to shipment. All unit wiring shall be both numbered and 
color coded. All units shall be manufactured in a facility cer-
tified to ISO 9001 standards, and the cooling performance 
shall be rated in accordance with DOE and ARI test proce-
dures. The heating performance shall be rated to DOE and 
GAMA test procedures. Units shall be CSA listed and classi-
fied to ANSI Z21.47/CAN/CSA 2.3 standards and UL 1995/
CAN/CSA No. 236-M90 conditions.

UNIT CABINET

Unit cabinet shall be constructed of G90 galvanized steel, 
with exterior surfaces coated with a non-chalking, powdered 
paint finish, certified at 1000 hours salt spray test per ASTM-
B117 standards. The unit top shall be a single piece “Water 
Shed” design, with drip edges and no-seam corners to pro-
vide optimum water integrity. Unit shall have a rigidly 
mounted condenser coil guard to provide protection from 
objects and personnel after installation. Indoor blower section 
shall be insulated with up to 3/4” thick, aluminum, foil faced 
insulation, fastened to prevent insulation from entering the air 
stream. Cabinet panels shall be “large” size, easily remov-
able for servicing and maintenance, with built-in lift handles. 
Unit shall be built on a formed, “Super-Structure” design base 
pan, with embossments at critical points to add strength, 
rigidity and aid in minimizing sound. Full perimeter base rails 
shall be provided to assure reliable transit of equipment, 
overhead rigging, for truck access and proper sealing on roof 
curb applications. Base rails shall be removable, when 
required, to lower unit height. Filters shall be furnished and 
be accessible through a removable access door, sealed air-
tight. Units vertical discharge and return duct configuration 
shall be designed to fit between standard 24” O.C. beams 
without modification to building structure, duct work and base 
unit. Condensate pan shall be internally sloped and conform 
to ASHRAE 62-89 self-draining standards, with 3/4” NPTI 
copper, ridged mount connection.

INDOOR (EVAPORATOR) FAN ASSEMBLY

Fan shall be direct drive, multi-speed design. Job site 
selected (BHP) brake horsepower shall not exceed the 
motors nameplate horsepower rating. Fan wheel shall be 
double-inlet type with forward-curved blades, dynamically 
balanced to operate smoothly throughout the entire range of 
operation. Airflow design shall be constant air volume. Bear-
ings shall be sealed and permanently lubricated for longer life 
and no maintenance. Fan assembly shall be “Slip Track” 
(slide-out) design for easy removal and cleaning.

OUTDOOR (CONDENSER) FAN ASSEMBLY

The outdoor fan shall be of the direct-driven propeller type, 
discharge air vertically, have aluminum blades riveted to cor-

rosion resistant steel spider bracket and shall be statically 
balanced for smooth operation. The outdoor fan motor shall 
be totally enclosed with permanently lubricated bearings and 
internally protected against overload conditions.

REFRIGERANT COMPONENTS

Compressors: 

a.

Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over
temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or
- 10% of the unit nameplate voltage.

b.

Shall have internal isolation and sound muffling to
minimize vibration and noise, and be externally iso-
lated on a dedicated, independent mounting.

Coils: 

a.

Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless
internally enhanced copper tubes with all joints
brazed.

b.

Evaporator coil shall be of the direct expansion,
blow through design, while condenser coil shall be
draw through design.

Refrigerant Circuit and Refrigerant Safety Components:

a.

Shall include independent fixed-orifice expansion
devices.

b.

Shall include filter/strainer to eliminate any foreign
matter.

UNIT OPERATING CHARACTERISTICS

Unit shall be capable of starting and running at 125º F out-
door temperature, exceeding maximum load criteria ARI 
Standard 210/240. The compressor, with standard controls, 
shall be capable of operation down to 45º F outdoor tempera-
ture. Accessory low ambient kit shall be available for opera-
tion to 0º F.

ELECTRICAL REQUIREMENTS

All unit power wiring shall enter unit cabinet at a single factory 
provided location and be capable of side or bottom entry, to 
minimize roof penetrations and avoid unit field modifications. 
Separate side and bottom openings shall be provided for the 
control wiring.

Summary of Contents for AFFINITY 018N03606

Page 1: ...Series packaged units are designed to han dle applications ranging from residential to light commercial and any in between The Affinity is a unit that gives you the flexibility and choices you need in...

Page 2: ...2 TON 8 5 DNA030 COOLING CAPACITIES 2 1 2 TON 9 6 DNA036 COOLING CAPACITIES 3 TON 10 7 DNA042 COOLING CAPACITIES 3 1 2 TON 11 8 DNA048 COOLING CAPACITIES 4 TON 12 9 DNA060 COOLING CAPACITIES 5 TON 13...

Page 3: ...ENSATE PAN A non corrosive long lasting water tight pan is positioned below the evaporator coil to collect and drain all condensate Less collection of stagnate condensate will build up The condensate...

Page 4: ...em No final field mounting required EASY SERVICE ACCESS A large single panel covers the electrical and gas controls makes servicing easy The blower compartment has an additional large panel with a bui...

Page 5: ...DOOR DAMPER Provides 0 through 50 outdoor air capability field adjustable Designed for duct mounted side supply return applications Includes hood and screen assembly WALL THERMOSTAT The units are desi...

Page 6: ...R RECIPROCATING S SCROLL R R R R R S S 1 See FILTER FRAME KIT on page 5 TABLE 2 RATINGS COOLING GAS HEATING MODEL DNA NET COOLING CAPACITY1 SOUND RATING dbels 2 GAS HEAT CAPACITY EFFICIENCIES MBH EER...

Page 7: ...1 Entering Dry Bulb F 86 9 4 11 7 13 3 13 1 10 2 12 8 14 0 13 9 11 1 13 9 14 8 14 7 11 1 14 1 15 2 15 1 11 1 14 3 15 6 15 5 83 8 5 10 9 12 9 12 9 9 3 11 9 13 8 13 8 10 1 12 9 14 8 14 7 10 3 13 3 15 2...

Page 8: ...0 16 4 18 1 18 0 14 2 17 8 18 8 18 8 15 3 19 2 19 5 19 6 15 3 19 5 19 8 19 9 15 4 19 8 20 1 20 1 83 11 9 15 2 17 7 17 5 12 9 16 5 18 6 18 6 13 9 17 8 19 5 19 6 14 3 18 4 19 8 19 9 14 6 19 0 20 1 20 1...

Page 9: ...15 9 20 0 20 6 20 1 17 7 22 3 22 5 21 9 19 6 24 7 24 4 23 8 19 5 24 9 24 7 24 0 19 5 25 1 25 0 24 3 83 14 4 18 5 20 5 19 9 16 1 20 7 22 5 21 8 17 8 22 9 24 4 23 8 18 2 23 5 24 7 24 0 18 6 24 1 25 0 24...

Page 10: ...21 1 27 2 29 8 28 8 22 4 28 7 30 6 29 5 23 7 30 3 31 3 30 2 23 2 30 1 31 7 30 6 22 8 29 8 32 1 30 9 83 19 4 25 4 29 3 28 4 20 5 26 8 30 3 29 3 21 6 28 2 31 3 30 2 21 6 28 5 31 7 30 6 21 7 28 7 32 1 3...

Page 11: ...86 23 6 29 4 31 7 31 8 25 7 32 0 33 3 33 7 27 8 34 6 34 8 35 6 28 0 35 1 35 6 36 4 28 1 35 7 36 5 37 3 83 21 5 27 3 30 9 30 9 23 4 29 7 32 9 32 9 25 3 32 1 34 8 35 0 26 1 33 2 35 6 36 2 26 8 34 4 36...

Page 12: ...6 26 7 34 8 35 7 36 0 30 1 38 1 37 2 37 5 33 4 41 5 38 8 39 1 36 1 42 5 39 2 39 5 38 8 43 6 39 7 40 0 83 23 3 31 3 35 3 35 6 26 0 34 9 37 0 37 3 28 7 38 4 38 8 39 1 30 8 40 5 39 2 39 5 32 8 42 6 39 7...

Page 13: ...b F 86 36 1 45 1 45 0 42 7 39 9 48 7 46 8 44 3 43 7 52 3 48 5 45 9 46 9 53 0 49 0 46 4 50 1 53 6 49 5 46 9 83 31 8 40 8 44 8 42 6 34 9 44 6 46 7 44 2 37 9 48 4 48 5 45 9 40 3 50 5 49 0 46 4 42 6 52 6...

Page 14: ...des allowances for a dry evaporator coil gas heat exchanger and no filters For additional pressure drops refer to Table 12 and 13 TABLE 11 BOTTOM SUPPLY AIR BLOWER PERFORMANCE1 MODEL DNA MTR SPD EXTER...

Page 15: ...s CFM during full economizer operation TABLE 13 ADDITIONAL STATIC PRESSURE RESISTANCE 4 5 TON DNA048 060 1 DESCRIPTION RESISTANCE IWG CFM 500 600 700 800 900 1 000 1 100 1 200 1 300 1 400 1 500 1 600...

Page 16: ...FACTOR TRANSFORMER SIZE VA MIN MAX RLA LRA 018 208 230 1 60 187 253 9 0 48 0 1 1 2 2 14 5 20 20 96 40 024 208 230 1 60 187 253 11 5 60 0 1 1 2 2 17 7 25 25 96 40 030 208 230 1 60 187 253 14 7 73 0 1 1...

Page 17: ...I N L E T L O U V E R S F R O N T G A S E L E C T R I C C O N T R O L S E R V I C E A C C E S S C O M P A R T M E N T P A N E L O V E R A L L O V E R A L L All dimensions are in inches They are subjec...

Page 18: ...D R A I N 3 4 N P T I G A S S U P P L Y 1 5 8 D I A K N O C K O U T 1 2 N P T I C O N N E C T I O N L O W V O L T A G E C O N N 1 8 D I A K N O C K O U T 1 3 4 1 5 2 9 9 1 6 1 5 3 1 2 1 3 4 1 3 4 1 5...

Page 19: ...L G A S S H U T O F F V A L V E R E T U R N A I R D U C T S U P P L Y A I R D U C T C O N T R O L W I R I N G T O I N D O O R T H E R M O S T A T T O P O W E R S U P P Y M A N U A L G A S S H U T O F...

Page 20: ...U N D I N S T A L L A T I O N TABLE 17 UNIT WEIGHTS AND CENTER OF GRAVITY UNIT SIZE SHIPPING WEIGHT lbs OPERATING WEIGHT lbs CORNER WEIGHTS location lbs ECONOMIZER lbs ROOF CURB lbs A B C D 018 365 3...

Page 21: ...1 8 X 2 1 1 2 R E C O M M E N D E D D U C T S I Z E 1 7 1 2 X 1 6 3 4 1 8 Roof curb also available 3 4 X 1 W I D E G A S K E T I N G F O R C U R B F R A M E A N D A L L D U C T S U P P O R T S U R F A...

Page 22: ...292443 XTG B 0807 22 Unitary Products Group FIGURE 14 TYPICAL WIRING DIAGRAM DNA 018 THRU 060 208 230 1 60 POWER SUPPLY...

Page 23: ...facility YORK s Affinity package units are designed to handle applications ranging from residential to light commercial and any in between The Affinity is a unit that gives you the flexibility and cho...

Page 24: ...Y Fan shall be direct drive multi speed design Job site selected BHP brake horsepower shall not exceed the motors nameplate horsepower rating Fan wheel shall be double inlet type with forward curved b...