292443-XTG-B-0807
16
Unitary Products Group
FIGURE 4 - TYPICAL FIELD POWER WIRING DIAGRAM
REFER TO ELECTRICAL
DATA TABLES TO SIZE
THE DISCONNECT
TABLE 14: ELECTRICAL DATA
MODEL
DNA
POWER
SUPPLY
VOLTAGE
LIMITATIONS
1
COMPRESSOR
COND.
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
AMPS
2
MAX.
HACR
BREAKER
SIZE,
AMPS
UNIT
POWER
FACTOR
TRANSFORMER
SIZE (VA)
MIN.
MAX.
RLA
LRA
018
208/230-1-60
187
253
9.0
48.0
1.1
2.2
14.5
20
20
.96
40
024
208/230-1-60
187
253
11.5
60.0
1.1
2.2
17.7
25
25
.96
40
030
208/230-1-60
187
253
14.7
73.0
1.1
2.2
21.7
30
30
.96
40
036
208/230-1-60
187
253
17.3
94.0
1.1
3.5
26.2
35
35
.96
40
042
208/230-1-60
187
253
20.5
120.0
1.1
3.5
30.2
40
40
.96
40
048
208/230-1-60
187
253
24.4
140.0
1.3
7.0
38.8
50
50
.96
40
060
208/230-1-60
187
253
28.9
175.0
1.3
7.0
44.4
60
60
.96
40
1. Utilization range “A” in accordance with ARI Standard 110.
2. Dual element, time delay type.