IM 05P01D31-81EN page 12/12
■ SELECT Display Setting Parameter
Menu symbol:
(CSEL)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
to
(CS1 to CS5)
SELECT Display-1 to -5
registration
Register the operation parameter
(except the Operation Mode) that is
frequently modified to display it in the
Operation Display.
OFF, 2301 to 5000, 6701 to 6710
For the setting range, see Communi-
cation User's Manual.
OFF
Table
below
STD
Use the following table to record SELECT Display setting value.
Parameter
n=1
n=2
n=3
n=4
n=5
CSn
■ Key Lock Setting Parameter
Menu symbol:
(KLOC)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(COM.W)
Communication write
enable/disable
OFF: Enable, ON: Disable
OFF
STD
(DATA)
Front panel parameter
data (▼,▲) key lock
OFF: Unlock, ON: Lock
OFF
(A/M)
Front panel A/M key lock
OFF
■ DI Function Registration Parameter
Menu symbol:
(DI.SL)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(A/M)
AUTO/MAN switch
Set an I relay number of contact
input.
Set “OFF” to disable the function.
Standard terminals
DI1: 5025, DI2: 5026
E1-terminal area
DI11: 5041, DI12: 5042, DI13: 5043,
DI14: 5044, DI15: 5045
5025
STD
(R/L)
REMOTE/LOCAL switch
OFF
(S/R)
STOP/RUN switch
5026
(AUTO)
Switch to AUTO
OFF
(MAN)
Switch to MAN
OFF
(REM)
Switch to REMOTE
OFF
(LCL)
Switch to LOCAL
OFF
(AT)
Auto-tuning START/STOP
switch
OFF
(LAT)
Latch release
OFF
(LCD)
LCD backlight ON/OFF
switch
OFF
(PVRW)
PV red/white switch
OFF
■ DI Function Numbering Parameter
Menu symbol:
(DI.NU)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(SP.B0)
Bit-0 of SP number
Set an I relay number of contact input.
Set “OFF” to disable the function.
Standard terminals
DI1: 5025, DI2: 5026
E1-terminal area
DI11: 5041, DI12: 5042, DI13: 5043,
DI14: 5044, DI15: 5045
OFF
EASY
(SP.B1)
Bit-1 of SP number
OFF
(SP.B2)
Bit-2 of SP number
OFF
(PN.B0)
Bit-0 of PID number
OFF
STD
(PN.B1)
Bit-1 of PID number
OFF
(PN.B2)
Bit-2 of PID number
OFF
(MP.B0)
Bit-0 of manual preset
output number
OFF
(MP.B1)
Bit-1 of manual preset
output number
OFF
(MP.B2)
Bit-2 of manual preset
output number
OFF
(SP.BC)
Bit changing method of SP
number
0: Status switch 1
1: Status switch 2
0
STD
■ AL1-AL3 Function Registration Parameter
Menu symbol:
(ALM)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(AL1.S)
AL1 function selection
Set an I relay number. For the items
other than below, see Communication
User's Manual.
Ex.) Set the number 4353 for AL1.S
to use the alarm 1.
Set “OFF” to disable the function.
No function: OFF
Alarm 1: 4353
Alarm 2: 4354
Alarm 3: 4355
Alarm 4: 4357
AUTO (OFF) / MAN (ON) status: 4193
REM (ON) / LCL (OFF) status: 4194
STOP (ON) / RUN (OFF) status: 4195
FAIL (Normally ON) output: 4256
4353
STD
(AL2.S)
AL2 function selection
4354
(AL3.S)
AL3 function selection
4355
(OR.S)
OUT relay function
selection
OFF
(OR2.S)
OUT2 relay function
selection
OFF
■ DO Setting Parameter (E1/E4-terminal Area)
Menu symbol:
(DO)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(DO1.S)
DO11/DO41 function
selection
Same as AL1.S
Set “OFF” to disable the function
OFF
Table
below
STD
(DO2.S)
DO12/DO42 function
selection
OFF
(DO3.S)
DO43 function selection
OFF
(DO4.S)
DO44 function selection
OFF
(DO5.S)
DO45 function selection
OFF
Use the following table to record DO setting value.
Parameter
E1-terminal Area
E4-terminal Area
DO1.S
DO2.S
DO3.S
DO4.S
DO5.S
■ System Setting Parameter
Menu symbol:
(SYS)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(R.MD)
Restart mode
Set how the controller should recover
from a power failure of 5 seconds or
more.
CONT: Continue action set before
power failure.
MAN: Start from MAN.
AUTO: Start from AUTO.
CONT
STD
(R.TM)
Restart timer
Set time between power on and the
instant where controller starts compu
-
tation.
0 to 10 s
0
(EPO)
Input error preset output
Set preset output value when the
input burnout or ADC error occurs.
Manual output is prioritized when the
input burnout occurs in MAN.
0: Preset output
1: 0% output
2: 100% output
0
(FREQ)
Power frequency
AUTO, 60: 60 Hz, 50: 50 Hz
AUTO
EASY
(QSM)
Quick setting mode
OFF: Disable
ON: Enable
ON
(LANG)
Guide display language
ENG: English
FRA: French
GER: German
SPA: Spanish
Depe-
nds
on the
model
and
suffix
codes
(PASS)
Password setting
0 (No password) to 65535
0
■ Error and Version Confirmation Parameter (for display only)
Menu symbol:
(VER)
Parameter
symbol
Name of Parameter
Status record
Display
level
(PA.ER)
Parameter error status
EASY
(OP.ER)
Option error status
(AD1.E)
A/D converter error status 1
(AD2.E)
A/D converter error status 2
(PV1.E)
PV input error status
(LA.ER)
Ladder error status
(MCU)
MCU version
(DCU)
DCU version
(ECU1)
ECU-1 version (E1-terminal area)
(ECU3)
ECU-3 version (E3-terminal area)
(ECU4)
ECU-4 version (E4-terminal area)
(PARA)
Parameter version
(H.VER)
Product version
(
SER1
)
Serial number 1
(SER2)
Serial number 2
(MAC1)
MAC address 1 (E3-terminal area)
(MAC2)
MAC address 2 (E3-terminal area)
(MAC3)
MAC address 3 (E3-terminal area)
■ Parameter Display Level Parameter
Menu symbol:
(LVL)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(LEVL)
Parameter display level
EASY: Easy setting mode
STD: Standard setting mode
PRO: Professional setting mode
STD
EASY
* For Professional setting mode, see User’s Manual.
Trademarks
● Our product names or brand names mentioned in this manual are
the trademarks or registered trademarks of Yokogawa Electric Corporation.
● Adobe, Acrobat, and Postscript are either registered trademarks or trademarks
of Adobe Systems Incorporated.
● Ethernet is a registered trademark of XEROX Corporation in the United States.
● Modbus is a registered trademark of Schneider Electric.
● PROFIBUS-DP is a registered trademark of PROFIBUS User Organization.
● DeviceNet is a registered trademark of Open DeviceNet Vendor Association.
● CC-Link is a registered trademark of CC-Link Partner Association.
● We do not use the TM or ® mark to indicate these trademarks or
registered trademarks in this manual.
● All other product names mentioned in this manual are trademarks
or registered trademarks of their respective companies.
• Authorised Representative in the EEA
Yokogawa Europe BV. (Address: Euroweg 2 , 3825 HD Amersfoort, The
Netherlands) is the Authorised Representative of Yokogawa Electric Corporation
for this Product in the EEA.
• Printed Manuals
Model
Description
UT35A, UT32A Digital Indicating Controller (Panel Mounting Type) Operation Guide
«
Standard Code Model
»
IM 05P01D31-11EN
UT35A, UT32A Digital Indicating Controller (Panel Mounting Type) Operation
Guide
«
Detailed Code Model
»
IM 05P01D31-15EN
UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN Rail Mounting Type)
Operation Guide
«
Standard Code Model
»
IM 05P01D81-11EN
UT32A-D Digital Indicating Controller (Dual-loop, Panel Mounting Type)
Operation Guide
«
Standard Code Model
»
IM 05P08D31-11EN
UT32A-D/MDL Digital Indicating Controller (Dual-loop, DIN Rail Mounting Type)
Operation Guide
«
Standard Code Model
»
IM 05P08D81-11EN
UT35A/RSP, UT32A/RSP Digital Indicating Controller (Non-isolated Remote
Input, Panel Mounting Type) Operation Guide
«
Standard Code Model
»
IM 05P01D31-81EN
UT32A Digital Indicating Controller Operation Guide
«
Entry Model
»
IM 05P01F31-11EN
Precautions on the Use of the UTAdvanced Series
IM 05P01A01-11EN
• Electronic Manuals
You can download the latest manuals from the following website:
URL: http://www.yokogawa.com/ns/ut/im/
Model
Description
UT35A, UT32A Digital Indicating Controller (Panel Mounting Type) Operation Guide
«
Standard Code Model
»
IM 05P01D31-11EN
UT35A, UT32A Digital Indicating Controller (Panel Mounting Type) Operation
Guide
«
Detailed Code Model
»
IM 05P01D31-15EN
UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN Rail Mounting Type)
Operation Guide
«
Standard Code Model
»
IM 05P01D81-11EN
UT35A/UT32A Digital Indicating Controller User’s Manual
IM 05P01D31-01EN
UT32A-D Digital Indicating Controller (Dual-loop, Panel Mounting Type)
Operation Guide
«
Standard Code Model
»
IM 05P08D31-11EN
UT32A-D/MDL Digital Indicating Controller (Dual-loop, DIN Rail Mounting Type)
Operation Guide
«
Standard Code Model
»
IM 05P08D81-11EN
UT32A-D, UT32A-D/MDL Digital Indicating Controller User’s Manual
IM 05P08D31-01EN
UT35A/RSP, UT32A/RSP Digital Indicating Controller (Non-isolated Remote
Input, Panel Mounting Type) Operation Guide
«
Standard Code Model
»
IM 05P01D31-81EN
UT32A Digital Indicating Controller Operation Guide
«
Entry Model
»
IM 05P01F31-11EN
UT32A Digital Indicating Controller User’s Manual
«
Entry Model
»
IM 05P01F31-01EN
UTAdvanced Series Communication Interface (RS-485, Ethernet) User’s Manual IM 05P07A01-01EN
UTAdvanced Series Communication Interface (Open Network) User’s Manual
IM 05P07A01-02EN
LL50A Parameter Setting Software Installation Manual
IM 05P05A01-01EN
LL50A Parameter Setting Software User’s Manual
IM 05P05A01-02EN
Precautions on the Use of the UTAdvanced Series
IM 05P01A01-11EN
• General Specification
Model
Description
UT35A, UT32A Digital Indicating Controller (Panel Mounting Type)
GS 05P01D31-01EN
UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN Rail Mounting Type) GS 05P01D81-01EN
UT32A-D Digital Indicating Controller (Dual-loop, Panel Mounting Type)
GS 05P08D31-01EN
UT32A-D/MDL Digital Indicating Controller (Dual-loop, DIN Rail Mounting Type) GS 05P08D81-01EN
LL50A Parameter Setting Software
GS 05P05A01-01EN
*
The last two characters of the manual number and general specification number indicate the
language in which the manual is written.