280241-YIM-D-0909

Johnson Controls Unitary Products

5

INSTALLATION

LIMITATIONS

These units must be installed in accordance with the follow-
ing national and local safety codes.

1.

National Electrical Code ANSI/NFPS No. 70 or Canadian 
Electrical Code Part 1, C22.1 (latest editions).

2.

National Fuel Gas Code Z223.1 or CSA B149.1 Installa-
tion Code.

3.

Local gas utility requirements.

4.

Local plumbing and waste water codes and other appli-
cable local codes.

Refer to Table 1 for unit application data and to Tables 3 thru 
6 for gas heat application data.

If components are to be added to a unit to meet local codes, 
they are to be installed at the dealer's and/or the customer's 
expense.

Size of unit for proposed installation should be based on heat 
loss/heat gain calculations made in accordance with industry 
recognized procedures identified by the Air Conditioning 
Contractors of America.

LOCATION

Use the following guidelines to select a suitable location for 
these units.

1.

Unit is designed for outdoor installation only.

2.

Condenser must have an unlimited supply of air. Where 
a choice of location is possible, position unit on either 
north or east side of building.

FIGURE 1 -  PRODUCT NOMENCLATURE

D

1

N

P

N

PRODUCT CATEGORY

3

0

6

0

6

3

0

6

VOLTAGE CODE

06 = 208/230-1-60
25 = 208/230-3-60
46 = 460-3-60

024 = 24,000 BTUH

042 = 42,000 BTUH

030 = 30,000 BTUH

048 = 48,000 BTUH
060 = 60,000 BTUH

036 = 36,000 BTUH

58 = 575-3-60

D = Single Package Air Conditioner 

PRODUCT IDENTIFIER

NP = 13 SEER Gas Heat/Electric 

NOMINAL COOLING

CAPACITY (MBH)

N = Single Stage
D = Two Stage 

FACTORY INSTALLED

NATURAL GAS HEAT

036 = 36,000 BTUH
056 = 56,000 BTUH (36,400 BTUH)
065 = 65,000 BTUH
072 = 72,000 BTUH (46,800 BTUH)
090 = 90,000 BTUH (56,160 BTUH)
110 = 110,000 BTUH (70,200 BTUH)

NOMINAL HIGH GAS HEAT OUTPUT CAPACITY

(NOMINAL LOW GAS HEAT OUTPUT CAPACITY)

PRODUCT GENERATION

1 = 1st Generation
2 = 2nd Generation
3 = 3rd Generation 

TABLE 1: UNIT APPLICATION DATA

Voltage Variation

Min. / Max.

1

1. Rated in accordance with ARI Standard 110, utilization 

range “A”.

208/230V

2

2. “T1” transformer primary tap must be moved from the 

230 volt connection to the 208 volt connection for low 
voltage applications of 208 volt and below

187 / 252

460V

432 / 504

575V

540 / 630

Wet Bulb Temperature (°F) of Air on

Evaporator Coil,  Min. / Max.

57 / 72

Dry Bulb Temperature (°F) of Air on

Condenser Coil, Min.

3

 / Max.

3. A low ambient accessory is available for operation 

down to 0 °F.

45 / 120

Excessive exposure of this furnace to contami-
nated combustion air may result in equipment 
damage or personal injury. Typical contaminates 
include: permanent wave solution, chlorinated 
washes and cleaners, chlorine based swimming 
pool chemicals, water softening chemicals, carbon 
tetrachloride, halogen type refrigerants, cleaning 
solvents (e.g. perchloroethylene), printing inks, 
paint removers, varnishes, hydrochloric acid, 
cements and glues, antistatic fabric softeners for 
clothes dryers, masonry acid washing materials.

Summary of Contents for AFFINITY SERIES

Page 1: ...are intended to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert installer that personal injury and or equipment damage may result if...

Page 2: ...ITION TRIAL PERIOD 17 PILOT FLAME STABILIZATION PERIOD 17 HEAT BLOWER ON DELAY 17 MAIN BURNER OPERATION 17 POST PURGE 18 HEAT BLOWER OFF DELAY 18 LOCKOUT 18 HIGH TEMPERATURE LIMIT SWITCH 18 ROLLOUT SW...

Page 3: ...060 SINGLE STAGE 208 230 1 60 POWER SUPPLY 27 23 TYPICAL WIRING DIAGRAM D NP 060 TWO STAGE 208 230 1 60 POWER SUPPLY 28 24 TYPICAL WIRING DIAGRAM D NP 030 048 SINGLE STAGE GAS HEAT 208 230 3 60 POWER...

Page 4: ...easier CAUTIONS are given to prevent equipment damage WARNINGS are given to alert the installer that personal injury and or equipment damage may result if installation procedure is not handled proper...

Page 5: ...48 000 BTUH 060 60 000 BTUH 036 36 000 BTUH 58 575 3 60 D Single Package Air Conditioner PRODUCT IDENTIFIER NP 13 SEER Gas Heat Electric NOMINAL COOLING CAPACITY MBH N Single Stage D Two Stage FACTOR...

Page 6: ...ngs in the skid are provided for this purpose Forks must pass completely through the base Refer to Table 2 for unit weights and to Figure 2 for approxi mate center of gravity DUCT WORK These units are...

Page 7: ...ccess to all serviceable components is provided by the fol lowing removable panels Blower compartment Gas control electrical service access Refer to Figure 10 for location of these access panels and m...

Page 8: ...HERMOSTAT ONLY Minimum wire size of 18 AWG wire should be used for all field installed 24 volt wire THERMOSTAT UNIT TERMINAL STRIP NOTE HEAT ANTICIPATOR SHOULD BE SET AT 0 35 AMPS FOR ALL MODELS 24 VO...

Page 9: ...TERMINAL STRIP NOTE HEAT ANTICIPATOR SHOULD BE SET AT 0 35 AMPS FOR ALL MODELS 24 VOLT TRANSFORMER C 2 1 C PROGRAMMABLE THERMOSTAT ONLY 1 2 1 W2 FIGURE 6 TYPICAL FIELD POWER WIRING DIAGRAM G R O U N...

Page 10: ...0 feet above sea level 2 Based on 1075 BTU Ft 3 3 The air flow must be adequate to obtain a temperature rise within the range shown Continuous return air temperature should not be below 55 F TABLE 4 N...

Page 11: ...to obtain a temperature rise within the range shown Continuous return air temperatures should not be below 55 F TABLE 6 PROPANE1 GAS APPLICATION DATA TWO STAGE AVAILABLE ON MODELS INPUT MBH 2 HIGH FI...

Page 12: ...by local codes a manual shut off valve may have to be installed outside of the unit 3 Use wrought iron or steel pipe for all gas lines Pipe dope should be applied sparingly to male threads only FIGUR...

Page 13: ...be fastened to the outside of the side gas control electri cal compartment with the screws provided in the bag attached to the inside of the gas control electrical compart ment see Figure 9 If flexib...

Page 14: ...OMPRESSOR COND FAN MOTOR FLA SUPPLY AIR BLOWER MOTOR FLA MINIMUM CIRCUIT AMPACITY MAX FUSE SIZE AMPS2 MAX HACR BREAKER SIZE AMPS UNIT POWER FACTOR TRANSFORMER SIZE VA MIN MAX RLA LRA 024 208 230 1 60...

Page 15: ...GAS ELECTRIC CONTROL SERVICE ACCESS COMPARTMENT PANEL OVERALL OVERALL TABLE 11 UNIT DIMENSIONS FRONT UNIT SIZE DIMENSION A B 024 030 036 33 1 2 18 1 4 042 048 060 41 1 2 23 1 8 TABLE 12 UNIT MINIMUM C...

Page 16: ...ONT CONDENSATE DRAIN 3 4 NPTF GAS SUPPLY 1 5 8 DIA KNOCKOUT 1 2 NPTF CONNECTION LOW VOLTAGE CONN DIA KNOCKOUT 8 7 1 3 4 1 5 2 9 9 1 6 1 5 3 1 2 1 3 4 1 3 4 1 5 4 1 4 1 2 3 1 2 3 3 8 1 4 1 2 2 8 3 8 1...

Page 17: ...ge period before de energizing If the pressure switch is lost during an ignition trial period the control immediately de energizes spark and gas The control begins pressure switch proving before an in...

Page 18: ...lve and flash 7 on the LED The blower output will be energized during an open rollout condition If the rollout switch closes the control shall remain locked out until power removed or W is removed Rol...

Page 19: ...for COOL occurs the circulating fan continues to run at the cool speed If a call for HEAT occurs the circulating fan switches to heat speed after a 30 second delay When the thermostat ends the call f...

Page 20: ...hould the standby gas line pressure exceed 13 5 nor the operating pressure drop below 4 5 for natural gas units If gas pressure is outside these limits contact the local gas utility for corrective act...

Page 21: ...3 8 of the end of the flame sensor and not contain any yellow color see Fig ure 17 4 Replace the pilot adjustment cover screw after the pilot flame is set To check adjust or remove the pilot assembly...

Page 22: ...your particular locality Contact your gas company for this information since it varies widely from city to city TABLE 14 GAS RATE CUBIC FEET PER HOUR1 SECONDS FOR ONE REV SIZE OF TEST DIAL 1 2 CU FT...

Page 23: ...280241 YIM D 0909 Johnson Controls Unitary Products 23 FIGURE 18 TYPICAL WIRING DIAGRAM D NP 024 SINGLE STAGE GAS HEAT 208 230 1 60 POWER SUPPLY...

Page 24: ...280241 YIM D 0909 24 Johnson Controls Unitary Products FIGURE 19 TYPICAL WIRING DIAGRAM D NP 024 TWO STAGE GAS HEAT 208 230 1 60 POWER SUPPLY...

Page 25: ...280241 YIM D 0909 Johnson Controls Unitary Products 25 FIGURE 20 TYPICAL WIRING DIAGRAM D NP 030 048 SINGLE STAGE GAS HEAT 208 230 1 60 POWER SUPPLY...

Page 26: ...280241 YIM D 0909 26 Johnson Controls Unitary Products FIGURE 21 TYPICAL WIRING DIAGRAM D NP 030 048 TWO STAGE GAS HEAT 208 230 1 60 POWER SUPPLY...

Page 27: ...280241 YIM D 0909 Johnson Controls Unitary Products 27 FIGURE 22 TYPICAL WIRING DIAGRAM D NP 060 SINGLE STAGE 208 230 1 60 POWER SUPPLY...

Page 28: ...280241 YIM D 0909 28 Johnson Controls Unitary Products FIGURE 23 TYPICAL WIRING DIAGRAM D NP 060 TWO STAGE 208 230 1 60 POWER SUPPLY...

Page 29: ...280241 YIM D 0909 Johnson Controls Unitary Products 29 FIGURE 24 TYPICAL WIRING DIAGRAM D NP 030 048 SINGLE STAGE GAS HEAT 208 230 3 60 POWER SUPPLY...

Page 30: ...280241 YIM D 0909 30 Johnson Controls Unitary Products FIGURE 25 TYPICAL WIRING DIAGRAM D NP 030 048 TWO STAGE GAS HEAT 208 230 3 60 POWER SUPPLY...

Page 31: ...280241 YIM D 0909 Johnson Controls Unitary Products 31 FIGURE 26 TYPICAL WIRING DIAGRAM D NP 060 SINGLE STAGE GAS HEAT 208 230 3 60 POWER SUPPLY...

Page 32: ...280241 YIM D 0909 32 Johnson Controls Unitary Products FIGURE 27 TYPICAL WIRING DIAGRAM D NP 060 TWO STAGE GAS HEAT 208 230 3 60 POWER SUPPLY...

Page 33: ...280241 YIM D 0909 Johnson Controls Unitary Products 33 FIGURE 28 TYPICAL WIRING DIAGRAM D NP 030 048 SINGLE STAGE GAS HEAT 460 575 3 60 POWER SUPPLY...

Page 34: ...280241 YIM D 0909 34 Johnson Controls Unitary Products FIGURE 29 TYPICAL WIRING DIAGRAM D NP 030 048 TWO STAGE GAS HEAT 460 575 3 60 POWER SUPPLY...

Page 35: ...280241 YIM D 0909 Johnson Controls Unitary Products 35 FIGURE 30 TYPICAL WIRING DIAGRAM D NP 060 SINGLE STAGE GAS HEAT 460 575 3 60 POWER SUPPLY...

Page 36: ...280241 YIM D 0909 36 Johnson Controls Unitary Products FIGURE 31 TYPICAL WIRING DIAGRAM D NP 060 TWO STAGE GAS HEAT 460 575 3 60 POWER SUPPLY...

Page 37: ...sent wire 801 BL and 805 BL are connected to M1 coil If only ASCT is present wire 202 Y is connected to ASCT 3 If neither LR or ASCT are present wire 202 Y is connected to M1coil as shown 7 Removed 8...

Page 38: ...280241 YIM D 0909 38 Johnson Controls Unitary Products...

Page 39: ...280241 YIM D 0909 Johnson Controls Unitary Products 39...

Page 40: ...o change without notice Printed in U S A 280241 YIM D 0909 Copyright 2009 by Johnson Controls All rights reserved Supersedes 280241 YIM C 1108 Johnson Controls Unitary Products 5005 York Drive Norman...

Reviews: