 Input Range, SP Limiter Setting Parameter

Menu symbol: 

 (MPV)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(P.UNI)

Control PV input unit

-: No unit

C: Degree Celsius

-: No unit

- -: No unit

- - -: No unit

F: Degree Fahrenheit

Same 

as PV 

input 

unit

STD

(P.DP)

Control PV input decimal

point position

0: No decimal place

1: One decimal place

2: Two decimal places

3: Three decimal places

4: Four decimal places

Depends 

on the 

input type

(P.RH)

Maximum value of

control PV input range

-19999 to 30000, (P.RL<P.RH),

| P.RH - P.RL | ≤ 30000

Depends 

on the 

input type

(P.RL)

Minimum value of control

PV input range

Depends 

on the 

input type

(SPH)

SP high limit

0.0 to 100.0% of PV input range (EU), 

(SPL<SPH)

100.0 % 

of PV 

input 

range

(SPL)

SP low limit

0.0 % 

of PV 

input 

range

 

Output Setting Parameter

Menu symbol: 

 (OUT)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(OT)

Output type selection

Upper two 

digits

Lower two 

digits

Control output or Heating-side control 

output (Lower two digits)

00: OFF

01: OUT terminals (voltage pulse)

02: OUT terminals (current)

03: OUT terminals (relay)

06: OUT2 terminals (relay)

07: RET/OUT2 terminals (voltage 

pulse)

08: RET/OUT2 terminals (current)

 

Cooling-side control output (Upper 

two digits)

00: OFF

01: OUT terminals (voltage pulse)

02: OUT terminals (current)

03: OUT terminals (relay)

06: OUT2 terminals (relay)

07: RET/OUT2 terminals (voltage 

pulse)

08: RET/OUT2 terminals (current)

Standard 

type: 

00.03

 

Heating/

cooling 

type: 

06.03

EASY

(CT)

Control output cycle time

 

Heating-side control 

output cycle time (in 

Heating/cooling control)

0.5 to 1000.0 s

30.0 s

(CTc)

Cooling-side control 

output cycle time

30.0 s

(V.AT)

Automatic valve position 

adjustment

OFF: Stop automatic adjustment

ON: Start automatic adjustment

OFF

(V.RS)

Valve position setting 

reset

Setting V.RS to ON resets the valve 

adjustment settings and causes the 

indication “V.RS” to blink.

OFF

(V.L)

Fully-closed valve posi-

tion setting

Pressing the SET/ENTER key with 

valve position set to the fully-closed 

position by Down arrow key causes 

the adjusted value to be stored. When 

V.L adjustment is complete, V.L stops 

blinking.

-

(V.H)

Fully-opened valve posi-

tion setting

Pressing the SET/ENTER key with 

valve position set to the fully-opened 

position by Up arrow key causes the 

adjusted value to be stored. When V.H 

adjustment is complete, V.H stops 

blinking

-

(TR.T)

Valve traveling time

5 to 300 s

60 s

STD

(V.MOD)

Valve adjusting mode

0: Valve position feedback type

1: Valve position feedback type 

(moves to the estimating type if a 

feedback input error or break oc-

curs.)

2: Valve position estimating type 

0

(RTS)

Retransmission output 

type of RET

OFF: Disable

PV1: PV

SP1: SP

OUT1: OUT (Valve opening: 0 to 100 

% in Position proportional control)

LPS: 15 V DC loop power supply

TSP1: Target SP

HOUT1: Heating-side OUT

COUT1: Cooling-side OUT

MV1: Position proportional output 

(internal computed value)

PV: PV terminals analog input

RSP: RSP terminals analog input

PV1

EASY

(RTH)

Maximum value of 

retransmission output 

scale of RET

When RTS = PV1, SP1, TSP1, PV, RSP

 

RTL + 1 digit to 30000

 

-19999 to RTH - 1 digit 

Decimal point position:

 

When RTS=PV1, SP1, or TSP1, 

decimal point position is same as 

that of PV input.

When RTS=PV, decimal point position 

is same as that of PV input scale.

When RTS=RSP, decimal point po-

sition 

is same as that of RSP input 

scale.

100 % 

of PV 

input 

range

STD

(RTL)

Minimum value of 

retransmission output 

scale of RET 

0 % 

of PV 

input 

range

(O1RS)

Retransmission output 

type of OUT current 

output

Same as RTS

OFF

(O1RH)

Maximum value of 

retransmission output 

scale of OUT current 

output

When O1RS = PV1, SP1, TSP1, PV, RSP

 

O1RL + 1 digit to 30000

 

-19999 to O1RH - 1 digit

Decimal point position: 

 

When O1RS=PV1, SP1, or TSP1, 

decimal point position is same as 

that of PV input.

When O1RS =PV, decimal point po-

sition is same as that of PV input 

scale.

When O1RS =RSP, decimal point 

position is same as that of RSP 

input scale.

-

(O1RL)

Minimum value of 

retransmission output 

scale of OUT current 

output

-

(OU.A)

OUT current output 

range

4-20: 4 to 20 mA

0-20: 0 to 20 mA

20-4: 20 to 4 mA

20-0: 20 to 0 mA

4-20

(RET.A)

RET current output 

range

4-20

 Heater Break Alarm Setting Parameter

Menu symbol: 

 (HBA)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(HB1.S)

Heater break alarm-1 

function selection

0: Heater current measurement 

1: Heater break alarm (Heating-side)

2: Cooling-side heater break alarm

1

EASY

(HB2.S)

Heater break alarm-2 

function selection

1

(HB1)

Heater break alarm-1 

current setpoint

OFF, 0.1 to 300.0 Arms

OFF

(HB2)

Heater break alarm-2 

current setpoint

OFF

(CT1.T)

CT1 

coil winding number ratio

1 to 3300

800

(CT2.T)

CT2 

coil winding number ratio

800

(HDN1)

Heater break alarm-1 

On-delay timer

0.00 to 99.59 (m.s)

0.00

STD

(HDN2)

Heater break alarm-2 

On-delay timer

0.00

In cases where the current transformers manufactured by U.R.D. Co., Ltd are used, set 

the following value for the coil winding number ratio.

CTL-6-S-H: 800

CTL-12L-30: 3000

 RS-485 Communication Setting Parameter (UT35A: E3-terminal 

Area, UT32A: E1-terminal Area)

Menu symbol: 

 (R485)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(PSL)

Protocol selection

PCL: PC link communication

PCLSM: PC link communication (with               

checksum)

LADR: Ladder communication

CO-M: Coordinated master station

CO-S: Coordinated slave station

MBASC: Modbus (ASCII)

MBRTU: Modbus (RTU)

CO-S1: Coordinated slave station 

(Loop-1 mode)

CO-S2: Coordinated slave station 

(Loop-2 mode)

P-P: Peer-to-peer communication

MBRTU

EASY

(BPS)

Baud rate

600: 600 bps

1200: 1200 bps

2400: 2400 bps

4800: 4800 bps

9600: 9600 bps

19200: 19.2k bps

38400: 38.4k bps

19200

(PRI)

Parity

NONE: None

 

EVEN: Even

 

ODD: Odd

EVEN

(STP)

Stop bit

1: 1 bit, 2: 2 bits

1

(DLN)

Data length

7: 7 bits, 8: 8 bits

8

(ADR)

Address

1 to 99

1

■ 

Ethernet Communication Setting Parameter (E3-terminal Area)

Menu symbol: 

 (ETHR)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(HSR)

High-speed response 

mode

OFF, 1 to 8

1

EASY

(BPS)

Baud rate

9600: 9600 bps

19200: 19.2k bps

38400: 38.4k bps

38400

(PRI)

Parity

NONE: None

EVEN: Even

ODD: Odd

EVEN

 to 

(IP1 to IP4)

IP address 1 to 4

0 to 255

Initial value: 

 

(IP1).(IP2).(IP3).(IP4) = 

(192).(168).(1).(1)

See left

Table 

below

 to 

(SM1 to SM4)

Subnet mask 1 to 4

0 to 255

Initial value: 

 

(SM1).(SM2).(SM3).(SM4) = 

(255).(255).(255).(0)

See left

Table 

below

 to 

(DG1 to DG4)

Default gateway 1 to 4

0 to 255

Initial value: 

 

(DG1).(DG2).(DG3).(DG4) = 

(0).(0).(0).(0)

See left

Table 

below

(PRT)

Port number

502, 1024 to 65535

502

(IPAR)

IP access restriction

OFF: Disable, ON: Enable

OFF

 to 

,

 to 

(1.IP1 to 1.IP4,

2.IP1 to 2.IP4)

Permitted IP address 1-1 

to 1-4

Permitted IP address 2-1 

to 2-4

0 to 255

Initial value: 

 

(1.IP1).(1.IP2).(1.IP3).(1.IP4) = 

(255).(255).(255).(255)

(2.IP1).(2.IP2).(2.IP3).(2.IP4) = 

(255).(255).(255).(255)

See left

Table 

below

(ESW)

Ethernet setting switch

Setting this parameter to “ON” 

enables the Ethernet communication 

parameter settings.

OFF, ON 

OFF

Use the following table to record Ethernet communication setting value.

Parameter

n=1

n=2

n=3

n=4

IPn

SMn

DGn

1.IPn
2.IPn

 PROFIBUS-DP Communication Setting Parameter (E3-terminal Area)

Menu symbol: 

 (PROF)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(BR)

Baud rate

9.6K: 9.6k bps

19.2K: 19.2k bps

93.75K: 93.75k bps

187.5K: 187.5k bps

0.5M: 0.5M bps

1.5M: 1.5M bps

3M: 3M bps

6M: 6M bps

12M: 12M bps

AUTO

45.45K: 45.45k bps

AUTO

EASY

(ADR)

Address

0 to 125

3

(BPS)

Baud rate

9600: 9600 bps

19200: 19.2k bps

38400: 38.4k bps

38400

(FILE)

Profile number

0 to 3

0

 DeviceNet Communication Setting Parameter (E3-terminal Area)

Menu symbol: 

 (DNET)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(BR)

Baud rate

125K: 125k bps

250K: 250k bps

500K: 500k bps

125K

EASY

(ADR)

Address

0 to 63

63

(BPS)

Baud rate

9600: 9600 bps

19200: 19.2k bps

38400: 38.4k bps

38400

(FILE)

Profile number

0 to 3

0

 CC-Link Communication Setting Parameter (UT35A: E3-terminal Area, 

UT32A: E1-terminal Area)

Menu symbol: 

 (CC-L)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(BR)

Baud rate

156K: 156k bps

625K: 625k bps

2.5K: 2.5k bps

5M: 5M bps

10M: 10M bps

10M

EASY

(ADR)

Address

1 to 64

1

(BPS)

Baud rate

9600: 9600 bps

19200: 19.2k bps

38400: 38.4k bps

38400

(FILE)

Profile number

0 to 3 and 6

(0, 1 and 6: Ver.1.10) (2 and 3: 

Ver.2.00)

0

■ Key Action Setting Parameter

Menu symbol: 

 (KEY)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(F1)

User function key-1 

 

action setting

OFF: Disable

A/M: AUTO/MAN switch

R/L1: REM/LCL switch

S/R: STOP/RUN switch

AUTO: Switch to AUTO

MAN: Switch to MAN

REM1: Switch to REM

LCL1: Switch to LCL

STOP: Switch to STOP

RUN: Switch to RUN

AT: Auto-tuning

LTUP: LCD brightness UP

LTDN: LCD brightness DOWN

BRI: Adjust LCD brightness

LCD: LCD backlight ON/OFF switch

LAT: Latch release

PID: PID tuning switch

OFF

EASY

(F2)

User function key-2 

 

action setting

OFF

(Fn)

User function key-n 

 

action setting

PID

■ Display Function Setting Parameter 

Menu symbol: 

 (DISP)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(PCMD)

Active color PV display 

switch

0: Fixed in white

1: Fixed in red

2: Link to alarm 1 (Alarm OFF: white, 

Alarm ON: red)

3: Link to alarm 1 (Alarm OFF: red, 

Alarm ON: white)

4: Link to alarm 1 or 2 (Alarm OFF: 

white, Alarm ON: red)

5: Link to alarm 1 or 2 (Alarm OFF: 

red, Alarm ON: white)

6: PV limit (Within range: white, Out 

of range: red)

7: PV limit (Within range: red, Out of 

range: white)

8: SP deviation (Within deviation: 

white, Out of deviation: red)

9: SP deviation (Within deviation: red, 

Out of deviation: white)

10: Link to DI (ON: red, OFF: white)

0

EASY

(PCH)

PV color change high 

limit

Set a display value when in PV limit 

or SP deviation.

 

-19999 to 30000 (Set a value within 

the input range.)

 

Decimal point position depends on 

the input type.

0

(PCL)

PV color change low limit

0

(BAR1)

Bar-graph display regis-

tration

0: Disable

1: OUT, Heating-side OUT, Internal value 

in Position proportional control

2: Cooling-side OUT

3: PV

4: SP

5: Deviation

6 to 16: Disable

17: Feedback input (valve opening)

18: PV terminals analog input

19: RSP terminals analog input

24: TSP

25: TSP deviation

5

(Heating

/cooling 

type: 1)

STD

(BDV)

Bar-graph deviation 

display band

0.0 to 100.0% of PV input range span 

(EUS)

1.0 % 

of PV 

input 

range 

span

(GUID)

Guide display ON/OFF

OFF: Nondisplay, ON: Display

ON

(ECO)

Economy mode

OFF: Disable

1: Economy mode ON (All indications 

except PV display OFF)

2: Economy mode ON (All indications 

OFF)

3: Brightness 10 % (whole indication)

OFF

(BRI)

Brightness

(Dark) 1 to 5 (Bright)

3

EASY

(MLSD)

Least significant digital 

mask of PV display

OFF: With least significant digit

 

ON: Without least significant digit

OFF

STD

(MKTP)

Method for least signifi-

cant digital mask of PV 

display

0: Rounding, 1: Rounding-off

0

STD

Summary of Contents for UT32A/RSP

Page 1: ...rman French and Spanish are available for the guide display 2 The LP option can be specified in the combination of Type 2 code any of 0 or 1 and Type 3 code any of 0 or 1 3 The HA option can be specified only when the Type 1 code is 0 or 2 4 When the CT option is specified the UT35A does not conform to the safety standards UL and CSA and CE marking Products with CT option are not intended for EEA ...

Page 2: ...input for com putation etc Number of inputs See the table of Model and Suffix Codes Input type instrument range and measurement accuracy See the table below Input Type Instrument Range Accuracy Standard signal 0 400 to 2 000 V 0 2 of instrument range 1 digit 1 000 to 5 000 V 0 1 of instrument range 1 digit DC voltage 0 000 to 2 000 V 0 2 of instrument range 1 digit 0 00 to 10 00 V 0 1 of instrumen...

Page 3: ...ires for wiring For RTD input use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires Since the control output relay has a life span resistance load of 100 000 times use the auxiliary relay to perform ON OFF control The use of inductance L loads such as auxiliary relays motors and solenoid valves causes malfunction or relay f...

Page 4: ... Relay contact output NC NO COM Contact rating 250 V AC 3 A 30 V DC 3 A resistance load 111 301 302 303 304 305 306 307 308 309 310 311 312 201 202 203 204 205 206 207 208 210 101 102 103 104 105 106 107 108 109 110 211 212 Current voltage pulse output 0 20 mA DC 4 20 mA DC Voltage pulse 12 V Heating cooling control output Suffix code Type 1 2 Cooling side control output Heating cooling relay cont...

Page 5: ...ntrol type setup Input output setup Valve position adjustment Use Quick setting function Position proportional type Position proportional type For Position proportional type 3 Quick Setting Function Setting of Input and Output The Quick setting function is a function to easily set the basic function of the control ler Turn on the controller to start the Quick setting function This function allows ...

Page 6: ...RM menu is displayed 1 2 3 4 5 The parameter AL1 alarm 1 type is displayed Press the SET ENTER key Press the SET ENTER key 5 6 Energized De energized Latch action Stand by action The alarm 1 type setpoint 02 PV low limit is registered After the setup is completed press the DISPLAY key or DISP key once to return to the Operation Display Symbol To change the alarm type change the last 2 digits of th...

Page 7: ... User s Manual IM 05P01D31 01EN The MAN lamp goes off which means that the auto tuning completed normally 5 6 7 8 The setting range is 1 to 4 represent group numbers or R To perform auto tuning for the PID of group 1 set the parameter AT to 1 To quit the auto tuning set the parameter to OFF During auto tuning The MAN lamp blinks The OUT symbol appears The output values at 100 0 and 0 appear altern...

Page 8: ...ystem data and hardware of extended function Nonresponding communication between hardware of extended function E1 to E4 terminal areas Faulty Contact us for repair Normal indication Normal indication Rightmost decimal point on PV display blinks Setup parameter PA ER Calibration value error Initialized to calibrated default value because of corrupted factory default value Faulty Contact us for repa...

Page 9: ...Without Stand by action 0 PV low limit 02 Table below EASY Alarm type 2 digits 00 Disable 01 PV high limit 02 PV low limit 03 SP high limit 04 SP low limit 05 Deviation high limit 06 Deviation low limit 07 Deviation high and low limits 08 Deviation within high and low limits 09 Target SP high limit 10 Target SP low limit 11 Target SP deviation high limit 12 Target SP deviation low limit 13 Target ...

Page 10: ...re not described in this manual See User s Manual IM 05P01D31 01EN Control Function Setting Parameter Menu symbol CTL Parameter symbol Name of Parameter Setting Range Initial value User setting Display level CNT Control type PID PID control ONOF ON OFF control 1 point of hysteresis ONOF2 ON OFF control 2 points of hysteresis 2P2L Two position two level control H C Heating cooling control PID or H ...

Page 11: ...cation with checksum LADR Ladder communication CO M Coordinated master station CO S Coordinated slave station MBASC Modbus ASCII MBRTU Modbus RTU CO S1 Coordinated slave station Loop 1 mode CO S2 Coordinated slave station Loop 2 mode P P Peer to peer communication MBRTU EASY BPS Baud rate 600 600 bps 1200 1200 bps 2400 2400 bps 4800 4800 bps 9600 9600 bps 19200 19 2k bps 38400 38 4k bps 19200 PRI ...

Page 12: ...error status LA ER Ladder error status MCU MCU version DCU DCU version ECU1 ECU 1 version E1 terminal area ECU3 ECU 3 version E3 terminal area ECU4 ECU 4 version E4 terminal area PARA Parameter version H VER Product version SER1 Serial number 1 SER2 Serial number 2 MAC1 MAC address 1 E3 terminal area MAC2 MAC address 2 E3 terminal area MAC3 MAC address 3 E3 terminal area Parameter Display Level Pa...

Reviews: