUPERHEAT AT...

Page 10: ...8 5 9 9 11 2 12 6 13 9 15 3 18 6 21 9 25 1 28 4 110 5 3 6 5 7 6 8 8 9 9 11 1 14 7 18 4 22 1 25 7 115 5 9 6 9 10 9 14 9 19 0 23 0 OUTDOOR TEMPERATURE F INDOOR WB TEMPERATURE F 55 57 59 61 63 65 67 69 7...

Page 11: ...14 9 20 6 26 2 31 9 75 5 8 7 2 8 6 14 2 19 9 25 5 31 1 80 5 3 6 7 8 0 13 6 19 2 24 8 30 3 85 6 1 7 4 12 9 18 5 24 0 29 6 90 5 8 10 5 15 3 20 0 24 8 95 8 2 12 1 16 1 20 0 100 6 8 10 0 13 1 16 3 105 5 5...

Page 12: ...75 volts MODEL NO BHH MOTOR SPEED EXTERNAL STATIC PRESSURE IWG 0 10 0 20 0 30 0 40 0 50 0 60 0 70 0 80 0 90 1 00 CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WAT...

Page 13: ...ues from the available external static pressure shown in the respective Blower Performance Table 2 The pressure thru the economizer is greater for 100 outdoor air then for 100 return air If the resist...

Page 14: ...LL OVERALL All dimensions are in inches They are subject to change without notice Certified dimensions will be provided upon request UNIT CONDENSATE CONNECTION NPTI TRAP REQUIRED OVERALL SIDE SUPPLY A...

Page 15: ...he fan switch is in the AUTO position the K1 relay will open and de energize the indoor blower motor after the appropriate time delay Defrost Operation The minimum time between defrosts can be field s...

Page 16: ...switch on the thermostat is in the ON position the indoor blower continues to run When the fan switch is in the AUTO position the indoor blower motor ramps down over a 15 second period Please refer to...

Page 17: ...TABLE 23 THERMOSTAT SIGNALS THREE PHASE UNITS SIGNAL STATE BOARD FUNCTION G ON FAN INSTANT ON OFF FAN INSTANT OFF G Y O ON FAN INSTANT ON COMPRESSOR AND OUTDOOR FAN INSTANT ON AFTER ANTI SHORT CYCLE...

Page 18: ...ONTROL BOARD 708 707 706 705 704 703 17B 13D 15D 14D 12D OD FAN MOTOR 1 M1 1 M1 2 L1 T2 T1 L2 BRN PRP 1 COMPR 101 BK 103 BR 102 Y RC2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25...

Page 19: ...25 KW ELEC HEAT HP HIGH PRESSURE SWITCH OPTIONAL ACCESSORY OPENS 380 PSIG K4 RELAY ELECTRIC HEATER 24 VDC COIL 15 20 25 KW ELEC HEAT HTR 1 ELECTRIC HEATER OPT ACCSSRY ALL KW ELEC HEAT HTR 2 ELECTRIC...

Page 20: ...E 10E 21B 37 36 35 34 33 32 31 30 29 28 27 129 PR 702 PR 701 Y 230V 24V ELEMENTARY DIAGRAM 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 DEF DEF T STAT 213 R 2 SPEED LTRIP ECM 2...

Page 21: ...EAT 230V COIL K7 RELAY LIMIT TRIP 24 VDC COIL TYPICAL WIRING DIAGRAM LEGEND See page 20 TYPICAL WIRING DIAGRAM NOTES See page 20 N O T E S 6 I F O P T I O N A L S A F E T Y S W I T C H K I T I S I N S...

Page 22: ...22 Unitary Products Group 66297 YIM C 0205 FIG 7 TYPICAL WIRING DIAGRAM BHH060 460 3 60 POWER SUPPLY...

Page 23: ...A R Y 5 A M P C C H C R A N K C A S E H E A T E R D S D E F R O S T S E N S O R C L O S E S 3 1 F O P E N S 5 5 D S D E F R O S T S E N S O R C L O S E S 3 1 F M 3 C O N T A C T O R O U T D O O R F A...

Page 24: ...LY HTR5 HTR5 HTR4 HTR4 HTR3 HTR3 HTR2 HTR2 M1 M1 705 PR 705 PR 708 PR 708 PR 716 PR 716 PR 713 PR 713 PR 710 PR 710 PR F6 F6 F4 F4 F2 F2 K6 K6 K4 K4 K5 K5 K3 K3 M1 M1 714 BK 714 BK 706 BK 706 BK 711 B...

Page 25: ...Unitary Products Group 25 66297 YIM C 0205 FIG 9 TYPICAL WIRING DIAGRAM 230 3 60 POWER SUPPLY...

Page 26: ...1 4 B R 8 D 7 E A B K 3 8 1 3 B R 8 1 4 Y L 2 L 2 L 2 1 2 3 H 1 L 1 L 1 L 1 K 1 2 0 9 R K 2 F A N C O N T R O L B O A R D T L H F L H 4 1 2 3 4 P 2 S 2 8 0 9 O 8 0 8 B R 2 0 4 B R S E E N O T E 8 1 1...

Page 27: ...SSRY 20 25 KW ELEC HEAT ELECTRIC HEATER OPT ACCSSRY 20 25 KW ELEC HEAT RELAY INDOOR FAN MOTOR RELAY ELECTRIC HEATER RELAY ELECTRIC HEATER 24 VDC COIL RELAY LIMIT TRIP 25 VDC COIL LOW PRESSURE SWITCH O...

Page 28: ...p 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright 2005 by York International Corporation All Rights Reserved 66297 YIM C 0205 ISO 9001 Certified Quali...

Reviews: