background image

IM 05P01D31-81EN   page 12/12

■ SELECT Display Setting Parameter

Menu symbol: 

 (CSEL)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

 to 

(CS1 to CS5)

SELECT Display-1 to -5 

registration

Register the operation parameter 

(except the Operation Mode) that is 

frequently modified to display it in the 

Operation Display.

 

OFF, 2301 to 5000, 6701 to 6710

 

For the setting range, see Communi-

cation User's Manual.

OFF

Table 

below

STD

Use the following table to record SELECT Display setting value.

Parameter

n=1

n=2

n=3

n=4

n=5

CSn

■ Key Lock Setting Parameter 

Menu symbol: 

 (KLOC)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(COM.W)

Communication write 

enable/disable

OFF: Enable, ON: Disable

OFF

STD

(DATA)

Front panel parameter 

data (▼,▲) key lock

OFF: Unlock, ON: Lock

OFF

(A/M)

Front panel A/M key lock

OFF

■ DI Function Registration Parameter

Menu symbol: 

 (DI.SL)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(A/M)

AUTO/MAN switch

Set an I relay number of contact 

input.

Set “OFF” to disable the function.

Standard terminals

DI1: 5025, DI2: 5026

E1-terminal area

 

DI11: 5041, DI12: 5042, DI13: 5043, 

DI14: 5044, DI15: 5045

5025

STD

(R/L)

REMOTE/LOCAL switch

OFF

(S/R)

STOP/RUN switch 

5026

(AUTO)

Switch to AUTO

OFF

(MAN)

Switch to MAN

OFF

(REM)

Switch to REMOTE

OFF

(LCL)

Switch to LOCAL

OFF

(AT)

Auto-tuning START/STOP 

switch

OFF

(LAT)

Latch release

OFF

(LCD)

LCD backlight ON/OFF 

switch

OFF

(PVRW)

PV red/white switch

OFF

■ DI Function Numbering Parameter

Menu symbol: 

 (DI.NU)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(SP.B0)

Bit-0 of SP number

Set an I relay number of contact input.

 

Set “OFF” to disable the function.

 

Standard terminals 

DI1: 5025, DI2: 5026

E1-terminal area

 

DI11: 5041, DI12: 5042, DI13: 5043, 

DI14: 5044, DI15: 5045

OFF

EASY

(SP.B1)

Bit-1 of SP number

OFF

(SP.B2)

Bit-2 of SP number

OFF

(PN.B0)

Bit-0 of PID number

OFF

STD

(PN.B1)

Bit-1 of PID number

OFF

(PN.B2)

Bit-2 of PID number

OFF

(MP.B0)

Bit-0 of manual preset 

output number

OFF

(MP.B1)

Bit-1 of manual preset 

output number

OFF

(MP.B2)

Bit-2 of manual preset 

output number

OFF

(SP.BC)

Bit changing method of SP 

number

0: Status switch 1

 

1: Status switch 2

0

STD

■ AL1-AL3 Function Registration Parameter

Menu symbol: 

 (ALM)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(AL1.S)

AL1 function selection

Set an I relay number. For the items 

other than below, see Communication 

User's Manual.

Ex.) Set the number 4353 for AL1.S 

to use the alarm 1.

Set “OFF” to disable the function.

No function: OFF

Alarm 1: 4353

Alarm 2: 4354

Alarm 3: 4355

Alarm 4: 4357

AUTO (OFF) / MAN (ON) status: 4193

REM (ON) / LCL (OFF) status: 4194

STOP (ON) / RUN (OFF) status: 4195

FAIL (Normally ON) output: 4256

4353

STD

(AL2.S)

AL2 function selection

4354

(AL3.S)

AL3 function selection

4355

(OR.S)

OUT relay function 

selection 

OFF

(OR2.S)

OUT2 relay function 

selection

OFF

■ DO Setting Parameter (E1/E4-terminal Area)

Menu symbol: 

 (DO)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(DO1.S)

DO11/DO41 function 

selection

Same as AL1.S

Set “OFF” to disable the function

OFF

Table 

below

STD

(DO2.S)

DO12/DO42 function 

selection

OFF

(DO3.S)

DO43 function selection

OFF

(DO4.S)

DO44 function selection

OFF

(DO5.S)

DO45 function selection

OFF

Use the following table to record DO setting value.

Parameter

E1-terminal Area

E4-terminal Area

DO1.S
DO2.S
DO3.S
DO4.S
DO5.S

■ System Setting Parameter

Menu symbol: 

 (SYS)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(R.MD)

Restart mode

Set how the controller should recover 

from a power failure of 5 seconds or 

more.

CONT: Continue action set before 

power failure.

MAN: Start from MAN.

AUTO: Start from AUTO.

CONT

STD

(R.TM)

Restart timer

Set time between power on and the 

instant where controller starts compu

-

tation. 

0 to 10 s

0

(EPO)

Input error preset output

Set preset output value when the 

input burnout or ADC error occurs. 

Manual output is prioritized when the 

input burnout occurs in MAN.

0: Preset output

 

1: 0% output

 

2: 100% output

0

(FREQ)

Power frequency

AUTO, 60: 60 Hz, 50: 50 Hz

AUTO

EASY

(QSM)

Quick setting mode

OFF: Disable

 

ON: Enable

ON

(LANG)

Guide display language

ENG: English

FRA: French

GER: German

SPA: Spanish

Depe-

nds 

on the 

model 

and 

suffix 

codes

(PASS)

Password setting

0 (No password) to 65535

0

■ Error and Version Confirmation Parameter (for display only)

Menu symbol: 

 (VER)

Parameter 

symbol

Name of Parameter

Status record

Display 

level

(PA.ER)

Parameter error status

EASY

(OP.ER)

Option error status

(AD1.E)

A/D converter error status 1 

(AD2.E)

A/D converter error status 2 

(PV1.E)

PV input error status

(LA.ER)

Ladder error status 

(MCU)

MCU version

(DCU)

DCU version

(ECU1)

ECU-1 version (E1-terminal area)

(ECU3)

ECU-3 version (E3-terminal area)

(ECU4)

ECU-4 version (E4-terminal area)

(PARA)

Parameter version

(H.VER)

Product version

(

SER1

)

Serial number 1

(SER2)

Serial number 2 

(MAC1)

MAC address 1 (E3-terminal area)

(MAC2)

MAC address 2 (E3-terminal area)

(MAC3)

MAC address 3 (E3-terminal area)

■ Parameter Display Level Parameter

Menu symbol: 

 (LVL)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(LEVL)

Parameter display level

EASY: Easy setting mode

STD: Standard setting mode

PRO: Professional setting mode

STD

EASY

* For Professional setting mode, see User’s Manual.

Trademarks

● Our product names or brand names mentioned in this manual are 

  the trademarks or registered trademarks of Yokogawa Electric Corporation.

● Adobe, Acrobat, and Postscript are either registered trademarks or trademarks

  of Adobe Systems Incorporated.

● Ethernet is a registered trademark of XEROX Corporation in the United States.

● Modbus is a registered trademark of Schneider Electric.

● PROFIBUS-DP is a registered trademark of PROFIBUS User Organization.

● DeviceNet is a registered trademark of Open DeviceNet Vendor Association.

● CC-Link is a registered trademark of CC-Link Partner Association.

● We do not use the TM or ® mark to indicate these trademarks or 

  registered trademarks in this manual.

● All other product names mentioned in this manual are trademarks

  or registered trademarks of their respective companies.

•  Authorised Representative in the EEA

  Yokogawa  Europe  BV.  (Address:  Euroweg  2  ,  3825  HD Amersfoort,  The 

Netherlands) is the Authorised Representative of Yokogawa Electric Corporation 

for this Product in the EEA.

•  Printed Manuals

Model

Description

UT35A, UT32A Digital Indicating Controller  (Panel Mounting Type) Operation Guide 

«

Standard Code Model

»

IM 05P01D31-11EN

UT35A, UT32A Digital Indicating Controller  (Panel Mounting Type) Operation 

Guide 

«

Detailed Code Model

»

IM 05P01D31-15EN

UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN Rail Mounting Type) 

Operation Guide 

«

Standard Code Model

»

IM 05P01D81-11EN

UT32A-D Digital Indicating Controller (Dual-loop, Panel Mounting Type) 

Operation Guide 

«

Standard Code Model

»

IM 05P08D31-11EN

UT32A-D/MDL Digital Indicating Controller (Dual-loop, DIN Rail Mounting Type) 

Operation Guide 

«

Standard Code Model

»

IM 05P08D81-11EN

UT35A/RSP, UT32A/RSP Digital Indicating Controller (Non-isolated Remote 

Input, Panel Mounting Type) Operation Guide 

«

Standard Code Model

»

IM 05P01D31-81EN

UT32A Digital Indicating Controller Operation Guide 

«

Entry Model

»

IM 05P01F31-11EN

Precautions on the Use of the UTAdvanced Series

IM 05P01A01-11EN

•  Electronic Manuals

  You can download the latest manuals from the following website:

  URL: http://www.yokogawa.com/ns/ut/im/

Model

Description

UT35A, UT32A Digital Indicating Controller  (Panel Mounting Type) Operation Guide 

«

Standard Code Model

»

IM 05P01D31-11EN

UT35A, UT32A Digital Indicating Controller  (Panel Mounting Type) Operation 

Guide 

«

Detailed Code Model

»

IM 05P01D31-15EN

UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN Rail Mounting Type) 

Operation Guide 

«

Standard Code Model

»

IM 05P01D81-11EN

UT35A/UT32A Digital Indicating Controller User’s Manual

IM 05P01D31-01EN

UT32A-D Digital Indicating Controller (Dual-loop, Panel Mounting Type) 

Operation Guide 

«

Standard Code Model

»

IM 05P08D31-11EN

UT32A-D/MDL Digital Indicating Controller (Dual-loop, DIN Rail Mounting Type) 

Operation Guide 

«

Standard Code Model

»

IM 05P08D81-11EN

UT32A-D, UT32A-D/MDL Digital Indicating Controller User’s Manual

IM 05P08D31-01EN

UT35A/RSP, UT32A/RSP Digital Indicating Controller (Non-isolated Remote 

Input, Panel Mounting Type) Operation Guide 

«

Standard Code Model

»

IM 05P01D31-81EN

UT32A Digital Indicating Controller Operation Guide 

«

Entry Model

»

IM 05P01F31-11EN

UT32A Digital Indicating Controller User’s Manual 

«

Entry Model

»

IM 05P01F31-01EN

UTAdvanced Series Communication Interface (RS-485, Ethernet) User’s Manual IM 05P07A01-01EN
UTAdvanced Series Communication Interface (Open Network) User’s Manual

IM 05P07A01-02EN

LL50A Parameter Setting Software Installation Manual

IM 05P05A01-01EN

LL50A Parameter Setting Software User’s Manual

IM 05P05A01-02EN

Precautions on the Use of the UTAdvanced Series

IM 05P01A01-11EN

•  General Specification

Model

Description

UT35A, UT32A Digital Indicating Controller (Panel Mounting Type)

GS 05P01D31-01EN

UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN Rail Mounting Type) GS 05P01D81-01EN
UT32A-D Digital Indicating Controller (Dual-loop, Panel Mounting Type)

GS 05P08D31-01EN

UT32A-D/MDL Digital Indicating Controller (Dual-loop, DIN Rail Mounting Type) GS 05P08D81-01EN
LL50A Parameter Setting Software

GS 05P05A01-01EN

The last two characters of the manual number and general specification number indicate the 

language in which the manual is written.

Summary of Contents for UT32A/RSP

Page 1: ...rman French and Spanish are available for the guide display 2 The LP option can be specified in the combination of Type 2 code any of 0 or 1 and Type 3 code any of 0 or 1 3 The HA option can be specified only when the Type 1 code is 0 or 2 4 When the CT option is specified the UT35A does not conform to the safety standards UL and CSA and CE marking Products with CT option are not intended for EEA ...

Page 2: ...input for com putation etc Number of inputs See the table of Model and Suffix Codes Input type instrument range and measurement accuracy See the table below Input Type Instrument Range Accuracy Standard signal 0 400 to 2 000 V 0 2 of instrument range 1 digit 1 000 to 5 000 V 0 1 of instrument range 1 digit DC voltage 0 000 to 2 000 V 0 2 of instrument range 1 digit 0 00 to 10 00 V 0 1 of instrumen...

Page 3: ...ires for wiring For RTD input use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires Since the control output relay has a life span resistance load of 100 000 times use the auxiliary relay to perform ON OFF control The use of inductance L loads such as auxiliary relays motors and solenoid valves causes malfunction or relay f...

Page 4: ... Relay contact output NC NO COM Contact rating 250 V AC 3 A 30 V DC 3 A resistance load 111 301 302 303 304 305 306 307 308 309 310 311 312 201 202 203 204 205 206 207 208 210 101 102 103 104 105 106 107 108 109 110 211 212 Current voltage pulse output 0 20 mA DC 4 20 mA DC Voltage pulse 12 V Heating cooling control output Suffix code Type 1 2 Cooling side control output Heating cooling relay cont...

Page 5: ...ntrol type setup Input output setup Valve position adjustment Use Quick setting function Position proportional type Position proportional type For Position proportional type 3 Quick Setting Function Setting of Input and Output The Quick setting function is a function to easily set the basic function of the control ler Turn on the controller to start the Quick setting function This function allows ...

Page 6: ...RM menu is displayed 1 2 3 4 5 The parameter AL1 alarm 1 type is displayed Press the SET ENTER key Press the SET ENTER key 5 6 Energized De energized Latch action Stand by action The alarm 1 type setpoint 02 PV low limit is registered After the setup is completed press the DISPLAY key or DISP key once to return to the Operation Display Symbol To change the alarm type change the last 2 digits of th...

Page 7: ... User s Manual IM 05P01D31 01EN The MAN lamp goes off which means that the auto tuning completed normally 5 6 7 8 The setting range is 1 to 4 represent group numbers or R To perform auto tuning for the PID of group 1 set the parameter AT to 1 To quit the auto tuning set the parameter to OFF During auto tuning The MAN lamp blinks The OUT symbol appears The output values at 100 0 and 0 appear altern...

Page 8: ...ystem data and hardware of extended function Nonresponding communication between hardware of extended function E1 to E4 terminal areas Faulty Contact us for repair Normal indication Normal indication Rightmost decimal point on PV display blinks Setup parameter PA ER Calibration value error Initialized to calibrated default value because of corrupted factory default value Faulty Contact us for repa...

Page 9: ...Without Stand by action 0 PV low limit 02 Table below EASY Alarm type 2 digits 00 Disable 01 PV high limit 02 PV low limit 03 SP high limit 04 SP low limit 05 Deviation high limit 06 Deviation low limit 07 Deviation high and low limits 08 Deviation within high and low limits 09 Target SP high limit 10 Target SP low limit 11 Target SP deviation high limit 12 Target SP deviation low limit 13 Target ...

Page 10: ...re not described in this manual See User s Manual IM 05P01D31 01EN Control Function Setting Parameter Menu symbol CTL Parameter symbol Name of Parameter Setting Range Initial value User setting Display level CNT Control type PID PID control ONOF ON OFF control 1 point of hysteresis ONOF2 ON OFF control 2 points of hysteresis 2P2L Two position two level control H C Heating cooling control PID or H ...

Page 11: ...cation with checksum LADR Ladder communication CO M Coordinated master station CO S Coordinated slave station MBASC Modbus ASCII MBRTU Modbus RTU CO S1 Coordinated slave station Loop 1 mode CO S2 Coordinated slave station Loop 2 mode P P Peer to peer communication MBRTU EASY BPS Baud rate 600 600 bps 1200 1200 bps 2400 2400 bps 4800 4800 bps 9600 9600 bps 19200 19 2k bps 38400 38 4k bps 19200 PRI ...

Page 12: ...error status LA ER Ladder error status MCU MCU version DCU DCU version ECU1 ECU 1 version E1 terminal area ECU3 ECU 3 version E3 terminal area ECU4 ECU 4 version E4 terminal area PARA Parameter version H VER Product version SER1 Serial number 1 SER2 Serial number 2 MAC1 MAC address 1 E3 terminal area MAC2 MAC address 2 E3 terminal area MAC3 MAC address 3 E3 terminal area Parameter Display Level Pa...

Reviews: