Johnson Controls Unitary Products
TABLE 11:
Electrical Data For Multi-source Power Supply: 208/230-1-60
Air Handlers Models
Heater Models
1,2
Heater Amps @240V
Min. Circuit Ampacity
MOP
3
208V
230V
208V
230V
Circuit
Circuit
1st
3
2nd
3rd
1st
3
2nd
3rd
1st
3
2nd
3rd
1st
3
2nd
3rd
25B
6HK16501306
52
25.0 37.6
–
26.4 41.5
–
25
40
–
30
45
–
6HK16501506
60
27.9 43.3
–
29.6 47.9
–
30
45
–
30
50
–
6HK16501806
72
45.3 39.0
–
48.8 43.1
–
50
40
–
50
45
–
6HK16502006
80
49.6 43.3
–
53.5 47.9
–
50
45
–
60
50
–
37B
6HK16501306
52
25.0 37.6
–
26.4 41.5
–
25
40
–
30
45
–
6HK16501506
60
27.9 43.3
–
29.6 47.9
–
30
45
–
30
50
–
6HK16501806
72
45.3 39.0
–
48.8 43.1
–
50
40
–
50
45
–
6HK16502006
80
49.6 43.3
–
53.5 47.9
–
50
45
–
60
50
–
37C
6HK16501306
52
25.0 37.6
–
26.4 41.5
–
25
40
–
30
45
–
6HK16501506
60
27.9 43.3
–
29.6 47.9
–
30
45
–
30
50
–
6HK16501806
72
45.3 39.0
–
48.8 43.1
–
50
40
–
50
45
–
6HK16502006
80
49.6 43.3
–
53.5 47.9
–
50
45
–
60
50
–
38B
TBD
TBD
TBD TBD TBD TBD TBD TBD TBD TBD TBD TBD TBD TBD
38C
6HK16501306
52
25.0 37.6
–
26.4 41.5
–
25
40
–
30
45
–
6HK16501506
60
27.9 43.3
–
29.6 47.9
–
30
45
–
30
50
–
6HK16501806
72
45.3 39.0
–
48.8 43.1
–
50
40
–
50
45
–
6HK16502006
80
49.6 43.3
–
53.5 47.9
–
50
45
–
60
50
–
49C
6HK16501306
52
27.9 37.6
–
29.5 41.5
–
30
40
–
30
45
–
6HK16501506
60
30.8 43.3
–
32.7 47.9
–
35
45
–
35
50
–
6HK16501806
72
48.1 39.0
–
51.9 43.1
–
50
40
–
60
45
–
6HK16502006
80
52.5 43.3
–
56.7 47.9
–
60
45
–
60
50
–
49D
6HK16501306
52
27.9 37.6
–
29.5 41.5
–
30
40
–
30
45
–
6HK16501506
60
30.8 43.3
–
32.7 47.9
–
35
45
–
35
50
–
6HK16501806
72
48.1 39.0
–
51.9 43.1
–
50
40
–
60
45
–
6HK16502006
80
52.5 43.3
–
56.7 47.9
–
60
45
–
60
50
–
6HK16502506
100
52.5 43.3 21.7 56.7 47.9 24.0
60
45
25
60
50
25
50C
6HK16501306
52
27.9 37.6
–
29.5 41.5
–
30
40
–
30
45
–
6HK16501506
60
30.8 43.3
–
32.7 47.9
–
35
45
–
35
50
–
6HK16501806
72
48.1 39.0
–
51.9 43.1
–
50
40
–
60
45
–
6HK16502006
80
52.5 43.3
–
56.7 47.9
–
60
45
–
60
50
–
50D
6HK16501306
52
27.9 37.6
–
29.5 41.5
–
30
40
–
30
45
–
6HK16501506
60
30.8 43.3
–
32.7 47.9
–
35
45
–
35
50
–
6HK16501806
72
48.1 39.0
–
51.9 43.1
–
50
40
–
60
45
–
6HK16502006
80
52.5 43.3
–
56.7 47.9
–
60
45
–
60
50
–
6HK16502506
100
52.5 43.3 21.7 56.7 47.9 24.0
60
45
25
60
50
25
61C
6HK16501306
52
27.9 37.6
–
29.5 41.5
–
30
40
–
30
45
–
6HK16501506
60
30.8 43.3
–
32.7 47.9
–
35
45
–
35
50
–
6HK16501806
72
48.1 39.0
–
51.9 43.1
–
50
40
–
60
45
–
6HK16502006
80
52.5 43.3
–
56.7 47.9
–
60
45
–
60
50
–
61D
6HK16501306
52
27.9 37.6
–
29.5 41.5
–
30
40
–
30
45
–
6HK16501506
60
30.8 43.3
–
32.7 47.9
–
35
45
–
35
50
–
6HK16501806
72
48.1 39.0
–
51.9 43.1
–
50
40
–
60
45
–
6HK16502006
80
52.5 43.3
–
56.7 47.9
–
60
45
–
60
50
–
6HK16502506
100
52.5 43.3 21.7 56.7 47.9 24.0
60
45
25
60
50
25
NOTES:
1. (0,1) - maybe 0 (no service disconnect) or 1 (with service disconnect).
2. (1,2) maybe 1 (with service disconnect, no breaker jumper bar) or 2 (with service disconnect & breaker jumper bar).
3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. Refer to the latest edition of the National Electric Code or
in Canada the Canadian electrical Code and local codes to determine correct wire sizing.