IM 05P01D31-81EN page 11/12
■
Input Range, SP Limiter Setting Parameter
Menu symbol:
(MPV)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(P.UNI)
Control PV input unit
-: No unit
C: Degree Celsius
-: No unit
- -: No unit
- - -: No unit
F: Degree Fahrenheit
Same
as PV
input
unit
STD
(P.DP)
Control PV input decimal
point position
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
Depends
on the
input type
(P.RH)
Maximum value of
control PV input range
-19999 to 30000, (P.RL<P.RH),
| P.RH - P.RL | ≤ 30000
Depends
on the
input type
(P.RL)
Minimum value of control
PV input range
Depends
on the
input type
(SPH)
SP high limit
0.0 to 100.0% of PV input range (EU),
(SPL<SPH)
100.0 %
of PV
input
range
(SPL)
SP low limit
0.0 %
of PV
input
range
■
Output Setting Parameter
Menu symbol:
(OUT)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(OT)
Output type selection
Upper two
digits
Lower two
digits
Control output or Heating-side control
output (Lower two digits)
00: OFF
01: OUT terminals (voltage pulse)
02: OUT terminals (current)
03: OUT terminals (relay)
06: OUT2 terminals (relay)
07: RET/OUT2 terminals (voltage
pulse)
08: RET/OUT2 terminals (current)
Cooling-side control output (Upper
two digits)
00: OFF
01: OUT terminals (voltage pulse)
02: OUT terminals (current)
03: OUT terminals (relay)
06: OUT2 terminals (relay)
07: RET/OUT2 terminals (voltage
pulse)
08: RET/OUT2 terminals (current)
Standard
type:
00.03
Heating/
cooling
type:
06.03
EASY
(CT)
Control output cycle time
Heating-side control
output cycle time (in
Heating/cooling control)
0.5 to 1000.0 s
30.0 s
(CTc)
Cooling-side control
output cycle time
30.0 s
(V.AT)
Automatic valve position
adjustment
OFF: Stop automatic adjustment
ON: Start automatic adjustment
OFF
(V.RS)
Valve position setting
reset
Setting V.RS to ON resets the valve
adjustment settings and causes the
indication “V.RS” to blink.
OFF
(V.L)
Fully-closed valve posi-
tion setting
Pressing the SET/ENTER key with
valve position set to the fully-closed
position by Down arrow key causes
the adjusted value to be stored. When
V.L adjustment is complete, V.L stops
blinking.
-
(V.H)
Fully-opened valve posi-
tion setting
Pressing the SET/ENTER key with
valve position set to the fully-opened
position by Up arrow key causes the
adjusted value to be stored. When V.H
adjustment is complete, V.H stops
blinking
-
(TR.T)
Valve traveling time
5 to 300 s
60 s
STD
(V.MOD)
Valve adjusting mode
0: Valve position feedback type
1: Valve position feedback type
(moves to the estimating type if a
feedback input error or break oc-
curs.)
2: Valve position estimating type
0
(RTS)
Retransmission output
type of RET
OFF: Disable
PV1: PV
SP1: SP
OUT1: OUT (Valve opening: 0 to 100
% in Position proportional control)
LPS: 15 V DC loop power supply
TSP1: Target SP
HOUT1: Heating-side OUT
COUT1: Cooling-side OUT
MV1: Position proportional output
(internal computed value)
PV: PV terminals analog input
RSP: RSP terminals analog input
PV1
EASY
(RTH)
Maximum value of
retransmission output
scale of RET
When RTS = PV1, SP1, TSP1, PV, RSP
RTL + 1 digit to 30000
-19999 to RTH - 1 digit
Decimal point position:
When RTS=PV1, SP1, or TSP1,
decimal point position is same as
that of PV input.
When RTS=PV, decimal point position
is same as that of PV input scale.
When RTS=RSP, decimal point po-
sition
is same as that of RSP input
scale.
100 %
of PV
input
range
STD
(RTL)
Minimum value of
retransmission output
scale of RET
0 %
of PV
input
range
(O1RS)
Retransmission output
type of OUT current
output
Same as RTS
OFF
(O1RH)
Maximum value of
retransmission output
scale of OUT current
output
When O1RS = PV1, SP1, TSP1, PV, RSP
O1RL + 1 digit to 30000
-19999 to O1RH - 1 digit
Decimal point position:
When O1RS=PV1, SP1, or TSP1,
decimal point position is same as
that of PV input.
When O1RS =PV, decimal point po-
sition is same as that of PV input
scale.
When O1RS =RSP, decimal point
position is same as that of RSP
input scale.
-
(O1RL)
Minimum value of
retransmission output
scale of OUT current
output
-
(OU.A)
OUT current output
range
4-20: 4 to 20 mA
0-20: 0 to 20 mA
20-4: 20 to 4 mA
20-0: 20 to 0 mA
4-20
(RET.A)
RET current output
range
4-20
■
Heater Break Alarm Setting Parameter
Menu symbol:
(HBA)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(HB1.S)
Heater break alarm-1
function selection
0: Heater current measurement
1: Heater break alarm (Heating-side)
2: Cooling-side heater break alarm
1
EASY
(HB2.S)
Heater break alarm-2
function selection
1
(HB1)
Heater break alarm-1
current setpoint
OFF, 0.1 to 300.0 Arms
OFF
(HB2)
Heater break alarm-2
current setpoint
OFF
(CT1.T)
CT1
coil winding number ratio
1 to 3300
800
(CT2.T)
CT2
coil winding number ratio
800
(HDN1)
Heater break alarm-1
On-delay timer
0.00 to 99.59 (m.s)
0.00
STD
(HDN2)
Heater break alarm-2
On-delay timer
0.00
In cases where the current transformers manufactured by U.R.D. Co., Ltd are used, set
the following value for the coil winding number ratio.
CTL-6-S-H: 800
CTL-12L-30: 3000
■
RS-485 Communication Setting Parameter (UT35A: E3-terminal
Area, UT32A: E1-terminal Area)
Menu symbol:
(R485)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(PSL)
Protocol selection
PCL: PC link communication
PCLSM: PC link communication (with
checksum)
LADR: Ladder communication
CO-M: Coordinated master station
CO-S: Coordinated slave station
MBASC: Modbus (ASCII)
MBRTU: Modbus (RTU)
CO-S1: Coordinated slave station
(Loop-1 mode)
CO-S2: Coordinated slave station
(Loop-2 mode)
P-P: Peer-to-peer communication
MBRTU
EASY
(BPS)
Baud rate
600: 600 bps
1200: 1200 bps
2400: 2400 bps
4800: 4800 bps
9600: 9600 bps
19200: 19.2k bps
38400: 38.4k bps
19200
(PRI)
Parity
NONE: None
EVEN: Even
ODD: Odd
EVEN
(STP)
Stop bit
1: 1 bit, 2: 2 bits
1
(DLN)
Data length
7: 7 bits, 8: 8 bits
8
(ADR)
Address
1 to 99
1
■
Ethernet Communication Setting Parameter (E3-terminal Area)
Menu symbol:
(ETHR)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(HSR)
High-speed response
mode
OFF, 1 to 8
1
EASY
(BPS)
Baud rate
9600: 9600 bps
19200: 19.2k bps
38400: 38.4k bps
38400
(PRI)
Parity
NONE: None
EVEN: Even
ODD: Odd
EVEN
to
(IP1 to IP4)
IP address 1 to 4
0 to 255
Initial value:
(IP1).(IP2).(IP3).(IP4) =
(192).(168).(1).(1)
See left
Table
below
to
(SM1 to SM4)
Subnet mask 1 to 4
0 to 255
Initial value:
(SM1).(SM2).(SM3).(SM4) =
(255).(255).(255).(0)
See left
Table
below
to
(DG1 to DG4)
Default gateway 1 to 4
0 to 255
Initial value:
(DG1).(DG2).(DG3).(DG4) =
(0).(0).(0).(0)
See left
Table
below
(PRT)
Port number
502, 1024 to 65535
502
(IPAR)
IP access restriction
OFF: Disable, ON: Enable
OFF
to
,
to
(1.IP1 to 1.IP4,
2.IP1 to 2.IP4)
Permitted IP address 1-1
to 1-4
Permitted IP address 2-1
to 2-4
0 to 255
Initial value:
(1.IP1).(1.IP2).(1.IP3).(1.IP4) =
(255).(255).(255).(255)
(2.IP1).(2.IP2).(2.IP3).(2.IP4) =
(255).(255).(255).(255)
See left
Table
below
(ESW)
Ethernet setting switch
Setting this parameter to “ON”
enables the Ethernet communication
parameter settings.
OFF, ON
OFF
Use the following table to record Ethernet communication setting value.
Parameter
n=1
n=2
n=3
n=4
IPn
SMn
DGn
1.IPn
2.IPn
■
PROFIBUS-DP Communication Setting Parameter (E3-terminal Area)
Menu symbol:
(PROF)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(BR)
Baud rate
9.6K: 9.6k bps
19.2K: 19.2k bps
93.75K: 93.75k bps
187.5K: 187.5k bps
0.5M: 0.5M bps
1.5M: 1.5M bps
3M: 3M bps
6M: 6M bps
12M: 12M bps
AUTO
45.45K: 45.45k bps
AUTO
EASY
(ADR)
Address
0 to 125
3
(BPS)
Baud rate
9600: 9600 bps
19200: 19.2k bps
38400: 38.4k bps
38400
(FILE)
Profile number
0 to 3
0
■
DeviceNet Communication Setting Parameter (E3-terminal Area)
Menu symbol:
(DNET)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(BR)
Baud rate
125K: 125k bps
250K: 250k bps
500K: 500k bps
125K
EASY
(ADR)
Address
0 to 63
63
(BPS)
Baud rate
9600: 9600 bps
19200: 19.2k bps
38400: 38.4k bps
38400
(FILE)
Profile number
0 to 3
0
■
CC-Link Communication Setting Parameter (UT35A: E3-terminal Area,
UT32A: E1-terminal Area)
Menu symbol:
(CC-L)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(BR)
Baud rate
156K: 156k bps
625K: 625k bps
2.5K: 2.5k bps
5M: 5M bps
10M: 10M bps
10M
EASY
(ADR)
Address
1 to 64
1
(BPS)
Baud rate
9600: 9600 bps
19200: 19.2k bps
38400: 38.4k bps
38400
(FILE)
Profile number
0 to 3 and 6
(0, 1 and 6: Ver.1.10) (2 and 3:
Ver.2.00)
0
■ Key Action Setting Parameter
Menu symbol:
(KEY)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(F1)
User function key-1
action setting
OFF: Disable
A/M: AUTO/MAN switch
R/L1: REM/LCL switch
S/R: STOP/RUN switch
AUTO: Switch to AUTO
MAN: Switch to MAN
REM1: Switch to REM
LCL1: Switch to LCL
STOP: Switch to STOP
RUN: Switch to RUN
AT: Auto-tuning
LTUP: LCD brightness UP
LTDN: LCD brightness DOWN
BRI: Adjust LCD brightness
LCD: LCD backlight ON/OFF switch
LAT: Latch release
PID: PID tuning switch
OFF
EASY
(F2)
User function key-2
action setting
OFF
(Fn)
User function key-n
action setting
PID
■ Display Function Setting Parameter
Menu symbol:
(DISP)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(PCMD)
Active color PV display
switch
0: Fixed in white
1: Fixed in red
2: Link to alarm 1 (Alarm OFF: white,
Alarm ON: red)
3: Link to alarm 1 (Alarm OFF: red,
Alarm ON: white)
4: Link to alarm 1 or 2 (Alarm OFF:
white, Alarm ON: red)
5: Link to alarm 1 or 2 (Alarm OFF:
red, Alarm ON: white)
6: PV limit (Within range: white, Out
of range: red)
7: PV limit (Within range: red, Out of
range: white)
8: SP deviation (Within deviation:
white, Out of deviation: red)
9: SP deviation (Within deviation: red,
Out of deviation: white)
10: Link to DI (ON: red, OFF: white)
0
EASY
(PCH)
PV color change high
limit
Set a display value when in PV limit
or SP deviation.
-19999 to 30000 (Set a value within
the input range.)
Decimal point position depends on
the input type.
0
(PCL)
PV color change low limit
0
(BAR1)
Bar-graph display regis-
tration
0: Disable
1: OUT, Heating-side OUT, Internal value
in Position proportional control
2: Cooling-side OUT
3: PV
4: SP
5: Deviation
6 to 16: Disable
17: Feedback input (valve opening)
18: PV terminals analog input
19: RSP terminals analog input
24: TSP
25: TSP deviation
5
(Heating
/cooling
type: 1)
STD
(BDV)
Bar-graph deviation
display band
0.0 to 100.0% of PV input range span
(EUS)
1.0 %
of PV
input
range
span
(GUID)
Guide display ON/OFF
OFF: Nondisplay, ON: Display
ON
(ECO)
Economy mode
OFF: Disable
1: Economy mode ON (All indications
except PV display OFF)
2: Economy mode ON (All indications
OFF)
3: Brightness 10 % (whole indication)
OFF
(BRI)
Brightness
(Dark) 1 to 5 (Bright)
3
EASY
(MLSD)
Least significant digital
mask of PV display
OFF: With least significant digit
ON: Without least significant digit
OFF
STD
(MKTP)
Method for least signifi-
cant digital mask of PV
display
0: Rounding, 1: Rounding-off
0
STD