background image

5121495-UIM-D-0516

Johnson Controls Unitary Products

9

FIELD CONNECTIONS CONTROL WIRING

1.

Route low voltage wiring into bottom of control box as shown in
Figure 9 or 10. Make low voltage wiring connections inside the low
voltage box per Figure 11.

2.

The complete connection diagram and schematic wiring label is
located on the inside surface of the unit service access panel.

3.

Replace the control box cover removed in Step 2 of the FIELD
CONNECTINS POWER WIRING procedures.

4.

All field wiring to be in accordance with national electrical codes

(NEC) and/or local-city codes.

5.

Mount the thermostat about 5 ft. above the floor, where it will be
exposed to normal room air circulation. Do not place it on an out-
side wall or where it is exposed to the radiant effect from exposed
glass or appliances, drafts from outside doors or supply air grilles.

6.

Route the 24-volt control wiring (NEC Class 2) from the outdoor
unit to the indoor unit and thermostat.

DEHUMIDIFICATION CONTROL (Typical)

The indoor unit Installation Manual instructions for the air handler or fur-
nace describe the interface with the outdoor heat pump. A dehumidifi-
cation control accessory 2HU16700124 may be used with variable
speed air handlers or furnaces in high humidity areas. This control
works with the variable speed indoor unit to provide cooling at a
reduced air flow, lowering evaporator temperature and increasing latent
capacity. The humidistat in this control opens the humidistat contacts as
the humidity increases. Installation instructions are packaged with the
accessory. Prior to the installation of the dehumidification control, the
humidistat jumper must be set to ‘YES” on the indoor variable speed air
handler or furnace control board.

During cooling, if the relative humidity in the space is higher than the
desired set point of the dehumidification control, the variable speed
blower motor will operate at lower speed until the dehumidification con-
trol is satisfied. A 40-60% relative humidity level is recommended to
achieve optimum comfort.

If a dehumidification control is installed, it is recommended that a mini-
mum air flow of 325 cfm/ton be supplied at all times.

To see connection diagrams of all UPG equipment, the “Low Voltage
System Wiring” document is available online at www.upgnet.com in the
Product Catalog Section.

INDOOR CUBIC FEET PER MINUTE (CFM) SELEC-

TION BOARD SETTINGS (Typical)

Refer to the indoor unit Installation Manual instructions for the air han-
dler or furnace interface with the outdoor heat pump. Refer to the Out-
door Technical Guide for the recommended indoor air flow settings of
each specific heat pump. For the system to operate correctly, ensure
that the indoor CFM Selection control jumpers are properly set. Set the
indoor cooling fan speed per the instructions for the air handler or fur-
nace by selecting the correct COOL and ADJUST (or ADJ) taps. Verify
the indoor airflow by using the LED display on the indoor CFM selection
board.

SECTION VIII: SYSTEM START-UP

ENERGIZE CRANKCASE HEATER

In order to energize the crankcase heater, set the indoor cooling ther-
mostat to the OFF position. Close the line power disconnect to the unit.

WITH POWER TO UNIT AND THERMOSTAT IN COOLING 
POSITION:

1. In the cooling cycle, discharge gas is pumped to the outdoor coil

which is the condenser. The indoor coil is the evaporator.

2. If fan switch is in ON position, a circuit is made through blower relay

to provide continuous blower operation.

3. With fan switch in AUTO position, a circuit is made from thermostat

cooling contact through blower relay to provide blower operation.

4. System will cycle with thermostat demand to provide cooling as

needed.

NOTICE

A Start Assist Kit is available and recommended for long line set

applications or in areas of known low voltage problems. The kit may
be required when a TXV is used (reference the Tabular Data Sheet
to determine if applicable).

NOTICE

To eliminate erratic operation, seal the hole in the wall at the ther-
mostat with permagum or equivalent to prevent air drafts affecting
the operation of in the thermostat.

 FIGURE 11: 

Typical Field Wiring (Air Handler / Electrical Heat) (Single-Phase)

7+(50267$7

,1'22581,7

287'22581,7

/2:92/7$*(7(50,1$/%/2&.
,1$,5+$1'/(5:,7+(/(&75,&+($7

'()5267
&21752/

),(/'
,167$//('
-803(5

'(+80,',),&$7,21&21752/&211(&7,21
+XPLGLVWDW-XPSHUPXVWEHUHPRYHG

*1'

6&5(:

&217$&725

7

7

/

/

0

5

<

2

:

*

7

(

5

5

<

<

2

2

:

:

&

&

*

:

%.

*1'

/8*

&,5&8,7
%5($.(5

32:(5:,5,1*
9&21752/:,5,1*
1(&&/$66

-803(57(50,1$/6($1':72+($7
21),56767$*('85,1*(0(5*(1&<+($7

7(50,1$/12786('21$//7+(50267$76

32:(5:,5,1*

&+(&.7+(/2:92/7$*(7(50,1$/%/2&.217+(,1'22581,7)257+($&78$/$55$1*(0(172)7+(7(50,1$/6
&211(&732:(5:,5,1*727(50,1$/%/2&.7%2181,76:,7+287(/(&75,&+($725&,5&8,7%5($.(5

%RU&

$//),(/':,5,1*72%(,1$&&25'$1&(:,7+(/(&75,&&2'(1(&$1'25/2&$/&2'(6

5('
%/.

<(/
25*

%51

:+7


$

:RXW

IMPORTANT

An attempt to start the compressor without at least 8 hours of crank-

case heat will damage the compressor.

Summary of Contents for 14 SEER-TH4 SERIES

Page 1: ...ng indoor coils can be used with a thermostatic expansion valve TXV Refer to the Tabular Data Sheet or to the Technical Guide for the proper selection SECTION II SAFETY This is a safety alert symbol W...

Page 2: ...e preferred method is to weigh in the charge For charging or checking the system charge at 55 F or below refer to the Optional Cold Weather Charging procedures near the end of SECTION VI SYSTEM CHARGE...

Page 3: ...ess and serviceability as well as the possible sound and vibration transmission into the structure These applications are best served by a properly engineered solution UNIT PLACEMENT 1 Provide a base...

Page 4: ...internally clean and dry system PRECAUTIONS DURING BRAZING SERVICE VALVE Precautions should be taken to prevent heat damage to service valve by wrapping a wet rag around it as shown in Figure 4 Also...

Page 5: ...ischarged loosen and remove the Schrader core 3 Place a backup wrench on distributor loosen and remove brass distributor nut Retain brass nut for use on liquid line Keep teflon washer in place and dis...

Page 6: ...gerant charge added accordingly MEASURE INDOOR AIR FLOW To determine rated air flow for a specific match consult the technical lit erature at www upgnet com When attempting to match this air flow sele...

Page 7: ...control box can swing open by removing the screw from the center of each side of the control box and allowing the control box to lower an inch or so into a pivotal position The control box can then s...

Page 8: ...disconnect switch to the unit 4 Route wires from disconnect through power wiring exit provided and into the unit control box as shown in Figures 9 10 5 Install the proper size time delay fuses or cir...

Page 9: ...www upgnet com in the Product Catalog Section INDOOR CUBIC FEET PER MINUTE CFM SELEC TION BOARD SETTINGS Typical Refer to the indoor unit Installation Manual instructions for the air han dler or furna...

Page 10: ...owing table summarizes the behavior of the control when the two TEST pins are connected More detailed descriptions of the various functions are included in other sec tions of this document TABLE 3 TES...

Page 11: ...arrangement of the refrigeration circuit within the coil The control may initiate a defrost cycle even when the coil is not completely cov ered with frost This is normal operation The control regulat...

Page 12: ...cur regardless of the liq uid line coil temperature reading The coil does not have to be cold for the unit to be forced into defrost Once the defrost cycle begins the con trol shall follow the normal...

Page 13: ...h code The control will reset the soft lockout condition when any of the follow ing occur after removal of the fault condition 1 Power is cycled to the R or Y inputs of the control This will cause the...

Page 14: ...AL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL DUAL CAPACITOR SHOWN SEPARATE CAPACITORS MAY BE USED ON ACTUAL UNIT WIRING MUS...

Page 15: ...5121495 UIM D 0516 Johnson Controls Unitary Products 15 NOTES...

Page 16: ...plicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is connecte...

Page 17: ...mp Cut Out Balance Point Defrost Curve Y2 Lock FFUEL Switch Point Hot Heat Pump Fill in the information ie ON OFF or the appropriate Value for the fields that apply to the defrost control board instal...

Page 18: ...des 5121495 UIM C 0316 York International Corp 5005 York Drive Norman OK 73069 Explain operation of system to equipment owner Explain the importance of regular filter replacement and equipment mainten...

Reviews: