The control recognizes a call for 2nd stage heat when W2 is 
energized (connected to "R"). The control energizes the high 
gas output and induced draft motor on high speed.

If the call for 2nd stage heat goes away and the 1st stage call 
remains, the control de energizes the high gas valve, drops 
inducer speed to low, and returns to low heat operation.

Response to loss of W1, low pressure switch, and flame are 
identical to low heat operation.

POST PURGE

The control board runs the induced draft motor for a 30 sec-
ond post-purge period, and then de-energizes the inducer. If 
a call for heat occurs during post-purge, the control finishes 
the post-purge, drops inducer out to re-prove open pressure 
switch before continuing with the heat cycle.

HEAT BLOWER OFF DELAY

The control board de-energizes the indoor blower motor after 
a delay time as selected by movable shunt (60, 90, 120 or 
180 seconds). Blower timing begins when the thermostat is 
satisfied or heat cycle was interrupted. The control returns to 
standby when the blower off delay is complete.

If the thermostat call for heat returns before the blower off 
delay is complete, the control begins an ignition sequence 
with pre-purge while the blower off delay continues.

LOCKOUT

While in lockout, the control board keeps the pilot gas valve, 
main gas valve and induced draft motor de-energized.

Lockouts due to failed ignition or flame losses may be reset 
by removing the call for heat (W1) for more than 1 second, 
but less than 20 seconds, or by removing power from the 
control for over 0.25 seconds. The control will automatically 
reset lockout after 60 minutes.

Lockouts due to detected internal control faults will reset after 
60 minutes or power interruption.

HIGH TEMPERATURE LIMIT SWITCH

Any time the high temperature limit switch is open the control 
board will run the indoor blower motor on heat speed, the 
inducer (on high speed for 2 stage models), de-energize the 
gas valve, and flash "6" on the LED. When the high tempera-
ture switch closes, the control will restart the ignition 
sequence beginning with pre-purge.

ROLLOUT SWITCH

If the rollout switch opens for more than 0.25 seconds, the 
control board will run the inducer (on high speed for 2 stage 
models) for a post-purge period, immediately de-energize the 
gas valve, and flash "7" on the LED. The blower output will be 
energized during an open rollout condition.

If the rollout switch closes, the control shall remain locked out 
until power removed or "W" is removed. 

Rollout switch lockout shall not reset automatically.

POWER INTERRUPTIONS

Power interruptions of any duration shall not cause lockout or 
any operation requiring manual intervention.

FLAME PRESENT WITH GAS OFF

If flame is sensed for longer than 4.0 seconds during a period 
when the gas valve should be closed, the control will enter 
lockout flashing "8" on the LED. The control will turn on the 
inducer blower while the flame is present.

Gas Valve Stuck Open or Closed

If either or both Pilot and Main Gas valve outputs are sensed 
to be off for more than 1 second when commanded to be on, 
the control board shuts off all outputs and enters a hard 
lockout flashing "9" on the LED.

If the Pilot valve or Main valve output is sensed to be 
energized for more than 1 second when commanded to be 
off, the control de-energizes the induced draft motor (if flame 
is not present) to attempt to open the pressure switch to de-
energize the gas valve. If the pilot or main gas valve is still 
sensed as energized after the inducer has been off for 5 
seconds, the control re-energizes the inducer to attempt to 
vent the unburned gas. In either case, the control enters a 
hard lockout flashing "9" on the LED. If the pilot or main valve 
becomes Un-Welded the inducer will de-energize, but the 
control will remain in a hard lockout and not respond to any 
thermostat demands.

The only way to recover from a hard lockout is to remove and 
then reapply 24VAC power to the control board.

Flame Sense Circuit Failure

If the control detects an internal hardware failure in the flame 
sense circuit, it shuts off all outputs and enters a hard lockout 
flashing "10" on the LED. The control will not respond to 
thermostat demands during a hard lockout. 

The only way to recover from a hard lockout is to remove and 
then reapply 24VAC power to the control.  If problem persist 
after removal and reapplication of 24VAC power, the board 
may need to be replaced.

SAFETY CONTROLS 

The control circuit includes the following safety controls:

1.

Limit Switch (LS)

 - This control is located inside the 

heat exchanger compartment and is set to open at the 
temperature indicated in the Temperature Controls Table 
of the unit wiring diagram. It resets automatically. The 
limit switch operates when a high temperature condition 
caused by inadequate supply air flow occurs, thus shut-

Summary of Contents for AFFINITY SERIES

Page 1: ...are intended to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert installer that personal injury and or equipment damage may result if...

Page 2: ...ITION TRIAL PERIOD 17 PILOT FLAME STABILIZATION PERIOD 17 HEAT BLOWER ON DELAY 17 MAIN BURNER OPERATION 17 POST PURGE 18 HEAT BLOWER OFF DELAY 18 LOCKOUT 18 HIGH TEMPERATURE LIMIT SWITCH 18 ROLLOUT SW...

