background image

 292443-XTG-B-0807

6

Unitary Products Group

TABLE 1: PHYSICAL DATA

MODEL

DNA

018

024

030

036

042

048

060

EVAPORATOR

BLOWER

CENTRIFUGAL BLOWER (Dia. x W. in.)

10 x 8

10 x 8

10 x 8

11 x 10

11 x 10

12 x 11

12 x 11

FAN MOTOR HP (3 Speed)

1/2

1/2

1/2

3/4

3/4

1

1

EVAPORATOR

COIL

ROWS  DEEP

2

2

2

2

3

3

3

FINS PER INCH

14

13

13

15

13

13

13

FACE AREA (Sq. Ft.)

2.25

3.5

3.5

3.5

3.5

4.5

4.5

CONDENSER

FAN

PROPELLER  DIA.  (in.)

22

22

22

22

22

22

22

FAN MOTOR HP

1/4

1/4

1/4

1/4

1/4

1/4

1/4

NOM. CFM TOTAL

1,800

2,200

2,400

2,400

2,400

3,000

3,000

CONDENSER

COIL

ROWS  DEEP

1

1

1

1

1

1

1

FINS PER INCH

13

13

16

20

20

20

20

FACE AREA (Sq. Ft.)

8.3

8.3

11.7

11.7

11.7

14.8

14.8

CHARGE

REFRIGERANT 22 (lbs./oz.)

3 / 2

3 / 16

4 / 12

4 / 3

4 / 12

6 / 0

5 / 4

FILTER

1

FACE AREA (Sq. Ft.) Size (Nominal)

2.6/20x20

2.6/20x20

2.6/20x20

2.6/20x20

2.6/20x20

3.3/20x12

3.3/20x12

FURNACE

SECTION

NATURAL GAS BURNER ORIFICE NO. (Drill Size)

43

43

43

43

43

40

40

PROPANE BURNER ORIFICE NO. (Drill Size)

55

55

55

55

55

53

53

GAS CONNECTION SIZE

1/2

 NPTI

1/2

 NPTI

1/2

 NPTI

1/2

 NPTI

1/2 

NPTI

1/2

 NPTI

1/2 

NPTI

COMPRESSOR

TYPE

HERMETICALLY SEALED
(R = RECIPROCATING, S = SCROLL)

R

R

R

R

R

S

S

1. See FILTER/FRAME KIT on page 5.

TABLE 2: RATINGS COOLING/GAS HEATING

MODEL

DNA

NET COOLING CAPACITY

1

SOUND

RATING

(dbels)

2

GAS HEAT CAPACITY / EFFICIENCIES

MBH

EER

3

INPUT
(MBH)

OUTPUT

(MBH)

AFUE

4

(%)

NUMBER OF

BURNERS

TEMP.

RISE

(°F) RANGE

018N03606

17.9

8.9

76

45

36

80.2

2

25 - 55

024N03606

23.0

9.2

78

45

36

80.2

2

25 - 55

024N05606

23.0

9.2

78

70

56

80.2

3

30 - 60

030N03606

29.0

9.0

78

45

36

80.2

2

25 - 55

030N05606

29.0

9.0

78

70

56

80.2

3

30 - 60

036N03606

34.8

8.9

82

45

36

80.4

2

25 - 55

036N05606

34.8

8.9

82

70

56

80.2

3

25 - 55

036N07206

34.8

8.9

82

90

72

80.1

4

30 - 60

042N03606

40.5

9.0

84

45

36

80.4

2

25 - 55

042N05606

40.5

9.0

84

70

56

80.2

3

25 - 55

042N07206

40.5

9.0

84

90

72

80.1

4

30 - 60

048N06506

46.5

8.6

82

80

64

80

3

25 - 55

048N09006

46.5

8.6

82

108

86

80

4

30 - 60

048N11006

46.5

8.6

82

135

108

80

5

35 - 65

060N06506

56.5

8.9

82

80

64

80

3

25 - 55

060N09006

56.5

8.9

82

108

86

80

4

30 - 60

060N11006

56.5

8.9

82

135

108

80

5

35 - 65

1. Net Cooling Capacity = ARI 210 standard rating conditions.
2. (dbels) = ARI 270-95
3. Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total 

electric power input in watt-hours during the same period.

4. AFUE = Annual Fuel Utilization Efficiency.

Summary of Contents for AFFINITY 292443-XTG-B-0807

Page 1: ... Series packaged units are designed to han dle applications ranging from residential to light commercial and any in between The Affinity is a unit that gives you the flexibility and choices you need in today s market FEATURING COOLING GAS HEATING UNITS NATURAL GAS OR PROPANE LOW PROFILE QUIET OPERATION COMMON FOOTPRINT OPTIONAL SLIDE IN MOTORIZED DAMPERS OPTIONAL SLIDE IN ECONOMIZERS OPTIONAL PROP...

Page 2: ...S 2 TON 8 5 DNA030 COOLING CAPACITIES 2 1 2 TON 9 6 DNA036 COOLING CAPACITIES 3 TON 10 7 DNA042 COOLING CAPACITIES 3 1 2 TON 11 8 DNA048 COOLING CAPACITIES 4 TON 12 9 DNA060 COOLING CAPACITIES 5 TON 13 10 SIDE SUPPLY AIR BLOWER PERFORMANCE 14 11 BOTTOM SUPPLY AIR BLOWER PERFORMANCE 14 12 ADDITIONAL STATIC PRESSURE RESISTANCE 1 1 2 3 1 2 TON DNA018 042 15 13 ADDITIONAL STATIC PRESSURE RESISTANCE 4 ...

Page 3: ...DENSATE PAN A non corrosive long lasting water tight pan is positioned below the evaporator coil to collect and drain all condensate Less collection of stagnate condensate will build up The condensate pan conforms to ASHRAE 62 89 standards Ventilation for Acceptable Indoor Air Quality CONDENSATE DRAIN The heavy duty 3 4 inch NPTI cop per connection is more tolerable during installation and is more...

Page 4: ...tem No final field mounting required EASY SERVICE ACCESS A large single panel covers the electrical and gas controls makes servicing easy The blower compartment has an additional large panel with a built in handle tab Removing this panel will allow the blower assem bly to slide out for easy removal for maintenance and ease of trouble shooting REPLACEMENT PARTS The installer has no need to carry an...

Page 5: ...TDOOR DAMPER Provides 0 through 50 outdoor air capability field adjustable Designed for duct mounted side supply return applications Includes hood and screen assembly WALL THERMOSTAT The units are designed to operate with 24 volt electronic and electro mechanical thermostats All units can operate with single stage heat single stage cool thermostats with or without the economizer LOW AMBIENT KIT Ki...

Page 6: ...D R RECIPROCATING S SCROLL R R R R R S S 1 See FILTER FRAME KIT on page 5 TABLE 2 RATINGS COOLING GAS HEATING MODEL DNA NET COOLING CAPACITY1 SOUND RATING dbels 2 GAS HEAT CAPACITY EFFICIENCIES MBH EER3 INPUT MBH OUTPUT MBH AFUE4 NUMBER OF BURNERS TEMP RISE F RANGE 018N03606 17 9 8 9 76 45 36 80 2 2 25 55 024N03606 23 0 9 2 78 45 36 80 2 2 25 55 024N05606 23 0 9 2 78 70 56 80 2 3 30 60 030N03606 2...

Page 7: ... 1 Entering Dry Bulb F 86 9 4 11 7 13 3 13 1 10 2 12 8 14 0 13 9 11 1 13 9 14 8 14 7 11 1 14 1 15 2 15 1 11 1 14 3 15 6 15 5 83 8 5 10 9 12 9 12 9 9 3 11 9 13 8 13 8 10 1 12 9 14 8 14 7 10 3 13 3 15 2 15 1 10 6 13 7 15 6 15 5 80 7 6 10 0 12 0 12 0 8 3 10 9 13 2 13 1 9 0 11 9 14 3 14 2 9 5 12 5 14 9 14 9 10 0 13 1 15 6 15 5 77 6 7 9 1 11 2 11 1 7 4 10 0 12 2 12 2 8 0 10 8 13 2 13 2 8 7 11 7 14 1 14...

Page 8: ...3 0 16 4 18 1 18 0 14 2 17 8 18 8 18 8 15 3 19 2 19 5 19 6 15 3 19 5 19 8 19 9 15 4 19 8 20 1 20 1 83 11 9 15 2 17 7 17 5 12 9 16 5 18 6 18 6 13 9 17 8 19 5 19 6 14 3 18 4 19 8 19 9 14 6 19 0 20 1 20 1 80 10 7 14 1 16 5 16 3 11 6 15 3 17 9 17 7 12 5 16 5 19 3 19 1 13 2 17 4 19 7 19 6 13 9 18 3 20 1 20 1 77 9 5 12 9 15 4 15 2 10 3 14 0 16 7 16 5 11 1 15 1 18 0 17 7 12 1 16 3 18 6 18 6 13 1 17 5 19 ...

Page 9: ... 15 9 20 0 20 6 20 1 17 7 22 3 22 5 21 9 19 6 24 7 24 4 23 8 19 5 24 9 24 7 24 0 19 5 25 1 25 0 24 3 83 14 4 18 5 20 5 19 9 16 1 20 7 22 5 21 8 17 8 22 9 24 4 23 8 18 2 23 5 24 7 24 0 18 6 24 1 25 0 24 3 80 13 0 17 1 19 6 18 8 14 5 19 1 21 9 21 0 16 1 21 2 24 3 23 3 16 9 22 2 24 6 23 8 17 6 23 2 25 0 24 3 77 11 5 15 6 18 1 17 3 12 9 17 5 20 3 19 5 14 4 19 5 22 5 21 6 15 5 20 9 23 3 22 5 16 7 22 2 ...

Page 10: ...6 21 1 27 2 29 8 28 8 22 4 28 7 30 6 29 5 23 7 30 3 31 3 30 2 23 2 30 1 31 7 30 6 22 8 29 8 32 1 30 9 83 19 4 25 4 29 3 28 4 20 5 26 8 30 3 29 3 21 6 28 2 31 3 30 2 21 6 28 5 31 7 30 6 21 7 28 7 32 1 30 9 80 17 7 23 7 27 6 27 0 18 6 24 9 29 0 28 4 19 5 26 1 30 4 29 8 20 1 26 9 31 2 30 4 20 6 27 7 32 1 30 9 77 15 9 21 9 25 8 25 3 16 6 23 0 27 1 26 5 17 4 24 0 28 3 27 7 18 5 25 3 29 7 28 8 19 6 26 6...

Page 11: ...F 86 23 6 29 4 31 7 31 8 25 7 32 0 33 3 33 7 27 8 34 6 34 8 35 6 28 0 35 1 35 6 36 4 28 1 35 7 36 5 37 3 83 21 5 27 3 30 9 30 9 23 4 29 7 32 9 32 9 25 3 32 1 34 8 35 0 26 1 33 2 35 6 36 2 26 8 34 4 36 5 37 3 80 19 5 25 3 28 9 28 8 21 2 27 5 31 4 31 3 22 9 29 7 33 8 33 8 24 2 31 3 35 2 35 5 25 5 33 0 36 5 37 3 77 17 5 23 3 26 8 26 8 18 9 25 2 29 1 29 1 20 4 27 2 31 4 31 4 22 3 29 5 33 3 33 7 24 1 3...

Page 12: ...86 26 7 34 8 35 7 36 0 30 1 38 1 37 2 37 5 33 4 41 5 38 8 39 1 36 1 42 5 39 2 39 5 38 8 43 6 39 7 40 0 83 23 3 31 3 35 3 35 6 26 0 34 9 37 0 37 3 28 7 38 4 38 8 39 1 30 8 40 5 39 2 39 5 32 8 42 6 39 7 40 0 80 19 9 27 9 32 0 32 2 22 0 30 8 35 3 35 6 24 1 33 8 38 7 39 0 25 5 35 7 39 2 39 5 26 9 37 7 39 7 40 0 77 16 5 24 5 28 6 28 8 17 9 26 8 31 3 31 6 19 4 29 1 34 0 34 3 20 2 30 4 33 9 34 2 20 9 31 ...

Page 13: ...lb F 86 36 1 45 1 45 0 42 7 39 9 48 7 46 8 44 3 43 7 52 3 48 5 45 9 46 9 53 0 49 0 46 4 50 1 53 6 49 5 46 9 83 31 8 40 8 44 8 42 6 34 9 44 6 46 7 44 2 37 9 48 4 48 5 45 9 40 3 50 5 49 0 46 4 42 6 52 6 49 5 46 9 80 27 6 36 5 41 5 39 4 29 8 39 5 44 9 42 6 32 1 42 5 48 3 45 8 33 6 44 6 48 9 46 3 35 2 46 6 49 5 46 9 77 23 3 32 2 37 2 35 1 24 8 34 5 39 8 37 5 26 3 36 7 42 4 40 0 27 0 37 9 42 2 39 7 27 ...

Page 14: ...udes allowances for a dry evaporator coil gas heat exchanger and no filters For additional pressure drops refer to Table 12 and 13 TABLE 11 BOTTOM SUPPLY AIR BLOWER PERFORMANCE1 MODEL DNA MTR SPD EXTERNAL STATIC PRESSURE IWG 10 20 30 40 50 60 70 80 90 1 00 1 10 CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS 018 HI 547 322 419 293 MED 6...

Page 15: ...ss CFM during full economizer operation TABLE 13 ADDITIONAL STATIC PRESSURE RESISTANCE 4 5 TON DNA048 060 1 DESCRIPTION RESISTANCE IWG CFM 500 600 700 800 900 1 000 1 100 1 200 1 300 1 400 1 500 1 600 1 700 1 800 1 900 2 000 WET EVAPORATOR COIL 03 04 05 06 07 07 08 09 09 ECONOMIZER2 02 02 03 03 04 04 04 05 05 FILTER FRAME KIT 04 05 05 06 07 08 09 10 11 1 Deduct these resistance values from the ava...

Page 16: ... FACTOR TRANSFORMER SIZE VA MIN MAX RLA LRA 018 208 230 1 60 187 253 9 0 48 0 1 1 2 2 14 5 20 20 96 40 024 208 230 1 60 187 253 11 5 60 0 1 1 2 2 17 7 25 25 96 40 030 208 230 1 60 187 253 14 7 73 0 1 1 2 2 21 7 30 30 96 40 036 208 230 1 60 187 253 17 3 94 0 1 1 3 5 26 2 35 35 96 40 042 208 230 1 60 187 253 20 5 120 0 1 1 3 5 30 2 40 40 96 40 048 208 230 1 60 187 253 24 4 140 0 1 3 7 0 38 8 50 50 9...

Page 17: ... I N L E T L O U V E R S F R O N T G A S E L E C T R I C C O N T R O L S E R V I C E A C C E S S C O M P A R T M E N T P A N E L O V E R A L L O V E R A L L All dimensions are in inches They are subject to change with out notice Certified dimensions will be provided upon request TABLE 15 UNIT DIMENSIONS FRONT UNIT SIZE DIMENSION A B 018 thru 042 33 1 2 18 1 4 048 and 060 41 1 2 23 1 8 TABLE 16 UNI...

Page 18: ... D R A I N 3 4 N P T I G A S S U P P L Y 1 5 8 D I A K N O C K O U T 1 2 N P T I C O N N E C T I O N L O W V O L T A G E C O N N 1 8 D I A K N O C K O U T 1 3 4 1 5 2 9 9 1 6 1 5 3 1 2 1 3 4 1 3 4 1 5 4 1 4 1 2 3 1 2 3 3 8 1 4 1 2 2 8 3 8 1 4 1 2 C O N D E N S E R C O I L B O T T O M S U P P L Y A I R O P E N I N G B O T T O M R E T U R N A I R O P E N I N G S I D E R E T U R N A I R O P E N I N G...

Page 19: ... L G A S S H U T O F F V A L V E R E T U R N A I R D U C T S U P P L Y A I R D U C T C O N T R O L W I R I N G T O I N D O O R T H E R M O S T A T T O P O W E R S U P P Y M A N U A L G A S S H U T O F F V A L V E F I E L D S U P P L I E D D I S C O N N E C T S W I T C H M O U N T E D O N U N I T T O P O W E R S U P P L Y T O G A S S U P P L Y L I N E C O N T R O L W I R I N G T O I N D O O R T H E...

Page 20: ...O U N D I N S T A L L A T I O N TABLE 17 UNIT WEIGHTS AND CENTER OF GRAVITY UNIT SIZE SHIPPING WEIGHT lbs OPERATING WEIGHT lbs CORNER WEIGHTS location lbs ECONOMIZER lbs ROOF CURB lbs A B C D 018 365 360 91 88 89 92 40 8 70 14 75 024 365 360 91 88 89 92 030 395 390 98 95 96 99 036 400 395 100 96 98 101 042 415 410 104 100 101 105 048 475 470 119 115 116 120 060 480 475 120 116 117 122 A B C D 49 1...

Page 21: ... 1 8 X 2 1 1 2 R E C O M M E N D E D D U C T S I Z E 1 7 1 2 X 1 6 3 4 1 8 Roof curb also available 3 4 X 1 W I D E G A S K E T I N G F O R C U R B F R A M E A N D A L L D U C T S U P P O R T S U R F A C E S U N I T B A S E W O O D N A I L E R 8 M I N A B O V E F I N I S H E D R O O F C U R B F R A M E I N S U L A T I O N U N I T B A S E R A I L C O U N T E R F L A S H I N G C A N T S T R I P I N ...

Page 22: ...292443 XTG B 0807 22 Unitary Products Group FIGURE 14 TYPICAL WIRING DIAGRAM DNA 018 THRU 060 208 230 1 60 POWER SUPPLY ...

Page 23: ... facility YORK s Affinity package units are designed to handle applications ranging from residential to light commercial and any in between The Affinity is a unit that gives you the flexibility and choices you need in today s market These packaged cooling heating air conditioners are designed for outdoor installation Only utility and duct connections are required at the point of installation The g...

Page 24: ... Fan shall be direct drive multi speed design Job site selected BHP brake horsepower shall not exceed the motors nameplate horsepower rating Fan wheel shall be double inlet type with forward curved blades dynamically balanced to operate smoothly throughout the entire range of operation Airflow design shall be constant air volume Bear ings shall be sealed and permanently lubricated for longer life ...