Water Pressure Drop cont.
Pressure Drop
Model 066
Model
GPM
Pressure Drop (psi)
30°F
50°F
70°F
90°F
110°F
130°F
150°F
040
5.0
0.9
0.6
0.6
0.5
0.5
0.4
0.3
7.5
2.3
2.1
2.0
1.9
1.8
1.6
1.5
10.0
3.7
3.5
3.3
3.2
3.0
2.8
2.7
12.5
5.0
4.7
4.4
4.2
4.1
3.9
3.7
050
8.0
1.7
1.4
1.4
1.3
1.3
1.2
1.1
11.5
3.6
3.4
3.2
3.0
2.8
2.6
2.5
15.0
5.6
5.4
5.0
4.6
4.4
4.3
4.1
18.5
8.3
8.1
7.6
7.2
6.8
6.6
6.4
066
10.0
3.2
3.0
2.8
2.7
2.5
2.4
2.3
14.5
5.5
5.3
5.1
4.9
4.7
4.6
4.5
19.0
7.9
7.6
7.3
7.1
6.8
6.6
6.5
23.5
11.5
11.3
11.0
10.8
10.3
10.1
9.9
7/8/14
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
5
10
15
20
25
30
W
ater P
res
su
re
drop,
ps
ig
Flow rate, gpm