Page 3: ...060 SINGLE STAGE 208 230 1 60 POWER SUPPLY 27 23 TYPICAL WIRING DIAGRAM D NP 060 TWO STAGE 208 230 1 60 POWER SUPPLY 28 24 TYPICAL WIRING DIAGRAM D NP 030 048 SINGLE STAGE GAS HEAT 208 230 3 60 POWER...

Page 4: ...easier CAUTIONS are given to prevent equipment damage WARNINGS are given to alert the installer that personal injury and or equipment damage may result if installation procedure is not handled proper...

Page 5: ...48 000 BTUH 060 60 000 BTUH 036 36 000 BTUH 58 575 3 60 D Single Package Air Conditioner PRODUCT IDENTIFIER NP 13 SEER Gas Heat Electric NOMINAL COOLING CAPACITY MBH N Single Stage D Two Stage FACTOR...

Page 6: ...ngs in the skid are provided for this purpose Forks must pass completely through the base Refer to Table 2 for unit weights and to Figure 2 for approxi mate center of gravity DUCT WORK These units are...

Page 7: ...ccess to all serviceable components is provided by the fol lowing removable panels Blower compartment Gas control electrical service access Refer to Figure 10 for location of these access panels and m...

Page 8: ...HERMOSTAT ONLY Minimum wire size of 18 AWG wire should be used for all field installed 24 volt wire THERMOSTAT UNIT TERMINAL STRIP NOTE HEAT ANTICIPATOR SHOULD BE SET AT 0 35 AMPS FOR ALL MODELS 24 VO...

Page 9: ...TERMINAL STRIP NOTE HEAT ANTICIPATOR SHOULD BE SET AT 0 35 AMPS FOR ALL MODELS 24 VOLT TRANSFORMER C 2 1 C PROGRAMMABLE THERMOSTAT ONLY 1 2 1 W2 FIGURE 6 TYPICAL FIELD POWER WIRING DIAGRAM G R O U N...

Page 10: ...0 feet above sea level 2 Based on 1075 BTU Ft 3 3 The air flow must be adequate to obtain a temperature rise within the range shown Continuous return air temperature should not be below 55 F TABLE 4 N...

Page 11: ...to obtain a temperature rise within the range shown Continuous return air temperatures should not be below 55 F TABLE 6 PROPANE1 GAS APPLICATION DATA TWO STAGE AVAILABLE ON MODELS INPUT MBH 2 HIGH FI...

Page 12: ...by local codes a manual shut off valve may have to be installed outside of the unit 3 Use wrought iron or steel pipe for all gas lines Pipe dope should be applied sparingly to male threads only FIGUR...

Page 13: ...be fastened to the outside of the side gas control electri cal compartment with the screws provided in the bag attached to the inside of the gas control electrical compart ment see Figure 9 If flexib...

Page 14: ...OMPRESSOR COND FAN MOTOR FLA SUPPLY AIR BLOWER MOTOR FLA MINIMUM CIRCUIT AMPACITY MAX FUSE SIZE AMPS2 MAX HACR BREAKER SIZE AMPS UNIT POWER FACTOR TRANSFORMER SIZE VA MIN MAX RLA LRA 024 208 230 1 60...

Page 15: ...GAS ELECTRIC CONTROL SERVICE ACCESS COMPARTMENT PANEL OVERALL OVERALL TABLE 11 UNIT DIMENSIONS FRONT UNIT SIZE DIMENSION A B 024 030 036 33 1 2 18 1 4 042 048 060 41 1 2 23 1 8 TABLE 12 UNIT MINIMUM C...

Page 16: ...ONT CONDENSATE DRAIN 3 4 NPTF GAS SUPPLY 1 5 8 DIA KNOCKOUT 1 2 NPTF CONNECTION LOW VOLTAGE CONN DIA KNOCKOUT 8 7 1 3 4 1 5 2 9 9 1 6 1 5 3 1 2 1 3 4 1 3 4 1 5 4 1 4 1 2 3 1 2 3 3 8 1 4 1 2 2 8 3 8 1...

Page 17: ...ge period before de energizing If the pressure switch is lost during an ignition trial period the control immediately de energizes spark and gas The control begins pressure switch proving before an in...

Page 18: ...lve and flash 7 on the LED The blower output will be energized during an open rollout condition If the rollout switch closes the control shall remain locked out until power removed or W is removed Rol...

Page 19: ...for COOL occurs the circulating fan continues to run at the cool speed If a call for HEAT occurs the circulating fan switches to heat speed after a 30 second delay When the thermostat ends the call f...

