Unitary Products Group

19

66297-YIM-C-0205

CCH CRANKCASE HEATER (OPTIONAL)

PTCR START ASSIST (OPTIONAL DEVICE)

HTR 4

ELECTRIC HEATER (OPT. ACCSSRY: 15, 20 &25 KW ELEC HEAT)

HTR 5 & 6

ELECTRIC HEATER (OPT. ACCSSRY: 20 & 25 KW ELEC HEAT)

K5

RELAY ELECTRIC HEATER, 24 VDC COIL (25 KW ELEC HEAT)

TB2

TERMINAL BLOCK ECM MOTOR "SPEED" CONNECTIONS

K6

RELAY ELECTRIC HEATER, 24 VDC COIL (20 & 25 KW ELEC HEAT)

K7

RELAY LIMIT TRIP, 24 VDC COIL

S5/P5

SOCKET/PLUG CONNECTION ON ID FAN MOTOR, 230V

S4/P4

SOCKET/PLUG CONNECTION ON ID FAN MOTOR, 24V

S3/P3

SOCKET/PLUG CONNECTION ON FAN CONTROL BOARD, LINE VOLTAGE

S2/P2

SOCKET/PLUG CONNECTION ON FAN CONTROL BOARD, LOW VOLTAGE

LS

LIMIT SWITCH, ELECTRIC HEAT (PART OF ELEC HEAT ACCESSORY)

FACTORY WIRING AND DEVICES
OPTIONAL WIRING AND DEVICES
FIELD WIRING

TB1 ON FAN/ELEC HEAT CONTROL BOARD

ROOM THERMOSTAT 24V CONNECTIONS

IDENTIFIED TERMINAL ON RUN CAPACITOR

DS DEFROST SENSOR, CLOSES @ 31 °F, OPENS @ 55 DS DEFROST SENSOR, CLOSES @ 31 °F.

RVS

REVERSING VALVE SOLENOID

RC2

OUTDOOR FAN RUN CAPACITOR (ALTERNATE)

T1

TRANSFORMER, 24V, 40 VA

M1

CONTACTOR, COMPRESSOR & OUTDOOR FAN

LEGEND:

RC1

COMPRESSOR START CAPACITOR (ALTERNATE)

RC1/RC2

COMPRESSOR START & OUTDOOR FAN RUN CAPACITOR

K1

RELAY INDOOR FAN MOTOR

FS

FREEZESTAT SWITCH (OPTIONAL ACCESSORY) OPEN @ 26 °F

LP

LOW PRESSURE SWITCH (OPTIONAL ACCESSORY) OPEN @ 7 PSIG

K2

RELAY ELECTRIC HEATER

K3

RELAY ELECTRIC HEATER, 24 VDC COIL (7.5, 10, 15, 20 & 25 KW ELEC HEAT)

HP

HIGH PRESSURE SWITCH (OPTIONAL ACCESSORY) OPENS @ 380 PSIG

K4

RELAY ELECTRIC HEATER, 24 VDC COIL (15, 20 & 25 KW ELEC HEAT)

HTR 1

ELECTRIC HEATER (OPT. ACCSSRY: ALL KW ELEC HEAT)

HTR 2

ELECTRIC HEATER (OPT. ACCSSRY: 7.5, 10, 15, 20 & 25 KW ELEC HEAT)

HTR 3

ELECTRIC HEATER (OPT. ACCSSRY: 25 KW ELEC HEAT)

F24

FUSE 24V SECONDARY, 5 AMP

F1, F2 FUSES, LINE VOLTAGE - (5, 7.5, 10, 15, 20 & 25 KW ELEC HEAT)

FUSES, LINE VOLTAGE - (7.5, 10, 15, 20 & 25 KW ELEC HEAT)

F5, F6

F3, F4

FUSES, LINE VOLTAGE - (15, 20 & 25 KW ELEC HEAT)

COMPR COMPRESSOR

F7, F8, F9 FUSES, LINE VOLTAGE - (15, 20 & 25 KW ELEC HEAT)

TYPICAL WIRING DIAGRAM LEGEND (See page 18)

TYPICAL WIRING DIAGRAM NOTES (See page 18)

CAUTION - OPEN ALL DISCONNECTS

BEFORE SERVICING THIS UNIT

1.  ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY,
    LOCAL AND/OR NATIONAL CODES IN EFFECT AT TIME OF

    INSTALLATION OF THIS UNIT.

2.  CAUTION:  LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN
    SERVICING CONTROLS.  WIRING ERRORS CAN CAUSE IMPROPER

    AND DANGEROUS OPERATION.  IF ANY OF THE WIRE AS 

    SUPPLIED WITH THIS UNIT MUST BE REMOVED, IT MUST BE

    REPLACED WITH TYPE 105˚ C, 600V WIRE OR EQUIVALENT
    CLEARLY RENUMBERED FOR IDENTIFICATION.  VERIFY PROPER 

    OPERATION AFTER SERVICING.

3.  MOTORS ARE INHERENTLY PROTECTED.

4.  UNIT FACTORY WIRED FOR 230 VOLT OPERATION.  FOR 208 
    VOLT OPERATION MOVE '108/PR' WIRE FROM 240V TO 208V

    ON TRANSFORMER T1.

5.  SEE UNIT NAMEPLATE FOR MAXIMUM FUSE SIZE AND MINIMUM

    CIRCUIT AMPACITY.

6.  IF OPTIONAL SAFETY SWITCH KIT IS INSTALLED,

    WIRE 219/BK IS REM0VED.

7.  WIRE 204/BR IS REMOVED WHEN ELECTRIC HEAT
    IS INSTALLED.

NOTES:

8.  SHUNT CONTACT ALSO USED WITH CRANKCASE HEATER. (OPTIONAL)

Summary of Contents for B1HH018

Page 1: ...in the following refer ence forms 55 70 N1 General Installation 55 70 N2 Pre start Post start Check List 511 26 N1 1V Electric Heater Accessory REPLACEMENT PARTS Refer to Replacement Parts Manual for...

Page 2: ...with slings placed under the unit Spreader bars of sufficient length should be used across the top of the unit BEFORE LIFTING A UNIT MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO T...

Page 3: ...reasing oper ating costs and wear and tear on the unit and controls Filters should be checked monthly especially since this unit is used for both heating and cooling CONDENSATE DRAIN A condensate trap...

Page 4: ...AREA Sq Ft Qty Size 4 28 2 14 x 22 COMPRESSOR HERMETIC Type Qty 1 Reciprocating Reciprocating Scroll Scroll Scroll Scroll Scroll FIG 2 TYPICAL FIELD WIRING DIAGRAM POWER WIRING REFER TO ELECTRICAL DA...

Page 5: ...7 32 0 0 4 1 5 7 8 15 15 0 96 75 042 208 230 1 60 187 253 20 0 104 0 1 1 3 5 29 6 40 40 0 96 40 208 230 3 60 187 253 13 9 88 0 1 1 3 5 22 0 30 30 0 96 75 460 3 60 414 504 6 4 44 0 0 6 1 8 10 4 15 15...

Page 6: ...0 1 5 5 6 2NP04501006 2NP04501506 2NH04502006 2NP04502506 7 5 10 0 11 3 15 0 15 0 20 0 18 8 25 0 36 1 41 7 54 2 62 5 72 2 83 3 90 3 104 2 88 2 95 2 110 8 121 2 133 4 147 3 155 9 173 3 100 110 125 125...

Page 7: ...30 25 30 048 575 3 60 5 1 37 2 0 6 1 6 2NH04501058 2NH04501558 2NH04502058 2NH04502558 10 0 15 0 20 0 25 0 9 6 14 4 19 2 24 1 20 6 26 7 32 7 38 7 25 30 35 40 25 30 35 40 060 575 3 60 7 0 50 0 0 6 2 8...

Page 8: ...4 6 27 7 90 5 9 7 2 8 7 10 1 11 5 15 3 19 1 22 9 26 7 95 5 1 6 4 7 7 12 2 16 7 21 1 25 6 100 5 3 6 2 10 0 13 9 17 7 21 5 105 7 9 11 1 14 2 17 4 110 5 8 8 3 10 8 13 3 115 5 5 7 3 9 2 INDOOR DB TEMPERAT...

Page 9: ...9 0 23 8 95 7 2 12 1 17 1 22 0 100 5 9 9 9 14 0 18 0 105 7 7 10 9 14 0 110 5 5 7 8 10 1 115 6 1 TABLE 10 COOLING SUPERHEAT AT COMPRESSOR SUCTION AIRFLOW 1 000 CFM B1HH030 TABLE 11 HEATING SUPERHEAT AT...

Page 10: ...8 5 9 9 11 2 12 6 13 9 15 3 18 6 21 9 25 1 28 4 110 5 3 6 5 7 6 8 8 9 9 11 1 14 7 18 4 22 1 25 7 115 5 9 6 9 10 9 14 9 19 0 23 0 OUTDOOR TEMPERATURE F INDOOR WB TEMPERATURE F 55 57 59 61 63 65 67 69 7...

Page 11: ...14 9 20 6 26 2 31 9 75 5 8 7 2 8 6 14 2 19 9 25 5 31 1 80 5 3 6 7 8 0 13 6 19 2 24 8 30 3 85 6 1 7 4 12 9 18 5 24 0 29 6 90 5 8 10 5 15 3 20 0 24 8 95 8 2 12 1 16 1 20 0 100 6 8 10 0 13 1 16 3 105 5 5...

Page 12: ...75 volts MODEL NO BHH MOTOR SPEED EXTERNAL STATIC PRESSURE IWG 0 10 0 20 0 30 0 40 0 50 0 60 0 70 0 80 0 90 1 00 CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WAT...

Page 13: ...ues from the available external static pressure shown in the respective Blower Performance Table 2 The pressure thru the economizer is greater for 100 outdoor air then for 100 return air If the resist...

Page 14: ...LL OVERALL All dimensions are in inches They are subject to change without notice Certified dimensions will be provided upon request UNIT CONDENSATE CONNECTION NPTI TRAP REQUIRED OVERALL SIDE SUPPLY A...

Page 15: ...he fan switch is in the AUTO position the K1 relay will open and de energize the indoor blower motor after the appropriate time delay Defrost Operation The minimum time between defrosts can be field s...

Page 16: ...switch on the thermostat is in the ON position the indoor blower continues to run When the fan switch is in the AUTO position the indoor blower motor ramps down over a 15 second period Please refer to...

Page 17: ...TABLE 23 THERMOSTAT SIGNALS THREE PHASE UNITS SIGNAL STATE BOARD FUNCTION G ON FAN INSTANT ON OFF FAN INSTANT OFF G Y O ON FAN INSTANT ON COMPRESSOR AND OUTDOOR FAN INSTANT ON AFTER ANTI SHORT CYCLE...

Page 18: ...ONTROL BOARD 708 707 706 705 704 703 17B 13D 15D 14D 12D OD FAN MOTOR 1 M1 1 M1 2 L1 T2 T1 L2 BRN PRP 1 COMPR 101 BK 103 BR 102 Y RC2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25...

Page 19: ...25 KW ELEC HEAT HP HIGH PRESSURE SWITCH OPTIONAL ACCESSORY OPENS 380 PSIG K4 RELAY ELECTRIC HEATER 24 VDC COIL 15 20 25 KW ELEC HEAT HTR 1 ELECTRIC HEATER OPT ACCSSRY ALL KW ELEC HEAT HTR 2 ELECTRIC...

Page 20: ...E 10E 21B 37 36 35 34 33 32 31 30 29 28 27 129 PR 702 PR 701 Y 230V 24V ELEMENTARY DIAGRAM 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 DEF DEF T STAT 213 R 2 SPEED LTRIP ECM 2...

Page 21: ...EAT 230V COIL K7 RELAY LIMIT TRIP 24 VDC COIL TYPICAL WIRING DIAGRAM LEGEND See page 20 TYPICAL WIRING DIAGRAM NOTES See page 20 N O T E S 6 I F O P T I O N A L S A F E T Y S W I T C H K I T I S I N S...

Page 22: ...22 Unitary Products Group 66297 YIM C 0205 FIG 7 TYPICAL WIRING DIAGRAM BHH060 460 3 60 POWER SUPPLY...

Page 23: ...A R Y 5 A M P C C H C R A N K C A S E H E A T E R D S D E F R O S T S E N S O R C L O S E S 3 1 F O P E N S 5 5 D S D E F R O S T S E N S O R C L O S E S 3 1 F M 3 C O N T A C T O R O U T D O O R F A...

Page 24: ...LY HTR5 HTR5 HTR4 HTR4 HTR3 HTR3 HTR2 HTR2 M1 M1 705 PR 705 PR 708 PR 708 PR 716 PR 716 PR 713 PR 713 PR 710 PR 710 PR F6 F6 F4 F4 F2 F2 K6 K6 K4 K4 K5 K5 K3 K3 M1 M1 714 BK 714 BK 706 BK 706 BK 711 B...

Page 25: ...Unitary Products Group 25 66297 YIM C 0205 FIG 9 TYPICAL WIRING DIAGRAM 230 3 60 POWER SUPPLY...

Page 26: ...1 4 B R 8 D 7 E A B K 3 8 1 3 B R 8 1 4 Y L 2 L 2 L 2 1 2 3 H 1 L 1 L 1 L 1 K 1 2 0 9 R K 2 F A N C O N T R O L B O A R D T L H F L H 4 1 2 3 4 P 2 S 2 8 0 9 O 8 0 8 B R 2 0 4 B R S E E N O T E 8 1 1...

Page 27: ...SSRY 20 25 KW ELEC HEAT ELECTRIC HEATER OPT ACCSSRY 20 25 KW ELEC HEAT RELAY INDOOR FAN MOTOR RELAY ELECTRIC HEATER RELAY ELECTRIC HEATER 24 VDC COIL RELAY LIMIT TRIP 25 VDC COIL LOW PRESSURE SWITCH O...

Page 28: ...p 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright 2005 by York International Corporation All Rights Reserved 66297 YIM C 0205 ISO 9001 Certified Quali...

Reviews: