14
TI 04R01B01-01EN
Dec. 12, 2011-00
6. Configure the settings shown in Table 5 for the respective parameters of AI1 Temp. When configuration of the
respective parameters is complete, click [Apply parameters] ([Download to device] for R2.04.01).
Table 5 Parameter Settings
Item
Parameter
AI1 Temp to AI8 Temp
Scale High Limit
Scale.EU at 100%
100.0
Scale Low Limit
Scale.EU at 0%
0.0
Unit
Scale Unit Index
°C (degC)
Input Type
Lin Type
Type K
Data Type
Process Value Type
Direct
7. Select the checkbox for Auto in [Mode. Target] of [Block Mode] and click [Apply parameters].
8. Repeat steps 4 to 7 for setting AI1 Temp to configure the settings for AI2 Temp to AI8 Temp.
9. When configuration of the respective settings is complete, click the connection/disconnection icon (disconnect)
in DTM Works to exit DTM Works.