Page 20: ...hould the standby gas line pressure exceed 13 5 nor the operating pressure drop below 4 5 for natural gas units If gas pressure is outside these limits contact the local gas utility for corrective act...

Page 21: ...3 8 of the end of the flame sensor and not contain any yellow color see Fig ure 17 4 Replace the pilot adjustment cover screw after the pilot flame is set To check adjust or remove the pilot assembly...

Page 22: ...your particular locality Contact your gas company for this information since it varies widely from city to city TABLE 14 GAS RATE CUBIC FEET PER HOUR1 SECONDS FOR ONE REV SIZE OF TEST DIAL 1 2 CU FT...

Page 23: ...280241 YIM D 0909 Johnson Controls Unitary Products 23 FIGURE 18 TYPICAL WIRING DIAGRAM D NP 024 SINGLE STAGE GAS HEAT 208 230 1 60 POWER SUPPLY...

Page 24: ...280241 YIM D 0909 24 Johnson Controls Unitary Products FIGURE 19 TYPICAL WIRING DIAGRAM D NP 024 TWO STAGE GAS HEAT 208 230 1 60 POWER SUPPLY...

Page 25: ...280241 YIM D 0909 Johnson Controls Unitary Products 25 FIGURE 20 TYPICAL WIRING DIAGRAM D NP 030 048 SINGLE STAGE GAS HEAT 208 230 1 60 POWER SUPPLY...

Page 26: ...280241 YIM D 0909 26 Johnson Controls Unitary Products FIGURE 21 TYPICAL WIRING DIAGRAM D NP 030 048 TWO STAGE GAS HEAT 208 230 1 60 POWER SUPPLY...

Page 27: ...280241 YIM D 0909 Johnson Controls Unitary Products 27 FIGURE 22 TYPICAL WIRING DIAGRAM D NP 060 SINGLE STAGE 208 230 1 60 POWER SUPPLY...

Page 28: ...280241 YIM D 0909 28 Johnson Controls Unitary Products FIGURE 23 TYPICAL WIRING DIAGRAM D NP 060 TWO STAGE 208 230 1 60 POWER SUPPLY...

Page 29: ...280241 YIM D 0909 Johnson Controls Unitary Products 29 FIGURE 24 TYPICAL WIRING DIAGRAM D NP 030 048 SINGLE STAGE GAS HEAT 208 230 3 60 POWER SUPPLY...

Page 30: ...280241 YIM D 0909 30 Johnson Controls Unitary Products FIGURE 25 TYPICAL WIRING DIAGRAM D NP 030 048 TWO STAGE GAS HEAT 208 230 3 60 POWER SUPPLY...

Page 31: ...280241 YIM D 0909 Johnson Controls Unitary Products 31 FIGURE 26 TYPICAL WIRING DIAGRAM D NP 060 SINGLE STAGE GAS HEAT 208 230 3 60 POWER SUPPLY...

Page 32: ...280241 YIM D 0909 32 Johnson Controls Unitary Products FIGURE 27 TYPICAL WIRING DIAGRAM D NP 060 TWO STAGE GAS HEAT 208 230 3 60 POWER SUPPLY...

Page 33: ...280241 YIM D 0909 Johnson Controls Unitary Products 33 FIGURE 28 TYPICAL WIRING DIAGRAM D NP 030 048 SINGLE STAGE GAS HEAT 460 575 3 60 POWER SUPPLY...

Page 34: ...280241 YIM D 0909 34 Johnson Controls Unitary Products FIGURE 29 TYPICAL WIRING DIAGRAM D NP 030 048 TWO STAGE GAS HEAT 460 575 3 60 POWER SUPPLY...

Page 35: ...280241 YIM D 0909 Johnson Controls Unitary Products 35 FIGURE 30 TYPICAL WIRING DIAGRAM D NP 060 SINGLE STAGE GAS HEAT 460 575 3 60 POWER SUPPLY...

Page 36: ...280241 YIM D 0909 36 Johnson Controls Unitary Products FIGURE 31 TYPICAL WIRING DIAGRAM D NP 060 TWO STAGE GAS HEAT 460 575 3 60 POWER SUPPLY...

Page 37: ...sent wire 801 BL and 805 BL are connected to M1 coil If only ASCT is present wire 202 Y is connected to ASCT 3 If neither LR or ASCT are present wire 202 Y is connected to M1coil as shown 7 Removed 8...

Page 38: ...280241 YIM D 0909 38 Johnson Controls Unitary Products...

Page 39: ...280241 YIM D 0909 Johnson Controls Unitary Products 39...

Page 40: ...o change without notice Printed in U S A 280241 YIM D 0909 Copyright 2009 by Johnson Controls All rights reserved Supersedes 280241 YIM C 1108 Johnson Controls Unitary Products 5005 York Drive Norman...

Reviews: