Configure calculated Temperature Coefficient (TC).
Follow routing
Commissioning>> Measurement setup>>
Commissioning>> Measurement setup>>
Temp.compensation>>
Temp.compensation>>
T.C.
Enter the temperature coefficient calculated from the
following formula:
A. Calculation of Temperature Coefficient Factor
( With known conductivity at reference temperature).
.
α
= Temperature compensation factor in %/°C
T
= Measured temperature in °C
Kt
= Conductivity at T
Tref
= Reference temperature
Kref
= Conductivity at Tref
T
K t
α
T
K t
α
T
K t
α
0
0.54
1.8
60
1.76
2.2
130
3.34
2.2
10
0.72
1.9
70
1.99
2.2
140
3.56
2.2
20
0.90
2.0
80
2.22
2.2
150
3.79
2.2
25
1.0
---
90
2.45
2.2
160
4.03
2.2
30
1.10
2.0
100
2.68
2.2
170
4.23
2.2
40
1.31
2.0
110
2.90
2.2
180
4.42
2.2
50
1.53
2.1
120
3.12
2.2
190
4.61
2.2
200
4.78
2.2
11-1. Appendix 1
Temperature compensation
The conductivity of a solution is very dependent on temperature. Typically for every 1 °C
change in temperature the solution conductivity will change by approximately 2 %. The
effect of temperature varies from one solution to another and is determined by several
factors like solution composition, concentration and temperature range. A coefficient (
α
) is
introduced to express the amount of temperature influence in % change in conductivity/°C.
In almost all applications this temperature influence must be compensated before the
conductivity reading can be interpreted as an accurate measure of concentration or purity.
NaCl or standard temperature compensation
From the factory the EXAxt is set with the default of a general temperature compensation
function based on a Sodium Chloride (table salt) solution. This is suitable for many
applications and is compatible with the NaCl compensation functions of typical laboratory
or portable instruments. SC temperature compensation.
36
IM 12D7B4-E-H
K
t
- K
ref
100
K
ref
α
=
T - T
ref
Table 5-1. NaCl-compensation according to IEC 746-3 with Tref = 25 °C
X
11. APPENDICES
Summary of Contents for SC150
Page 2: ......
Page 20: ...IM 12D7B4 E H 14...
Page 21: ...IM 12D7B4 E H 15 5 MENU STRUCTURE COMMISSIONING...
Page 35: ...IM 12D7B4 E H 29 Time Span x 1 hour Temperature Concentration...
Page 49: ...IM 12D7B4 E H 43...
Page 50: ...IM 12D7B4 E H 44...
Page 56: ...QIS 12D7B4 E H 50...