background image

5292157-UIM-B-0317

8

Johnson Controls Unitary Products

AIR FILTERS

Return air filters are required and must be field supplied. Filtration can
be accomplished external to the unit or the integral filter rack may be
used. A 1" filter access rack has been built into the unit. Remove filter
access cover shown. Install proper size filter. Standard 1" size
permanent or throw away filter may be used, or permanent washable
filters are available using model numbers: 1PF0601, 602 or 603. See
Table 5 for filter size.

.

SECTION V: COIL METERING DEVICES

This unit is supplied with a factory installed Electronic Expansion Valve
(EEV). The EEV, the temperature sensor, and the pressure transducer
are factory wired to the control board.

SECTION VI: REFRIGERANT LINE 

CONNECTION

Connect lines as follows:

1.

Suction and liquid line connections are made outside the cabinet.
Leave the tubing connection panel attached to the cabinet. Coil
access panel should be removed for brazing. The lines are
expanded to receive the field line set tubes for most outdoor unit
matches.

2.

Remove grommets where tubes exit the cabinet to prevent burning
them during brazing. In some units, the vapor line grommet may be
shipped as a loose part with the unit. Refer to Figure 10.

3.

Cut the end of the suction tube using a tube cutter. Place the tube
cutter as close as possible to the end of the tube to allow as much
depth as possible for the connection and brazing of the suction line.
To ensure suction line fits into connection, deburr the stub out
(including inner pressure protrusion from cutting).

4.

Remove the liquid line copper cap which is soft soldered onto the
outside of the 3/8” stub protruding from front of the coil cabinet tub-
ing panel as follows: 

a.

Screw a sheet metal screw into the center of the cap. 

b.

Apply a small amount of heat to the cap while pulling on the
screw using slip joint pliers.

5.

Insert liquid and suction lines into the coil connections at the coil
cabinet tubing panel.

6.

Wrap a water soaked rag around the coil connection tubes inside
the cabinet to avoid transferring excess heat to the coil, the EEV,
the temperature sensor or the pressure transducer.

7.

Purge refrigerant lines with dry nitrogen.

8.

Braze the suction and liquid lines, and allow the joints to cool.

9.

Re-attach the grommets to the lines carefully to prevent air leak-
age. In some units, the vapor line grommet may be shipped as a
loose part with the unit. Refer to Figure 10.

 CAUTION

Equipment should never be operated without filters.

 CAUTION

COIL UNDER PRESSURE.
Verify that pressure has been released by depressing schrader valve
core.

NOTICE

To prevent moisture and contaminates from entering the system, the
coil should not be open to atmosphere for extended periods of time. If
the coil cannot be brazed into the refrigeration system during a rou-
tine installation period, the ends should be temporarily closed or
plugged. For a short term delay, use masking tape over the ends of
the copper tubing to close the tube from the air. For a longer term
delay, use plugs or caps. There is no need to purge the coil if this pro-
cedure is followed.

 CAUTION

Coil is under inert gas pressure. Relieve pressure from coil by
depressing Schrader core at end of suction manifold stub out.

 CAUTION

Dry nitrogen should always be supplied through the tubing while it is
being brazed, because the temperature required is high enough to
cause oxidation of the copper unless an inert atmosphere is provided.
The flow of dry nitrogen should continue until the joint has cooled.
Always use a pressure regulator and safety valve to insure that only
low pressure dry nitrogen is introduced into the tubing. Only a small
flow is necessary to displace air and prevent oxidation.

NOTICE

Avoid handling aluminum coil components after handling the copper
line set or other tubing without first cleaning hands.

!

!

!

!

NOTICE

Route the refrigerant lines to the coil in a manner that will not obstruct
service access to the coil, air handling system, furnace flue or filter.

IMPORTANT

The electronic expansion valve (EEV) in this unit is shipped in the
closed position to protect the valve during transportation. Prior to
brazing, line power must be applied to the air handler field wiring
terminals for 1 minute. The initial power causes the EEV to open
allowing nitrogen to flow through the system during the brazing pro-
cess.

NOTICE

If power cannot be applied to the EEV control board prior to brazing
refrigeration piping, a tool is available to manually operate the EEV.
An EEV manual operating tool can be purchased from Source 1 as
part number S1-02649686000. Six revolutions of the tool open the
valve fully.

NOTICE

All indoor coil connections are copper-to-copper and should be
brazed with a phosphorous-copper alloy material such as Silfos-5 or
equivalent. DO NOT use soft solder.

Summary of Contents for AVV25B

Page 1: ...source Power Supply 208 230 1 60 20 Electrical Data For Single Source Power Supply 208 230 3 60 21 Electrical Data For Multi source Power Supply 208 230 3 60 22 Air Flow Data CFM 1 2 3 4 When operati...

Page 2: ...requirements and conform to existing national standards and safety codes In some instances these instructions exceed certain local codes and ordinances especially those who have not kept up with chan...

Page 3: ...Attachment Component Location XFW ZRUN PD EH IDVWHQHG FDXWLRXVO ZLWK VFUHZV WR WKH VLGHV DQG UHDU RI XQLW RQO 35 0 5 5 1 137 9 325 5 5 5 17 1 211 7 21 48 5 5 5 17 1 211 7 21 25 217 5 1 3 1 6 21 5 5 1...

Page 4: ...wer and verify that it is within the normal operating voltage range for the unit The accept able voltage range for these units is as follows FIGURE 4 Dimensions Duct Connection Dimensions 7 5 66 5 1 2...

Page 5: ...ulation with vinyl vapor barrier should be used AIR HANDLER CONFIGURATION These air handler units are supplied ready to be installed in an upflow or horizontal left position Refer to Figure 5 If the u...

Page 6: ...is advisable to design the duct work so that the grille is not in direct line with the opening in the unit One or two elbows and acoustical duct liner assures a quieter system Operation where return a...

Page 7: ...turbulence inside the plenum This turbulence can change the air flow patterns across the electric heater limit switches If the factory suggested transition cannot be fabricated it is recommended that...

Page 8: ...lly to prevent air leak age In some units the vapor line grommet may be shipped as a loose part with the unit Refer to Figure 10 CAUTION Equipment should never be operated without filters CAUTION COIL...

Page 9: ...be plugged Instruct the owner that the evaporator coil drain pan should be inspected and cleaned regularly to prevent odors and assure proper drainage If a secondary drain is not used it must be plugg...

Page 10: ...t connection of aluminum wiring to air handlers is not approved If aluminum conductors are present all applicable local and national codes must be followed when converting from aluminum to copper cond...

Page 11: ...ted hole and keep low voltage wiring as short as possible To further minimize air leakage seal the wiring entry point at the out side of the unit The field wiring is to be connected with wire connecto...

Page 12: ...C 24 VAC System Common Pin 2 3 R 24 VAC System Power Pin 3 4 A RS 485 Input Pin 4 5 PR1 5V VCC Pressure Transducer Indoor Pressure Transducer Pin 1 6 PR1 0 5 4 5V Pressure Transducer Signal Pin 2 7 P...

Page 13: ...jumper to be changed from NO to YES 3 Set the MODE jumper to A C Air Conditioner or HP Heat Pump position depending on the outdoor unit included with the system 4 Set HEAT airflow jumper to proper po...

Page 14: ...is connected to the heater relays using pins 4 5 and 6 of connector P1 The relay outputs are 24 VAC The control energizes the heat relays as shown in Table 4 Depending on the heat kit installed in th...

Page 15: ...wer in conjunc tion with the outdoor unit compressor speed To Set Heat Pump Airflow The modulating outdoor AC or HP operate the indoor blower in conjunc tion with the outdoor unit compressor speed To...

Page 16: ...Refer to the latest edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing TABLE 7 Electrical Heat Minimum Fan Speed Heater K...

Page 17: ...HK46502025 19 2 14 4 17 6 49 2 60 2 7 2 8 8 14 4 17 6 6HK46502525 24 18 22 61 5 75 2 9 11 18 22 1 0 1 0 no service disconnect OR 1 with service disconnect 2 1 2 1 with service disconnect no breaker ju...

Page 18: ...3 128 3 125 150 AVV50C 6HK 0 1 6500206 10 9 1 8 8 25 25 6HK 0 1 6500506 20 9 1 8 8 35 35 6HK 0 1 6500806 32 9 1 8 8 45 50 6HK 0 1 6501006 40 9 1 8 8 60 60 6HK 1 2 6501306 52 9 1 8 8 70 80 6HK 1 2 650...

Page 19: ...ybe 0 no service disconnect or 1 with service disconnect 2 1 2 maybe 1 with service disconnect no breaker jumper bar or 2 with service disconnect breaker jumper bar 3 MOP Maximum Overcurrent Protectio...

Page 20: ...5 41 5 30 40 30 45 6HK16501506 60 30 8 43 3 32 7 47 9 35 45 35 50 6HK16501806 72 48 1 39 0 51 9 43 1 50 40 60 45 6HK16502006 80 52 5 43 3 56 7 47 9 60 45 60 50 6HK16502506 100 52 5 43 3 21 7 56 7 47 9...

Page 21: ...3 55 5 55 60 6HK465020253 46 2 56 3 61 0 60 70 37C 6HK36501025 23 1 31 3 33 3 35 35 6HK36501525 34 6 43 7 47 1 45 50 6HK36501825 41 6 51 3 55 5 55 60 6HK465020253 46 2 56 3 61 0 60 70 38B TBD TBD TBD...

Page 22: ...eat Tap2 AVV25B AVV37B AVV37C AVV38B AVV38C AVV49C High Low High Low High Low High Low High Low High Low A 1225 1020 1225 1020 1425 1150 TBD TBD 1430 1200 1650 1200 B 1150 950 1150 950 1150 1000 TBD T...

Page 23: ...y drain SECTION XV AIR SYSTEM ADJUSTMENT To check the Cubic Feet per Minute CFM measure the external duct static using a manometer and static pressure tips To prepare coil for static pressure drop mea...

Page 24: ...p sheet showing the critical readings of the unit at the time of commissioning must be uploaded as part of the online registration process FIGURE 18 Drain Traps 3 MINIMUM HANDMADE TRAP PREMADE TRAPS S...

Page 25: ...5292157 UIM B 0317 Johnson Controls Unitary Products 25 SECTION XVIII WIRING DIAGRAM FIGURE 20 Wiring Diagram ECM Single Phase Heat Kits Sheet 1 of 2 6KHHW RI...

Page 26: ...5292157 UIM B 0317 26 Johnson Controls Unitary Products FIGURE 21 Wiring Diagram ECM Single Phase Heat Kits Sheet 2 of 2 6KHHW RI...

Page 27: ...N BLUE BLUE BLUE BLUE YELLOW YELLOW BLACK BLACK YELLOW YELLOW BLACK BLACK RED WHITE BLACK BLUE BLACK BLUE YELLOW BLACK YELLOW YELLOW BLUE BLACK BLUE BLACK YELLOW RLY 1 RLY 2 RLY 3 RLY 6 RLY 5 RLY 4 HE...

Page 28: ...5292157 UIM B 0317 28 Johnson Controls Unitary Products NOTES...

Page 29: ...dry bulb temperature Return air dry bulb temperature Temperature drop 1 2 3 4 5 Low Medium Low Medium Medium High High A B C D Outside air dry bulb temperature Return air wet bulb temperature Supply a...

Page 30: ...oting and correcting any problems Operate the unit through cooling cycles from the thermostat noting and correcting any problems Operate the unit through mechanical heating cycles from the thermostat...

Reviews: