background image

035-17737-003 Rev. A (0504)

Unitary Products Group

5

SECTION II: SERVICE AND MAINTENANCE 

MANUAL

SAFETY SECTION

The following safety rules must be followed when servicing the
furnace.

FURNACE MAINTENANCE SECTION

The furnace should be cleaned and adjusted by a certified dealer or
qualified service contractor once a year or before the start of every
heating season. The following items must be cleaned and serviced or
replaced if there are signs of deterioration.

1.

The vent terminal.

2.

The furnace vent and combustion air intake passageways. Should
it be necessary to service the vent/air intake system, the manufac-
turer recommends this service be conducted by a qualified service
agency. The operation of this appliance requires the reassembly
and resealing of the vent/air intake system.

3.

The furnace burners, ignitor and flame sensor.

4.

The condensate collection and disposal system. If any disassem-
bly of components containing flue or vent gases is required, a
qualified service agency must perform the service.

SEQUENCE OF OPERATION

The following describes the sequence of operation of the furnace. Refer
to Figure 1 for component location.

Continuous Blower

Cooling/heating thermostats have a fan switch that has an ON and
AUTO position. In the ON position the thermostat circuit is completed
between terminals R and G. The motor will operate on the speed tap
wire that is connected to the cooling terminal on the control board.

Intermittent Blower - Cooling

Cooling/heating thermostats have a fan switch that has an ON and
AUTO position. In the AUTO position the thermostat circuit is completed
between terminals R and G when there is a call for cooling. The motor
will operate on the speed tap wire that is connected to the cooling termi-
nal on the control board. The fan off setting is fixed at 60 seconds for
SEER enhancement.

Heating Cycle

When the thermostat switch is set on HEAT and the fan is set on AUTO,
and there is a call for heat, a circuit is completed between terminals R
and W of the thermostat. When the proper amount of combustion air is
being provided, the pressure switch will close, the ignition control pro-
vides a 17-second warm-up period, the gas valve then opens, the gas
starts to flow, ignition occurs and the flame sensor begins its sensing
function. The blower motor will energize 30 seconds after the gas valve
opens, if a flame is detected. Normal furnace operation will continue
until the thermostat circuit between R and W is opened, which causes
the ignition system and gas valve to de-energize and the burner flames
to be extinguished. The vent motor will operate for an additional 15 sec-
onds and the blower motor will operate for the amount of time set by the
fan-off delay jumper located on the control board. See Figure 6. The
heating cycle is complete, and ready for the start of the next heating
cycle.

If the flame is not detected within 7 seconds of the gas valve opening,
the gas valve is shut off and a retry operation begins. If the flame is lost
for 2 seconds during the 10-second stabilization period, the gas valve is
shut off and a retry operation begins. During a retry operation, the vent
motor starts a 15 second inter-purge and the ignitor warm-up time is
extended to 27 seconds. If the flame is established for more than 10
seconds after ignition during a retry, the control will clear the ignition
attempt (retry) counter. If three retries occur during a call for heat, the
furnace will shut down for one hour. If at the end of the one hour shut
down there is a call for heat, the furnace will initiate a normal start cycle.
If the problem has not been corrected the furnace will again lockout
after three retries.

A momentary loss of gas supply, flame blowout, or a faulty flame probe
circuit will result in a disruption in the flame and be sensed within 1.0
seconds. The gas valve will de-energize and the control will begin a
recycle operation. A normal ignition sequence will begin after a 15 sec-
ond inter-purge. If during the five recycles the gas supply does not
return, or the fault condition is not corrected the ignition control will lock-
out for 60 minutes.

During burner operation, a momentary loss of power for 50 milliseconds
or longer will de-energize the gas valve. When the power is restored,
the gas valve will remain de-energized and the ignition sequence will
immediately restart.

ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in
dangerous operation, serious injury, death or property
damage.
Improper servicing could result in dangerous operation,
serious injury, and death or property damage.

Before servicing, disconnect all electrical power to the fur-
nace. 

When servicing controls, label all wires prior to disconnect-
ing. Reconnect wires correctly. 

Verify proper operation after servicing.

 FIGURE 6: 

Typical Heat/Cool Speed Tap Connections

P

ARK

P

ARK

HI

COOL

HEA

T

EAC

L1

XFMR

HUM

NEUTRALS

RED - LOW SPEED

YELLOW - MED. LOW SPEED

BLACK - HIGH SPEED
BLUE -MED. HIGH SPEED

FAN OFF
ADJUSTMENT
JUMPER

Y/Y2 W

R

G

C

Summary of Contents for 92% GF9

Page 1: ...wet or the furnace if deemed necessary FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Do not store or use gasoline or other...

Page 2: ...nace casing making sure the physical support is sound without sagging cracks or gaps Examine the furnace base making sure it is physically sound without cracks gaps or sagging and has a good seal 5 Ex...

Page 3: ...es to clear out any gas If you then smell gas STOP Follow B in the safety information above If you don t smell gas go to next step 7 Move gas control switch to the ON position Do not force See Figure...

Page 4: ...e cabinet Some installations may have the air filter in a rack attached to the cas ing of the furnace or placed in the return air duct If the filter location or replacement process is not obvious cont...

Page 5: ...nue until the thermostat circuit between R and W is opened which causes the ignition system and gas valve to de energize and the burner flames to be extinguished The vent motor will operate for an add...

Page 6: ...em by setting the thermostat above the room temperature Observe the system s response Then use the troubleshooting section in this manual to check the system s operation FURNACE CONTROL DIAGNOSTICS Th...

Page 7: ...s 6 7 8 will be reset This provides protection to an unoccupied structure if a temporary condition exists causing a furnace malfunction An example would be a low incoming gas supply pressure preventin...

Page 8: ...ry Products Group SECTION III REPLACEMENT PARTS LIST 11 5 1 15 16 3 14 4 2 6 10 9 12 13 7 32 27 54 40 25 52 21 26 29 38 34 35 30 46 22 20 62 17 57 51 59 64 61 55 41 65 48 45 24 63 23 14 58 19 9 37 28...

Page 9: ...ay 188 ID 2 ft req d 41 TUBING SILICONE Clear with insert 1 3 ft req d 42 GASKET AIR INTAKE 43 GASKET COMBUSTION BLOWER 44 GASKET CONDENSATE PAN 45 GASKET UPPER CONDENSATE PAN 46 GASKET GAS CONTROLS 4...

Page 10: ...R0324 1NK0301 CONDENSATE NEUTRALIZER KIT 1SF0101 EXTERNAL SIDE RETURN FILTER RACK GF9 ONLY REPLACEMENT PART CONTACT INFORMATION This is a generic parts list To request a complete parts list refer to t...

Page 11: ...035 17737 003 Rev A 0504 Unitary Products Group 11 SECTION IV WIRING DIAGRAM FIGURE 8 Wiring Diagram...

Page 12: ...s only to products installed in the United States and Canada EXCLUSIONS This warranty does not cover any 1 Shipping labor or material charges 2 Damages resulting from transportation installation or se...

Reviews: