 291627-YTG-B-0807

4

Unitary Products Group

FAN SYSTEM

 - All models operate over a wide range of 

design conditions with a 3-speed direct-drive fan motor. 
These units easily match all types of applications and pro-
vides greater on site flexibility to match comfort requirement.

SIMPLE CONTROL CIRCUIT

 - A low voltage printed circuit 

board contains a diagnostic indicator light and a low voltage 
terminal strip. An additional set of pin connectors is also pro-
vided to simplify the field interface of external controls. Mate-
n-lock plug connectors are used. The electrical control box is 
not located in the compressor compartment. The controls are 
mounted on a Control-Tilt control panel to allow the access 
cover to be removed for trouble shooting and maintenance 
without affecting the normal system operating pressures. All 
wiring internal to the unit is color/number coded.

PROTECTED COMPRESSOR

 - The compressor is internally 

protected against high pressure and temperature. This is 
accomplished by the simultaneous operation of high pressure 
relief valve and a temperature sensor which protect the com-
pressor if undesirable operating conditions occur.

EXCLUSIVE COIL DESIGN

 - Grooved copper tubes and 

enhanced aluminum fin construction improves heat transfer 
for maximum efficiency and durability.

HEAT EXCHANGERS

 - Are corrosion-resistant, aluminized-

steel tubular construction to provide long-life, trouble-free 
operation. The unique blow-through design also assures that 
condensate does not collect in humid areas when in the cool-
ing cycle. This adds to longer heat exchanger life and higher 
long term efficiencies.

POST PURGE INDUCED DRAFT COMBUSTION

 - Exhausts 

combustion products from the heat exchanger upon comple-
tion of the heating cycle to prolong the heat exchanger life.

SELF DIAGNOSTIC FAN CONTROL MODULE

 - Due to this 

self diagnostic control, less on site time is required to trouble 
shoot these units.

SPARK TO PILOT IGNITION

 - Provides faster heat delivery. 

This ignition is highly reliable, durable and eliminates nui-
sance lockouts.

MULTI PORT IN-SHOT BURNERS

 - No field adjustment is 

required to mix the air and gas. These burners are con-
structed of high-grade corrosion-resistant, aluminized-steel.

LOW MAINTENANCE

 - Long life, permanently lubricated 

condenser and evaporator fan motor bearings need no 
annual maintenance adding greater reliability to the unit. 
Blower assembly can be easily cleaned by the unique Slip- 
Track slide-out blower assembly.

SECURED SERVICE ACCESS PORTS

 - Protected, exter-

nally mounted, re-usable service access ports are provided 
on both the high and low lines for ease of evacuating and 
charging the system. No final field mounting required.

EASY SERVICE ACCESS

 - A large, single panel covers the 

electrical and gas controls makes servicing easy. The blower 

compartment has an additional large panel with a built-in 
handle tab. Removing this panel will allow the blower assem-
bly to slide-out for easy removal for maintenance and ease of 
trouble shooting.

REPLACEMENT PARTS

 - The installer has no need to carry 

an inventory of unique parts or needs special training to 
replace any of the components parts for these units. All are 
easily obtained from Source 1 or other part houses. 

SYSTEM INTEGRATION

 - Each unit has the internal ability 

to integrate an electronic air cleaner or humidifier to work in 
conjunction with the base unit.

FILTER / FRAME KIT

 - The filter rack is suitable for either 1" 

or 2" filters. (1" filter is supplied).

FIELD-INSTALLED ACCESSORIES

PROPANE CONVERSION KIT

 - Kit includes burner orifices, 

gas valve conversion and installation instructions necessary 
to field convert unit from natural gas to propane.

HIGH ALTITUDE CONVERSION KIT

 (Natural Gas/Propane) 

- Kit includes all necessary labels and instructions to field 
alter units with natural gas/propane for installation above 
2000 feet. Burner orifices must be obtained from Source 1 
Parts. Propane Conversion Kit must be obtained separately.

ECONOMIZER DOWN DISCHARGE / SUPPLY KIT

 - Modu-

lating integrated economizer provides simultaneous opera-
tion between the mechanical cooling and economizer 
operation. Independent blade design insures proper control 
and less than 1% leak rate. Includes hood and mesh bird 
screen filter integrated into the hood, dry bulb sensor and 
relief damper. Separate field accessories of single enthalpy 
and dual enthalpy are also available. A built-in barometric 
relief of 25% is provided.

SINGLE ENTHALPY SENSOR

 - Sensor replaces dry bulb 

sensor standard in economizer kit. Provides improved econo-
mizer operation by sensing the dry bulb temperature from 
outdoors plus the enthalpy content of the outdoor air.

DUAL ENTHALPY SENSOR

 - Additional sensor to single 

enthalpy sensor. Sensor senses both the return air tempera-
ture dry bulb and humidity in conjunction with the single 
enthalpy to determine the most economical mix. Single 
Enthalpy sensor also required.

PRESSURE SWITCH UPGRADE KIT

 - Contains screw in 

type High pressure, Low Pressure/Loss of Charge switch, 
freeze protection switch and lockout relay. Switches are 
placed onto existing scharder ports located in the unit by fur-
nished adapters. When abnormal conditions are sensed 
through the pressure switches, the unit will lock out prevent-
ing any further operation until reset or problem is corrected. 
Package agency approved.

HAIL GUARD KIT

 - Kit contains protective grilles made of 

expanded aluminum with full perimeter frame. Sloped hoods 
are also included to assure maximum protection.

Summary of Contents for AFFINITY 291627-YTG-B-0807

Page 1: ...g from residential to light commercial and any in between The Affinity is a unit that gives you the flexibility and choices you need in today s market FEATURING COOLING GAS HEATING UNITS NATURAL GAS O...

Page 2: ...TA 7 2 RATINGS COOLING GAS HEATING 8 3 DNH030 COOLING CAPACITIES 2 1 2 TON 9 4 DNH036 COOLING CAPACITIES 3 TON 10 5 DNH042 COOLING CAPACITIES 3 1 2 TON 11 6 DNH048 COOLING CAPACITIES 4 TON 12 7 DNH060...

Page 3: ...ENSATE PAN A non corrosive long lasting water tight pan is positioned below the evaporator coil to collect and drain all condensate Less collection of stagnate condensate will build up The condensate...

Page 4: ...g the system No final field mounting required EASY SERVICE ACCESS A large single panel covers the electrical and gas controls makes servicing easy The blower compartment has an additional large panel...

Page 5: ...screen assembly WALL THERMOSTAT The units are designed to operate with 24 volt electronic and electro mechanical thermostats All units can operate with single stage heat single stage cool thermostats...

Page 6: ...1 4 1 4 1 4 1 3 1 3 NOM CFM TOTAL 2 400 2 400 2 400 3 000 3 000 CONDENSER COIL ROWS DEEP 1 2 1 2 2 FINS PER INCH 20 20 20 20 20 FACE AREA Sq Ft 11 7 11 7 14 7 14 7 14 7 CHARGE REFRIGERANT 22 lbs oz 4...

Page 7: ...0 6 3 25 55 042N09025 42 0 12 0 80 108 87 80 8 4 45 75 042N09046 42 0 12 0 80 108 87 80 8 4 45 75 048N06525 48 0 12 0 84 80 64 80 8 3 25 55 048N06546 48 0 12 0 84 80 64 80 8 3 25 55 048N09025 48 0 12...

Page 8: ...MBH 1 Entering Dry Bulb F 86 16 0 19 6 19 4 19 0 18 4 22 3 21 4 20 9 20 8 24 9 23 3 22 8 22 3 25 0 23 4 22 9 23 7 25 2 23 5 23 0 83 13 9 18 0 19 4 19 0 15 9 20 6 21 4 20 9 17 9 23 2 23 3 22 8 18 9 23...

Page 9: ...20 6 25 9 28 3 28 3 23 0 28 9 30 5 30 6 25 3 31 8 32 6 32 9 25 2 32 0 33 2 33 4 25 1 32 2 33 7 33 9 83 18 9 24 2 27 9 27 8 21 0 26 9 30 3 30 4 23 2 29 7 32 6 32 9 23 6 30 4 33 2 33 4 24 0 31 1 33 7 33...

Page 10: ...F 86 24 8 31 0 29 9 29 5 28 2 34 9 32 7 32 2 31 6 38 7 35 5 35 0 34 0 39 1 36 2 34 8 36 3 39 4 35 0 34 5 83 21 8 28 0 29 9 29 5 24 7 31 6 32 7 32 2 27 5 35 3 35 5 35 0 29 3 36 8 35 2 34 8 31 1 38 4 35...

Page 11: ...6 31 8 39 0 39 9 39 9 34 3 41 4 40 8 40 7 36 9 43 8 41 6 41 5 40 3 45 7 42 8 42 8 43 8 47 6 44 1 44 0 83 28 4 35 7 38 9 39 0 30 3 38 0 40 2 40 3 32 2 40 3 41 6 41 5 35 0 43 3 42 8 42 8 37 9 46 2 44 1...

Page 12: ...6 41 8 51 8 53 0 51 7 43 6 54 0 53 8 52 6 45 5 56 2 54 6 53 4 47 1 56 7 54 3 56 1 48 7 57 3 54 0 52 8 83 36 9 47 0 52 2 51 7 38 4 48 9 53 4 52 6 39 9 50 7 54 6 53 4 41 2 52 3 54 3 53 1 42 5 53 8 54 0...

Page 13: ...1315 657 1204 623 1093 588 MED 1432 650 1381 628 1330 605 1279 583 1210 556 1140 529 LOW 1191 527 1149 510 1107 494 1065 477 048 HI 1742 898 1695 869 1648 841 1601 811 1555 781 1501 747 1446 714 1317...

Page 14: ...913 1706 888 1648 861 1590 834 1445 783 1301 731 MED 1734 848 1693 821 1651 794 1595 764 1539 734 1461 693 1382 653 1266 613 LOW 1532 700 1508 683 1458 667 1444 643 1404 620 1348 593 1291 566 060 only...

Page 15: ...1295 639 1147 600 MED 1482 628 1428 613 1374 599 1320 584 1242 556 1163 528 1085 500 LOW 1239 510 1184 496 1130 481 1075 467 048 HI 1655 771 1609 749 1563 727 1504 698 1444 670 1381 648 1319 626 MED 1...

Page 16: ...814 945 1731 905 1578 582 LOW 1937 990 1892 983 1846 935 1785 908 1723 880 1655 843 1587 805 060 3 tube only 230 460 volts HEAT 1500 245 1500 297 1500 348 1500 400 1500 470 1500 540 1500 610 1500 680...

Page 17: ...m the available external static pressure shown in Table 8 9 10 and 11 2 The pressure through the economizer is greater for 100 outdoor air then for 100 return air If the resistance of the return air d...

Page 18: ...504 4 3 27 0 6 1 4 7 4 15 15 96 75 036 208 230 3 60 187 253 11 4 77 1 1 3 5 18 9 25 25 96 75 036 460 3 60 414 504 5 7 39 0 6 1 8 9 5 15 15 96 75 042 208 230 3 60 187 253 13 9 88 1 3 3 5 22 2 30 30 96...

Page 19: ...I R I N L E T L O U V E R S F R O N T G A S E L E C T R I C C O N T R O L S E R V I C E A C C E S S C O M P A R T M E N T P A N E L O V E R A L L O V E R A L L All dimensions are in inches They are s...

Page 20: ...D R A I N 3 4 N P T I G A S S U P P L Y 1 5 8 D I A K N O C K O U T 1 2 N P T I C O N N E C T I O N L O W V O L T A G E C O N N 1 8 D I A K N O C K O U T 1 3 4 1 5 2 9 9 1 6 1 5 3 1 2 1 3 4 1 3 4 1 5...

Page 21: ...L G A S S H U T O F F V A L V E R E T U R N A I R D U C T S U P P L Y A I R D U C T C O N T R O L W I R I N G T O I N D O O R T H E R M O S T A T T O P O W E R S U P P Y M A N U A L G A S S H U T O F...

Page 22: ...U C T S L A B O N G R O U N D I N S T A L L A T I O N TABLE 17 UNIT WEIGHTS AND CENTER OF GRAVITY UNIT SIZE SHIPPING WEIGHT lbs OPERATING WEIGHT lbs CORNER WEIGHTS location lbs ECONOMIZER lbs ROOF CU...

Page 23: ...1 8 X 2 1 1 2 R E C O M M E N D E D D U C T S I Z E 1 7 1 2 X 1 6 3 4 1 8 Roof curb also available 3 4 X 1 W I D E G A S K E T I N G F O R C U R B F R A M E A N D A L L D U C T S U P P O R T S U R F A...

Page 24: ...291627 YTG B 0807 24 Unitary Products Group FIGURE 14 TYPICAL WIRING DIAGRAM DNH 030 036 042 048 208 230 3 60 POWER SUPPLY...

Page 25: ...291627 YTG B 0807 Unitary Products Group 25 FIGURE 15 TYPICAL WIRING DIAGRAM DNH 030 036 042 048 460 3 60 POWER SUPPLY...

Page 26: ...291627 YTG B 0807 26 Unitary Products Group FIGURE 16 TYPICAL WIRING DIAGRAM DNH 060 208 230 3 60 POWER SUPPLY...

Page 27: ...291627 YTG B 0807 Unitary Products Group 27 FIGURE 17 TYPICAL WIRING DIAGRAM DNH 060 460 3 60 POWER SUPPLY...

Page 28: ...If neither LR or ASCT are present wire 202 Y is connected to M1 coil as shown 7 Shunt contact also used with crankcase heater optional 8 Unit factory wired for low or medium speed indoor blower operat...

Page 29: ...otection from objects and personnel after installation Indoor blower section shall be insulated with up to 3 4 thick aluminum foil faced insulation fastened to prevent insulation from entering the air...

Page 30: ...nts brazed b Evaporator coil shall be of the direct expansion blow through design while condenser coil shall be draw through design Refrigerant Circuit and Refrigerant Safety Components a Shall includ...

Page 31: ...291627 YTG B 0807 Unitary Products Group 31...

Page 32: ...t to change without notice Printed in U S A 291627 YTG B 0807 Copyright 2007 by Unitary Products Group All rights reserved Supersedes 291627 YTG A 0207 Unitary 5005 Norman Products York OK Group Drive...

Reviews: