333491-YTG-B-0807
42
Unitary Products Group
Electrical Data
DNZ024-060 Gas Heat
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
Max
Fuse
2
/
Breaker
3
Size
(Amps)
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
RLA
LRA
MCC
FLA
FLA
024
(2.0)
208/230-1-60 12.8
60
20
1.2
4.1
21.3
30
030
(2.5)
208/230-1-60 14.7
73
23
1.2
6.0
25.6
35
208/230-3-60 10.4
60
16
1.2
6.0
20.2
25
460-3-60
4.5
31
7
0.6
3.0
9.2
15
036
(3.0)
208/230-1-60 15.4
83
24
1.2
6.0
26.5
35
208/230-3-60 11.5
77
18
1.2
6.0
21.6
30
460-3-60
5.1
35
8
0.8
3.0
10.1
15
042
(3.5)
208/230-1-60 18.6
105
29
1.2
7.6
32.1
40
208/230-3-60 13.4
88
21
1.2
7.6
25.6
35
460-3-60
6.4
39
10
0.8
3.8
12.6
15
048
(4.0)
208/230-1-60 20.5
109
32
1.7
7.6
34.9
45
208/230-3-60 14.5
91
23
1.7
7.6
27.4
35
460-3-60
7.0
46
11
1.0
3.8
13.6
20
060
(5.0)
208/230-1-60 26.4
134
41
1.8
7.6
42.4
60
208/230-3-60 15.9
110
25
1.8
7.6
29.3
40
460-3-60
7.7
52
12
0.9
3.8
14.3
20
DNY024-060 Gas Heat
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
Max
Fuse
2
/
Breaker
3
Size
(Amps)
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
RLA
LRA
MCC
FLA
FLA
024
(2.0)
208/230-1-60 10.2
52
16
1.4
4.3
18.5
25
036
(3.0)
208/230-1-60 16.6
82
26
1.4
6.8
29
35
208/230-3-60 11.1
58
17
1.4
6.8
22.1
30
460-3-60
4.5
29
7
0.8
3.4
9.8
15
048
(4.0)
208/230-1-60 21.1
96
33
1.7
9.1
37.2
45
208/230-3-60 13.4
88
21
1.7
9.1
27.6
35
460-3-60
6.4
41
10
0.9
4.6
13.5
15
060
(5.0)
208/230-1-60 25.6
118
40
1.8
9.1
42.9
60
208/230-3-60 17.6
135
28
1.8
9.1
32.9
40
460-3-60
9.0
62
14
0.9
4.6
16.8
25
DNX024-048 Gas Heat
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
Max
Fuse
2
/
Breaker
3
Size
(Amps)
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
RLA
LRA
MCC
FLA
FLA
024
(2.0)
208/230-1-60 10.2
52
16
1.4
4.3
18.1
25
036
(3.0)
208/230-1-60 16.6
82
26
0.9
9.1
30.7
40
208/230-3-60 11.1
58
17
0.9
9.1
23.8
30
460-3-60
4.5
29
7
0.5
4.6
10.7
15
048
(4.0)
208/230-1-60 21.1
96
33
1.8
9.1
36.3
45
208/230-3-60 13.4
88
21
1.8
9.1
26.7
35
460-3-60
6.4
41
10
0.9
4.6
13.0
15